Chapter 7 Explanation of Functions
7 - 46
7.6.4 Forcible-operation from terminal (F-TM) function
The forcible-operation function allows you to forcibly enable the inverter operation via control circuit
terminals when the control circuit terminal block is not selected as the device to input frequency and
operation commands. An intelligent input terminal is used to turn this function on and off.
When the intelligent input terminal to which the forcible-terminal operation function is assigned is off,
frequency and operation commands are input from the devices selected by functions "A001" and "A002".
When the terminal is on, the device to input frequency and operation commands is forcibly switched to the
control circuit terminal block.
If the input device is switched while the inverter is operating, the current operation command is canceled
and the inverter stops the output. When restarting the inverter operation, turn off the operation command
that was to be entered from each input device for safety's sake, and then enter a new operation command.
When use it together with (OPE) function, (OPE) function is given priority.
Item Function code Data Description
Terminal function C001 to C005 51 F-TM: Forcible-terminal operation
7.6.5 Action selection in case of external operator disconnection [b165]
When the inverter detects a disconnection with the operator(Operator communication is cut off for five
seconds or more.), inverter operation is subject to (b165).
Item Function code Data Description
Ex. operator com. loss action b165
00 TripE40.x
01 Trip after Deceleration stopE40.x
02 Disregard
03 Free-run stop
04 Deceleration stop
7.6.6 Initial-screen selection (selection of the initial screen to be displayed after power-on)
The initial-screen selection function allows you to specify the screen that is displayed on the digital
operator immediately after the inverter power is turned on. The table below lists the screens (items)
selectable. (The factory setting is "01" [d001].)
Item Function code Data Description
Initial-screen selection b038
000
Func. code that SET key pressed last displayed.
(*1)
001 to 060
d001 to d060
(set value(***) is the monitor No. (d***) )
201 F001 (output frequency setting)
202
B display of LCD operator
(In case of Digital operator, same (000) setting)
(*1):(Example) If the inverter power is turned off immediately after the setting of "b038" has been changed,
the monitor will display "b038" as the initial screen after the next power-on.