User Manual

Chapter 13 Option
13 - 42
“b” Function
Run
Mode
Edit
Default
s
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Uni
t
s
b089
(Auto.Carrier
reduce)
Automatic carrier
frequency reduction
Three option codes:
00Disabled
01Enabled, depending
on the output current
02Enabled, depending
on the heat-sink
temperature
00
b091
(Stop mode
select)
Stop mode selection
00(Dec and Stop) /
01(FRS)
00
b094
(Initial target
data)
Initialization target
data setting
00(ALL parameters)/
01(expect terminal
andcommunication data)
00
b100
(Free V/F
-F1)
Free V/F setting,
freq.1
Set range, 0 ~ value of
b102
0.
Hz
b101
(Free V/F
-V1)
Free V/F setting,
voltage.1
Set range, 0.0 ~ 300.0V
0.0
V
b102
(Free V/F
-F2)
Free V/F setting,
freq.2
Set range, value of b100
~b104
0.
Hz
b103
(Free V/F
-V2)
Free V/F setting,
voltage.2
Set range, 0.0 ~ 300.0V
0.0
V
b104
(Free V/F
-F3)
Free V/F setting,
freq.3
Set range, value of b102
~b106
0.
Hz
b105
(Free V/F
-V3)
Free V/F setting,
voltage.3
Set range, 0.0 ~ 300.0V
0.0
V
b106
(Free V/F
-F4)
Free V/F setting,
freq.4
Set range, value of b104
~b108
0.
Hz
b107
(Free V/F
-V4)
Free V/F setting,
voltage.4
Set range, 0.0 ~ 300.0V
0.0
V
b108
(Free V/F
-F5)
Free V/F setting,
freq.5
Set range, value of b108~
b110
0.
Hz
b109
(Free V/F
-V5)
Free V/F setting,
voltage.5
Set range, 0.0 ~ 300.0V
0.0
V
b110
(Free V/F
-F6)
Free V/F setting,
freq.6
Set range, value of b108
b112
0.
Hz
b111
(Free V/F
-V6)
Free V/F setting,
voltage.6
Set range, 0.0 ~ 300.0V
0.0
V