User Manual
Chapter 13 Option
13 - 20
“C” Function
Run
Mod
e
Edit
Defaults
Func.
Code
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
C241
Overload warning
level, 2
nd
motor
Rated
current
x 1.15
← ←
A
C042
Frequency arrival
setting for
acceleration
Sets the frequency arrival setting
threshold for the output frequency during
acceleration,
range is 0.00 to 400.00 Hz
0.00
← ←
Hz
C043
Frequency arrival
setting for
deceleration
Sets the frequency arrival setting
threshold for the output frequency during
deceleration,
range is 0.00 to 400.00 Hz
0.00
← ←
Hz
C044
PID deviation level
Sets the allowable PID loop error
magnitude (absolute value), SP-PV,
range is 0.0 to 100%
3.0
← ←
%
C052
PID FBV output
high limit
When the PV exceeds this value, the
PID loop turns OFF the PID second
stage output, range is 0.0 to 100%
100.0
← ←
%
C053
PID FBV output
low limit
When the PV goes below this value, the
PID loop turns ON the PID second stage
output, range is 0.0 to 100%
0.0
← ←
%
C061
Electronic thermal
warning level
Set range is 0 to 100%
Setting 0 means disabled.
90
← ←
%
C063
Zero speed
detection level
Set range is 0.00 to 100.00Hz
0.00
← ←
Hz
C064
Heat sink overheat
warning
Set range is 0 to 110 C
100.
← ←
C
C070
Selection of
OPE/Modbus
00 (OPE) / 01 (Modbus)
00
← ←
C071
Communication
speed
Five option codes:
044,800 bps
059,600 bps
0619,200 bps
0738,400 bps
05
← ←
bps
C072
Modbus address
Set the address of the inverter on the
network. Range is 1 to 247
1.
← ←
C074
Communication
parity
Three option codes:
00No parity
01Even parity
02Odd parity
00
← ←
C075
Communication
stop bit
Two option codes:
011 bit
022 bit
01
← ←
C076
Communication
error select
Selects inverter response to
communications error.
Five options:
00Trip
01Decelerate to a stop and trip
02Disable
03Free run stop (coasting)
04Decelerates to a stop
02
← ←
C077
Communication
error time-out
Sets the communications watchdog
timer period.
Range is 0.00 to 99.99 seconds.
0.0 = disabled
0.00
← ←
s
C078
Communication
wait time
Time the inverter waits after receiving a
message before it transmits.
Range is 0. to 1000. m seconds.
0.
← ←
ms