User Manual

Chapter 13 Option
13 - 37
“b” Function
Run
Mode
Edit
Default
s
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Uni
t
s
b008
(Restart
mode
OV/OC)
Restart mode on
over voltage / over
current trip
Select inverter restart
method,
Four option codes:
00Alarm output after
trip, no automatic restart
01Restart at 0Hz
02Resume operation
after frequency matching
03Resume previous
freq. after active freq.
matching, then decelerate
to stop and display trip
info
00
b010
(No. of restar
t
OV/OC)
Number of retry on
over voltage / over
current trip
Range is 1 to 3 times
3
b011
(Retry wait
time OV/OC)
Retry wait time on
over voltage / over
current trip
Range is 0.3 to 100.0 sec.
1.0
s
b012
(E.Thermal
Level)
Level of electronic
thermal
Set a level between 20%
and 100% for the rated
inverter current.
Rated
current
for each
inverter
model *1
A
b212
(E.Thermal
Level-M2)
Level of electronic
thermal,
2
nd
motor
A
b013
(E.Thermal
Character)
Electronic thermal
characteristic
Select from three curves,
option codes:
00Reduced torque
01Constant torque
02Free setting
01
b213
(E.Thermal
Charact-M2)
Electronic thermal
characteristic, 2
nd
motor
01
b015
(Free
E.Thermal
FQ-1)
Free setting
electronic thermal
~freq.1
Range is 0 to b017 Hz
0
Hz
b016
(Free
E.Thermal
I-1)
Free setting
electronic thermal
~current1
Range is 0.00 to inverter
rated current Amps
0.00
A
b017
(Free
E.Thermal
FQ-2)
Free setting
electronic thermal
~freq.2
Range is b015 to b019 Hz
0
Hz
b018
(Free
E.Thermal
I-2)
Free setting
electronic thermal
~current2
Range is 0.00 to inverter
rated current Amps
0.00
A