User Manual

Chapter 6 Operation
6 - 14
(B) Method to perform driving with the dedicated operator (NES1-OP)
*same applies to external Operator (OPE-S/SR/SBK,OPE-SR mini)
(1) Setting the operation command and Frequency command by operator (*Must be set by the operator.)
How to drive by key operation of the Dedicated operator.
Setup
Function Name Code Data Note
Frequency source A001 02(Operator)
Run command source A002 02(Operator) Run command LED light up
Output frequency
setting
F001 0.0 to A004(Max frequency)
default is 0.00Hz.
Keypad RUN key
routing
F004 00(Forward) / 01(Reverse) Can not be changed during
operation
The initial value of the acceleration and deceleration time is 10 seconds. Please change the following
parameters as necessary.
Function Name
Code Setting Range Note
Acceleration time (1) F002 0.00 to 3600 seconds Initial value : 10.00 seconds
Deceleration time (1) F003 0.00 to 3600 seconds Initial value : 10.00 seconds
The control circuit terminal block wiringNo connect
Operation
Please be operated in accordance with section 6.7.

Source is set “VR”, this LED is lit.
RUN key was pressed and started
operation this LED is lit.
A
fter set to 02(A002).
RUN key is vaild.
This LED is lit.