Function List
Monitoring and Main Profile Parameters
A Group: Standard Functions
: Allowed
[
X
: Not allowed
]
The parameter tables in this chapter have a column titled "Run Mode Edit." An Ex mark x means the parameter cannot be edited; a Check mark
means the parameter can be edited. The table example to the right contains two adjacent marks "x ". These two marks (that can also be
"xx" or "
") correspond to low-access or high-access levels to Run Mode edits (note Lo and Hi in column heading).Parameter shown in
case "b037" is "00" (Full display).
: Allowed
[
X
: Not allowed
]
Function Code Name Range Default Unit
Run mode edit
Lo Hi
Basic
setting
A001 Frequency source setting
00(Keypad potentiometer)/01 (control circuit terminal block)/02 (digital operator)/03
(Modbus)/10 (operation function result)
01
-
X X
A201 Frequency source setting, 2nd motor 01
-
X X
A002 Run command source setting
01(control circuit terminal block)/02 (digital operator)/03 (Modbus)
01
-
X X
A202 Run command source setting, 2nd motor 01
-
X X
A003 Base frequency setting 30.0 to "maximum frequency(1st)" 60.0 Hz
X X
A203 Base frequency setting, 2nd motor 30.0 to "maximum frequency(2st)" 60.0 Hz
X X
A004 Maximum frequency setting "Base frequency(1st)" to 400.0 60.0 Hz
X X
A204 Maximum frequency setting, 2nd motor "Base frequency(2st)" to 400.0 60.0 Hz
X X
Analog input
setting
A011 [O/OI] input active range start frequency 0.00 to 99.99/100.0 to 400.0 0.00 Hz
X
A012 [O/OI] input active range end frequency 0.00 to 99.99/100.0 to 400.0 0.00 Hz
X
A013 Aanalog input active range start voltage 0 to 100 0. %
X
A014 Aanalog input active range end voltage 0 to 100 100. %
X
A015 Aanalog input start frequency enable 00(use set value)/01(use 0 Hz) 01
-
X
A016 Analog input filter 1 to 30 or 31 (500 ms filter ±0.1 Hz with hysteresis) 31. Spl
X
Multi-speed
and jogging
A019 Multi-speed operation selection 00(Binary mode)/01(Bit mode) 00
-
X X
A020 Multi-speed frequency setting (0)
0.0/start freq. to maximum freq.
0.00 Hz
A220 Multi-speed frequency (2nd), setting 2nd motor 0.00 Hz
A021 Multi-speed frequency setting (1) 60.00 Hz
A022 Multi-speed frequency setting (2) 40.00 Hz
A023 Multi-speed frequency setting (3) 20.00 Hz
A024 Multi-speed frequency setting (4) 0.00 Hz
A025 Multi-speed frequency setting (5) 0.00 Hz
A026 Multi-speed frequency setting (6) 0.00 Hz
A027 Multi-speed frequency setting (7) 0.00 Hz
A038 Jog frequency Start frequency to 9.99 6.00 Hz
A039 Jog stop mode
00 (free-running after jogging stops [disabled during operation])/01 (deceleration and
stop after jogging stops [disabled during operation])/02 (DC braking after jogging stops
[disabled during operation])/03 (free-running after jogging stops [enabled during
operation])/04 (deceleration and stop after jogging stops [enabled during operation])/05
(DC braking after jogging stops [enabled during operation])
04
-
X
V/f
Characteristic
A041 Torque boost select 00(Manual)/01(Automatic) 00
-
X X
A241 Torque boost select 2nd motor 00(Manual)/01(Automatic) 00
-
X X
A042 Manual torque boost value 0.0 to 20.0 1.0 %
A242 Manual torque boost value, 2nd motor 0.0 to 20.0 1.0 %
A043 Manual torque boost frequency adjustment 0.0 to 50.0 5.0 %
A243
Manual torque boost frequency adjustment, 2nd motor
0.0 to 50.0 5.0 %
Function Code Name Range Default Unit
Run mode edit
Lo Hi
Monitor
d001 Output frequency monitoring 0.00 to 99.99/100.0 to 400.0
-
Hz
d002 Output current monitor 0.0 to 6553.5
-
A
- -
d003 Rotation direction monitor F(Forward)/o(Stop)/r(Reverse)
- - - -
d004 PID feedback monitoring
0.00 to 99.99 in steps of 0.01 / 100.0 to 999.9 in steps of 0.1
1000. to 9999. in steps of 1
1000 to 9999 in steps of 10 / 100 to 999 in units of 1000
- - - -
d005 Intelligent input terminal status
- - - -
d006 Intelligent output terminal status
- - - -
d007 Scaled output frequency monitoring
0.00 to 99.99/100.0 to 999.9/1000. to 9999./1000 to 3999
- -
d013 Output voltage monitor 0.0 to 600.0
-
V
- -
d014 Power monitoring 0 to 999.9
-
kW
- -
d015 Cumulative power monitoring
0.0 to 999.9 in steps of 1 kW/h, or the unit set for function "b079"
1000 to 9999 in units of 10 kW/h, or the unit set for function "b079"
100 to 999 in units of 1000 kW/h, or the unit set for function "b079"
- - - -
d016 Cumulative operation RUN time monitoring
0. to 9999. in units of 1 hour
1000 to 9999 in units of 10 hours
100 to 999 in units of 1,000 hours
-
hr
- -
d017 Cumulative power-on time monitoring
0. to 9999. in units of 1 hour
1000 to 9999 in units of 10 hours
100 to 999 in units of 1,000 hours
-
hr
- -
d018 Heat sink temperature monitoring -020. to 120.0
-
˚C
- -
d050 Dual Monitoring display the monitoring data selected by b160, b161
- - - -
d080 Trip counter
0. to 9999. in units of 1 trip
1000 to 6553 in units of 10 trips
-
time
- -
d081 Trip monitor 1
Displays trip event information
- - - -
d082 Trip monitor 2
- - - -
d083 Trip monitor 3
- - - -
d084 Trip monitor 4
- - - -
d085 Trip monitor 5
- - - -
d086 Trip monitor 6
- - - -
d090 Warning monitoring Warning code
- -
X X
d102 DC voltage monitoring 0.0 to 999.9/1000.
-
V
X X
d104 Electronic thermal overload monitoring 0.0 to 100.0
-
%
X X
Main Profile
Parameters
F001 Output frequency setting
0.0,start frequency to Maximum frequency(1st/2st)
0.0 to 100.0(%)(PID function on time )
0.00 Hz
F002 Acceleration time (1)
0.00 to 99.99/100.0 to 999.9/1000. to 3600.
10.00 s
F202 Acceleration time (1),2nd motor 10.00 s
F003 Deceleration time (1)
0.00 to 99.99/100.0 to 999.9/1000. to 3600.
10.00 s
F203 Deceleration time (1),2nd motor 10.00 s
F004 Keypad Run key routing 00(Forward)/01(Reverse) 00
-
X X