User Manual
Chapter 13 Option
13 - 34
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
A141
(A-input
calc.FQ)
A input select for
calculate function
Seven options:
00Operator
01VR
02Terminal [O/OI]
input
04RS485
00
← ←
A142
(B-input
calc.FQ)
B input select for
calculate function
Seven options:
00Operator
01VR
02Terminal [O/OI]
input
04RS485
02
← ←
A143
(Calculation
symbol)
Calculation symbol
Calculates a value
based on the A input
source (A141
selects) and B input
source
(A142selects).
Three options:
00ADD (A input +
B input)
01SUB (A input -
B input)
02MUL (A input *
B input)
00
← ←
A145
(Add
frequency)
ADD frequency
An offset value that
is applied to the
output frequency
when the [ADD]
terminal is ON.
Range is 0.00 to
400.00 Hz
0.00
← ←
Hz
A146
(Add
direction)
ADD direction select
Two options:
00Plus (adds
A145 value to the
output frequency
setting)
01Minus
(subtracts A145
value from the
output frequency
setting)
00
← ←
A154
(Decel hold
FQ)
Deceleration hold
frequency
Sets the frequency
to hold deceleration,
range is 0.00 to
400.00Hz
0.00
← ←
Hz
A155
(Decel hold
time)
Deceleration hold time
Sets the duration of
deceleration hold,
range is 0.0 to 60.0
seconds.
0.0
← ←
s
A156
(PID sleep
level)
PID sleep function
action threshold
Sets the threshold
for the action, set
range 0.00 to
400.00 Hz
0.00
← ←
Hz