User Manual

Chapter 13 Option
13 - 27
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
A012
([O/OI] end
FQ)
[O/OI] input active
range end frequency
The output
frequency
corresponding to the
analog input range
ending point,
range is 0.0 to
400.00
0.00
Hz
A013
([O/OI]
start %)
[O/OI] input active
range start voltage
The starting point
(offset) for the active
analog input range,
range is 0. to 100.
0.
%
A014
([O/OI] end %)
[O/OI] input active
range end voltage
The ending point
(offset) for the active
analog input range,
range is 0. to 100.
100.
%
A015
([O/OI] start
FQ select)
[O/OI] input start
frequency enable
Two options; select
codes:
00Use offset
(A011 value)
01Use 0Hz
01
A016
(Analog-in
filter)
Analog input filter
Range n = 1 to 31,
1 to 31 :•2ms filter
31. 8 31 Spl.
A019
(Multispeed
select)
Multi-speed operation
selection
Select codes:
00...Binary
operation
(8 speeds selectable
with 3 terminals)
01...Bit operation
(4 speeds selectable
with 3
terminals)
00
A020
(Multispeed 0)
Multi-speed freq. 0
Defines the first
speed of a
multi-speed profile,
range is 0.00 / start
frequency to 400.0
A020 = Speed 0
(1st motor)
0.00
Hz
A220
(Multispeed
0-M2)
Multi-speed freq. 0,
2
nd
motor
Defines the first
speed of a
multi-speed profile
or a 2nd motor,
range is 0.00 / start
frequency to 400.0
A220 = Speed 0
(2nd motor)
0.00
Hz
A021
to
A027
(Multispeed 1
to
Multispeed 7)
Multi-speed freq. 1 to 7
(for both motors)
Defines 7 more
speeds,
range is 0.00 / start
frequency to 400.0.
A021=Speed 1
~A027=Speed7
See next
row
Hz
A021
60.00 50.00
50.00
Hz
A022
40.00 35.00
35.00
Hz
A023
20.00
Hz
A024~ A027
0.00
Hz