User Manual
Chapter 13 Option
13 - 9
“
A
” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
A095
Acc1 to
Acc2
frequency
transition
point
Output frequency at which Accel1
switches to Accel2, range is 0.00 to
400.00 Hz
0.00
← ←
Hz
A295
Acc1 to
Acc2
frequency
transition
point, 2
nd
motor
0.00
← ←
Hz
A096
Dec1 to
Dec2
frequency
transition
point
Output frequency at which Decel1
switches to Decel2, range is 0.0 to
400.0 Hz
0.00
← ←
Hz
A296
Dec1 to
Dec2
frequency
transition
point, 2
nd
motor
0.00
← ←
Hz
A097
Acceleratio
n curve
selection
Set the characteristic curve of Acc1 and
Acc2, five options:
00linear
01S-curve
02U-curve
03Inverse U-curve
00
← ←
A098
Deceleratio
n curve
selection
Set the characteristic curve of Dec1 and
Dec2, options are same as above (A097)
00
← ←
A131
Acceleratio
n curve
constant
Range is 1 to 10.
2
← ←
A132
Deceleratio
n curve
constant
Range is 1 to 10.
2
← ←
A141
A input
select for
calculate
function
Seven options:
00Operator
01VR
02Terminal [O/OI] input
04RS485
00
← ←
A142
B input
select for
calculate
function
Seven options:
00Operator
01VR
02Terminal [O/OI] input
04RS485
02
← ←
A143
Calculation
symbol
Calculates a value based on the A input
source (A141 selects) and B input source
(A142 selects).
Three options:
00ADD (A input + B input)
01SUB (A input - B input)
02MUL (A input * B input)
00
← ←
A145
ADD
frequency
An offset value that is applied to the
output frequency when the [ADD] terminal
is ON.
Range is 0.00 to 400.00 Hz
0.00
← ←
Hz