User Manual

Chapter 13 Option
13 - 34
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
A141
(A-input
calc.FQ)
A input select for
calculate function
Seven options:
00Operator
01VR
02Terminal [O/OI]
input
04RS485
00
A142
(B-input
calc.FQ)
B input select for
calculate function
Seven options:
00Operator
01VR
02Terminal [O/OI]
input
04RS485
02
A143
(Calculation
symbol)
Calculation symbol
Calculates a value
based on the A input
source (A141
selects) and B input
source
(A142selects).
Three options:
00ADD (A input +
B input)
01SUB (A input -
B input)
02MUL (A input *
B input)
00
A145
(Add
frequency)
ADD frequency
An offset value that
is applied to the
output frequency
when the [ADD]
terminal is ON.
Range is 0.00 to
400.00 Hz
0.00
Hz
A146
(Add
direction)
ADD direction select
Two options:
00Plus (adds
A145 value to the
output frequency
setting)
01Minus
(subtracts A145
value from the
output frequency
setting)
00
A154
(Decel hold
FQ)
Deceleration hold
frequency
Sets the frequency
to hold deceleration,
range is 0.00 to
400.00Hz
0.00
Hz
A155
(Decel hold
time)
Deceleration hold time
Sets the duration of
deceleration hold,
range is 0.0 to 60.0
seconds.
0.0
s
A156
(PID sleep
level)
PID sleep function
action threshold
Sets the threshold
for the action, set
range 0.00 to
400.00 Hz
0.00
Hz