User Manual

Chapter 13 Option
13 - 29
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
A045
(V/F gain)
V/f gain
Sets voltage gain of
the inverter, range is
20 to 100%
100.
%
A245
(V/F gain-M2)
V/f gain, 2
nd
motor
100.
%
A046
(A.TQ-BST V
gain)
Voltage compensation
gain for automatic
torque boost
Sets voltage
compensation gain
under automatic
torque boost, range
is 0 to 255
100.
A246
(A.TQ-BST V
gain-M2)
Voltage compensation
gain for automatic
torque boost, 2
nd
motor
100.
A047
(A.TQ-BST SL
gain)
Slip compensation gain
for automatic torque
boost
Sets slip
compensation gain
under automatic
torque boost, range
is 0 to 255
100.
A247
(A.TQ-BST SL
gain-M2)
Slip compensation gain
for automatic torque
boost, 2
nd
motor
100.
A051
(DB enable)
DC braking enable
Three options;
select codes:
00Disable
01Enable during
stop
02Frequency
detection
00
A052
(DB
Frequency)
DC braking frequency
The frequency at
which DC braking
begins,
range is 0.00to
60.00Hz
0.50
Hz
A053
(DB wait time)
DC braking wait time
The delay from the
end of controlled
deceleration to start
of DC braking
(motor free runs
until DC braking
begins),
range is 0.0 to 5.0
seconds.
0.0
s
A054
(DB force)
DC braking force for
deceleration
Level of DC braking
force, settable from
0 to 100%
50.
%
A055
(DB decel
time)
DC braking time for
deceleration
Sets the duration for
DC braking, range is
from 0.0 to 10.0
seconds.
0.5
s
A056
(DB input
select)
DC braking / edge or
level detection for [DB]
input
Two options; select
codes:
00Edge detection
01Level detection
01
A057
(DB force
start)
DC braking force at
start
Level of DC braking
force at start,
settable from 0 to
100%
0.
%