Chapter 13 Option
13 - 36
“b” Function
Run
Mode
Edit
Default
s
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Uni
t
s
b001
(Restart
mode UV)
Restart mode on
power failure /
under-voltage trip
Select inverter restart
method,
Four option codes:
00Alarm output after
trip, no automatic restart
01Restart at 0Hz
02Resume operation
after frequency matching
03Resume previous
freq. after freq. matching,
then decelerate to stop
and display trip info
00
b002
(Allowable
UV time)
Allowable
under-voltage power
failure time
The amount of time a
power input
under-voltage can occur
without tripping the power
failure alarm. Range is
0.3 to 25.0 sec. If
under-voltage exists
longer than this time, the
inverter trips, even if the
restart mode is selected.
1.0
s
b003
(Retry wait
time UV)
Retry wait time
before motor restart
Time delay after
under-voltage condition
goes away, before the
inverter runs motor again.
Range is 0.3 to 100.0
seconds.
1.0
s
b004
(UV trip on
stop)
Instantaneous power
failure /
under-voltage trip
alarm enable
Three option codes:
00Disable
01Enable
02Disable during stop
and decelerates to a stop
00
b005
(No. of restar
t
UV)
Number of restarts
on power failure /
under-voltage trip
events
Two option codes:
00Restart 16 times
01Always restart
00
b007
(Restart
min.FQ)
Restart frequency
threshold
Restart the motor from
0Hz if the frequency
becomes less than this
set value during the motor
is coasting, range is 0.00
to 400.00Hz
0.50
Hz