User Manual

Chapter 7 Explanation of Functions
7 - 24
7.5.4 Start frequency setting
The start frequency setting function allows you to specify the inverter output frequency that the inverter
initially outputs when an operation command is input.
Use this function mainly to adjust the start torque.
If the start frequency (b082) is set too high, the inverter will start the motor with a full voltage, which will
increase the start current. Such status may trigger the overload restriction operation or make the inverter
prone to easily tripping because of the overcurrent protection.
Item Function code Range of data Description
Start frequency
adjustment
b082 0.01 to 9.99 (Hz) Setting of the start frequency
7.5.5 Reduced voltage start function
The reduced voltage start function enables you to make the inverter increase the output voltage gradually
when starting the motor.
Set a small value for the reduced voltage start selection (b036) if you intend to increase the start torque.
On the other hand, setting a small value will cause the inverter to perform full-voltage starting and to easily
trip because of overcurrent.
Item Function code Range of data Description
Reduced voltage start
selection
b036
00 Disabling the reduced voltage starting
01 to 250
01: Short (about 4 ms)
250: Long (about 1000ms)
00 01 250
・・・
Reduced Voltage Start
b036
Start frequency
b082
FW
Output frequency
Output voltage
FW
Output frequency
Output voltage
b082