User Manual
Chapter 13 Option
13 - 10
“
A
” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
A146
ADD
direction
select
Two options:
00Plus (adds A145 value to the output
frequency setting)
01Minus (subtracts A145 value from the
output frequency setting)
00
← ←
A154
Deceleratio
n hold
frequency
Sets the frequency to hold deceleration,
range is 0.00 to 400.00Hz
0.00
← ←
Hz
A155
Deceleratio
n hold time
Sets the duration of deceleration hold,
range is 0.0 to 60.0 seconds.
0.0
← ←
s
A156
PID sleep
function
action
threshold
Sets the threshold for the action, set
range 0.00 to 400.00 Hz
0.00
← ←
Hz
A157
PID sleep
function
action
delay time
Sets the delay time for the action, set
range 0.0 to 25.5 seconds.
0.0
← ←
s
A158
PID sleep
function
return
threshhold
A156 to 400.0(Hz)
0.00
← ←
Hz
A161
[VR] input
active
range start
frequency
The output frequency corresponding to
the analog input range starting point,
range is 0.00 to 400.00 Hz
0.00
← ←
Hz
A162
[VR] input
active
range end
frequency
The output frequency corresponding to
the current input range ending point,
range is 0.00 to 400.00 Hz
0.00
← ←
Hz
A163
[VR] input
active
range
start %
The starting point (offset) for the current
input range,
range is 0. to 100.%
0.
← ←
%
A164
[VR] input
active
range
end %
The ending point (offset) for the current
input range,
range is 0. to 100.%
100.
← ←
%
A165
[VR] input
start
frequency
select
Two options; select codes:
00Use offset (A161 value)
01Use 0Hz
01
← ←