User Manual
Chapter 8 Communication Functions
8 - 24
ii) List of warning data
Modbus
data
Operator
display
Condition
1
Frequency upper limit setting (A061) >Maximum frequency setting (A004)
2
Frequency lower limit setting (A062) >Maximum frequency setting (A004)
3
Output frequency setting (F001),
multispeed 0 (A020) (note 1)
> Maximum frequency setting (A004)
10
Output frequency setting (F001),
multispeed 0 (A020) (note 1)
> Frequency upper limit setting (A061)
17
Fequency lower limit setting (A062) >
Output frequency setting (F001), multispeed 0
(A020) (note 1)
23
Start frequency adjustment (b082) >Frequency upper limit setting (A061)
25
Start frequency adjustment (b082) >Fequency lower limit setting (A062)
27
Start frequency adjustment (b082) >
Output frequency setting (F001), multispeed 0
(A020) (note 1)
30
Start frequency adjustment (b082) >Jog frequency setting (A038)
31
Output frequency setting (F001),
multispeed 0 (A020) (note 1)
=
Jump (center) frequency settings 1/2/3 ± " Jump
(hysteresis) frequency width settings 1/2/3"
A063 ± A064, A065 ± A066, A067 ± A068
33
Multispeed 1 to 7 settings (A021 to
A027)
=
34
Free-setting V/f frequency (7) (b112) <Frequency upper limit setting (A061)
36
Free-setting V/f frequency (7) (b112) <Fequency lower limit setting (A062)
38
Free-setting V/f frequency (7) (b112) <
Output frequency setting (F001), multispeed 0
(A020) (note 1)
5
Frequency upper limit setting (A261) >Maximum frequency setting (A204)
6
Frequency lower limit setting (A262) >Maximum frequency setting (A204)
7
Output frequency setting (F001),
multispeed 0 (A220) (note 1)
> Maximum frequency setting (A204)
14
Output frequency setting (F001),
multispeed 0 (A220) (note 1)
> Frequency upper limit setting (A261)
21
Fequency lower limit setting (A262) >
Output frequency setting (F001), multispeed 0
(A220) (note 1)
24
Start frequency adjustment (b082) >Frequency upper limit setting (A261)
26
Start frequency adjustment (b082) >Fequency lower limit setting (A262)
28
Start frequency adjustment (b082) >
Output frequency setting (F001), multispeed 0
(A220) (note 1)
32
Output frequency setting (F001),
multispeed 0 (A220) (note 1)
=
Jump (center) frequency settings 1/2/3 ± " Jump
(hysteresis) frequency width settings 1/2/3"
A063 ± A064, A065 ± A066, A067 ± A068
35
Free-setting V/f frequency (7) (b112) <Frequency upper limit setting (A261)
37
Free-setting V/f frequency (7) (b112) <Fequency lower limit setting (A262)
39
Free-setting V/f frequency (7) (b112) <
Output frequency setting (F001), multispeed 0
(A220) (note 1)
Note) The warning data of the Modbus communication do not accord with the warning cord of the
operator.