User Manual

Chapter 13 Option
13 - 19
“C” Function
Run
Mod
e
Edit
Defaults
Func.
Code
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
C001
Input [1] function
Select input terminal [1] function, 34
options (see next section)
00
[FW]
C002
Input [2] function
Select input terminal [2] function, 34
options (see next section)
01
[RV]
C003
Input [3] function
Select input terminal [3] function, 34
options (see next section)
02
[CF1]
C004
Input [4] function
Select input terminal [4] function, 34
options (see next section)
03
[CF2]
C005
Input [5] function
Select input terminal [5] function, 34
options (see next section)
18
[RS]
C011
Input [1] active
state
Select logic conversion, two option
codes:
00normally open [NO]
01normally closed [NC]
00
C012
Input [2] active
state
00
C013
Input [3] active
state
00
C014
Input [4] active
state
00
C015
Input [5] active
state
00
C021
Output [11]
function
27 programmable functions available for
logic (discrete) outputs
(see next section)
01
[FA1]
C026
Alarm relay
function
27 programmable functions available for
logic (discrete) outputs
(see next section)
05
[AL]
C027
[FM] terminal
selection
(Pulse/PWM
output)
9 programmable functions:
00Output frequency (PWM)
01Output current (PWM)
03Output frequency (Pulse train)
04Output voltage (PWM)
05Input power (PWM)
06Electronic thermal load ratio (PWM)
07LAD frequency (PWM)
08Output current (Pulse train)
10Heat sink temperature (PWM)
07
C030
Digital current
monitor reference
value
Current with digital current monitor
output at 1,440Hz
Range is 20%~200% of rated current
Rated
current
A
C031
Output [11] active
state
Select logic conversion, two option
codes:
00normally open [NO]
01normally closed [NC]
00
C036
Alarm relay active
state
01
C038
Output mode of
low current
detection
Two option codes:
00During acceleration, deceleration
and constant speed
01During constant speed only
01
C039
Low current
detection level
Set the level of low load detection, range
is 0.00 to 2.00*inverter rated current
Rated
current
A
C040
Output mode of
overload warning
Two option codes:
00During accel., decel. and constant
speed
01During constant speed only
01
C041
Overload warning
level
Sets the overload warning signal level
between 0% and 200% (from 0 to two
time the rated current of the inverter)
Rated
current
x 1.15
A