User Manual

Chapter 13 Option
13 - 11
“b” Function
Run
Mode
Edit
Default
s
Func.
Code
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
b001
Restart
mode on
power
failure /
under-vol
tage trip
Select inverter restart method,
Four option codes:
00Alarm output after trip, no automatic restart
01Restart at 0Hz
02Resume operation after frequency
matching
03Resume previous freq. after freq.
matching, then decelerate to stop and
display trip info
00
b002
Allowable
under-vol
tage
power
failure
time
The amount of time a power input under-voltage
can occur without tripping the power failure
alarm. Range is 0.3 to 25 sec. If under-voltage
exists longer than this time, the inverter trips,
even if the restart mode is selected.
1.0
s
b003
Retry
wait time
before
motor
restart
Time delay after under-voltage condition goes
away, before the inverter runs motor again.
Range is 0.3 to 100.0 seconds.
1.0
s
b004
Instantan
eous
power
failure /
under-vol
tage trip
alarm
enable
Three option codes:
00Disable
01Enable
02Disable during stop and
decelerates to a stop
00
b005
Number
of restarts
on power
failure /
under-vol
tage trip
events
Two option codes:
00Restart 16 times
01Always restart
00
b007
Restart
frequency
threshold
Restart the motor from 0Hz if the frequency
becomes less than this set value during the
motor is coasting, range is 0.00 to 400.00Hz
0.50
Hz
b008
Restart
mode on
over
voltage /
over
current
trip
Select inverter restart method,
Four option codes:
00Alarm output after trip, no automatic restart
01Restart at 0Hz
02Resume operation after frequency
matching
03Resume previous freq. after active freq.
matching, then decelerate to stop and
display trip info
00
b010
Number
of retry
on over
voltage /
over
current
trip
Range is 1 to 3 times
3