User Manual

Chapter 13 Option
13 - 17
“b” Function
Run
Mode
Edit
Default
s
Func.
Code
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
b112
Free V/F
setting,
freq.7
Set range, b110 ~ 400
0.
Hz
b113
Free V/F
setting,
voltage.7
Setrange,0.0to300.0V(200Vclass),
0.0 to 600V(400Vclass)
0.0
V
b130
Decelerat
ion
overvolta
ge
suppressi
on enable
00Disabled
01Enabled
02Enabled with accel.
03when CONST/DEC
00
b131
Decel.
overvolt.
suppress
level
DC bus voltage of suppression. Range is:
200V class330 to 390
400V class660 to 780
360/
720
V
b132
Decel.
overvolt.
suppress
const.
Accel. rate when b130=02.
Set range: 0.10 ~ 30.00 seconds.
1.00
s
b133
Decel.
overvolt.
suppress
proportio
nal gain
Proportional gain when b130=01. Range is:
0.00 to 5.00
0.20
b134
Decel.
overvolt.
suppress
integral
time
Integration time when b130=01. Range is: 0.0 to
150.0 seconds.
1.0
s
b150
Display
ex.operat
or
connecte
d
When an external operator is
connected via RS-422 port, the
built-in display is locked and shows
only one "d" parameter configured
in:001 ~ 050
001
b160
1st
paramete
r of Dual
Monitor
Set any two "d" parameters in b160
and b161, then they can be monitored
in d050. The two parameters are
switched by up/down keys.
Set range: 001 ~ 018
001
b161
2nd
paramete
r of Dual
Monitor
002
b163
Frequenc
y set in
monitorin
g
Two option codes:
00Freq. set disabled
01Freq. set enabled
01
b164
Automati
c return
to the
initial
display
10 min. after the last key operation, display
returns to the initial parameter set by b038. Two
option codes:
00Disable
01Enable
00
b165
Ex.
operator
com. loss
action
Five option codes:
00Trip
01Trip after deceleration to a stop
02Ignore
03Coasting (FRS)
04Decelerates to a stop
02