User Manual
Chapter 13 Option
13 - 41
“b” Function
Run
Mode
Edit
Default
s
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Uni
t
s
b070
(Discon
Level)
Operation level at
O/OI disconnection
Set range, 0 to 100%, or
“no” (ignore)
no
← ←
-
b078
(Clear kWh
data)
Watt-hour clearance
Two option codes:
00OFF
01ON (press STR then
clear)
00
← ←
-
b079
(kWh display
gain)
Watt-hour display
gain
Set range is,
1to1000
1.
← ←
b082
(Start
Frequency)
Start frequency
Sets the starting
frequency for the inverter
output, range is 0.01 to
9.99 Hz
0.50
← ←
Hz
b083
(Carrier
Frequency)
Carrier frequency
Sets the PWM carrier
(internal switching
frequency), range is 2.0
to 15.0 kHz
2.0
← ←
kH
z
b084
(Initialize
Mode)
Initialization mode
(parameters or trip
history)
Select initialized data,
four option codes:
00Initialization disabled
01Clears Trip history
02Initializes all
Parameters
03Clears Trip history
and initializes all
parameters
00
← ←
b085
(Initial data
select)
Country for
initialization
Select default parameter
values for country on
initialization, two option
codes:
00Mode 0
01Mode 1
03Mode 3
00
03
01
b086
(FQ scale
factor)
Frequency scaling
conversion factor
Specify a constant to
scale the displayed
frequency for d007
monitor, range is 0.01 to
99.99
1.00
← ←
b087
(STOP key
enable)
STOP key enable
Select whether the STOP
key on the keypad is
enabled, three option
codes:
00Enabled
01Disabled always
02 Disabled for stop
00
← ←
b088
(Restart after
FRS)
Restart mode after
FRS
Selects how the inverter
resumes operation when
free-run stop (FRS) is
cancelled, two options:
00Restart from 0Hz
01Restart from
frequency detected from
real speed of motor (freq.
matching)
00
← ←