Chapter 9 Error Codes
9 - 5
9.3 Warning Codes for Digital operator
The warning code for Digital operator is follows.
It is not displayed with the standard panel.
The inverter displays a warning code when the data set as a target function code satisfies the condition
(specified in the Condition column) in relation to the data set as the corresponding basic function code.
Warning
code
Condition
Frequency upper limit setting (A061) > Maximum frequency setting (A004)
Frequency lower limit setting (A062) > Maximum frequency setting (A004)
Output frequency setting (F001),
multispeed 0 (A020) (note 1)
> Maximum frequency setting (A004)
Output frequency setting (F001),
multispeed 0 (A020) (note 1)
> Frequency upper limit setting (A061)
Fequency lower limit setting (A062) >
Output frequency setting (F001), multispeed 0 (A020)
(note 1)
Start frequency adjustment (b082) > Frequency upper limit setting (A061)
Start frequency adjustment (b082) > Fequency lower limit setting (A062)
Start frequency adjustment (b082) >
Output frequency setting (F001), multispeed 0 (A020)
(note 1)
Start frequency adjustment (b082) > Jog frequency setting (A038)
Output frequency setting (F001),
multispeed 0 (A020) (note 1)
=
Jump (center) frequency settings 1/2/3 ± " Jump
(hysteresis) frequency width settings 1/2/3"
A063 ± A064, A065 ± A066, A067 ± A068
Multispeed 1 to 7 settings (A021 to
A027)
=
Free-setting V/f frequency (7) (b112) < Frequency upper limit setting (A061)
Free-setting V/f frequency (7) (b112) < Fequency lower limit setting (A062)
Free-setting V/f frequency (7) (b112) <
Output frequency setting (F001), multispeed 0 (A020)
(note 1)
Frequency upper limit setting (A261) > Maximum frequency setting (A204)
Frequency lower limit setting (A262) > Maximum frequency setting (A204)
Output frequency setting (F001),
multispeed 0 (A220) (note 1)
> Maximum frequency setting (A204)
Output frequency setting (F001),
multispeed 0 (A220) (note 1)
> Frequency upper limit setting (A261)
Fequency lower limit setting (A262) >
Output frequency setting (F001), multispeed 0 (A220)
(note 1)
Start frequency adjustment (b082) > Frequency upper limit setting (A261)
Start frequency adjustment (b082) > Fequency lower limit setting (A262)
Start frequency adjustment (b082) >
Output frequency setting (F001), multispeed 0 (A220)
(note 1)
Output frequency setting (F001),
multispeed 0 (A220) (note 1)
=
Jump (center) frequency settings 1/2/3 ± " Jump
(hysteresis) frequency width settings 1/2/3"
A063 ± A064, A065 ± A066, A067 ± A068
Free-setting V/f frequency (7) (b112) < Frequency upper limit setting (A261)
Free-setting V/f frequency (7) (b112) < Fequency lower limit setting (A262)
Free-setting V/f frequency (7) (b112) <
Output frequency setting (F001), multispeed 0 (A220)
(note 1)
Note1)These parameters are checked, even when the digital operator (02) is not specified for the frequency source
setting (A001).