User Manual

Chapter 13 Option
13 - 16
“b” Function
Run
Mode
Edit
Default
s
Func.
Code
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
b088
Restart
mode
after FRS
Selects how the inverter resumes operation
when free-run stop (FRS) is cancelled,
two options:
00Restart from 0Hz
01Restart from frequency detected from real
speed of motor (freq. matching)
00
b089
Automati
c carrier
frequency
reduction
Three option codes:
00Disabled
01Enabled, depending on the output current
02Enabled, depending on the heat-sink
temperature
00
b091
Stop
mode
selection
00(Dec and Stop) / 01(FRS)
00
b094
Initializati
on target
data
setting
00(ALL parameters)/ 01(expect terminal
andcommunication data)
00
b100
Free V/F
setting,
freq.1
Set range, 0 ~ value of b102
0.
Hz
b101
Free V/F
setting,
voltage.1
Setrange,0.0to300.0V(200Vclass),
0.0 to 600V(400Vclass)
0.0
V
b102
Free V/F
setting,
freq.2
Set range, value of b100 ~b104
0.
Hz
b103
Free V/F
setting,
voltage.2
Setrange,0.0to300.0V(200Vclass),
0.0 to 600V(400Vclass)
0.0
V
b104
Free V/F
setting,
freq.3
Set range, value of b102 ~b106
0.
Hz
b105
Free V/F
setting,
voltage.3
Setrange,0.0to300.0V(200Vclass),
0.0 to 600V(400Vclass)
0.0
V
b106
Free V/F
setting,
freq.4
Set range, value of b104 ~b108
0.
Hz
b107
Free V/F
setting,
voltage.4
Setrange,0.0to300.0V(200Vclass),
0.0 to 600V(400Vclass)
0.0
V
b108
Free V/F
setting,
freq.5
Set range, value of b108 ~b110
0.
Hz
b109
Free V/F
setting,
voltage.5
Setrange,0.0to300.0V(200Vclass),
0.0 to 600V(400Vclass)
0.0
V
b110
Free V/F
setting,
freq.6
Set range, value of b108~b112
0.
Hz
b111
Free V/F
setting,
voltage.6
Setrange,0.0to300.0V(200Vclass),
0.0 to 600V(400Vclass)
0.0
V