User Manual

Chapter 13 Option
13 - 46
“C” Function
Ru
n
Mo
d
e
Edi
t
Defaults
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Uni
t
s
C027
([FM] Function)
[FM] terminal
selection
(Pulse/PWM output)
9 programmable
functions:
00Output
frequency (PWM)
01Output current
(PWM)
03Output
frequency (Pulse
train)
04Output voltage
(PWM)
05Input power
(PWM)
06Electronic
thermal load ratio
(PWM)
07LAD frequency
(PWM)
08Output current
(Pulse train)
10Heat sink
temperature (PWM)
07
C030
(Digital I Ref.)
Digital current
monitor reference
value
Current with digital
current monitor
output at 1,440Hz
Range is
20%~200% of rated
current
Rated
current
A
C031
(Output [11]
actv.state)
Output [11] active
state
Select logic
conversion, two
option codes:
00normally open
[NO]
01normally closed
[NC]
00
C036
(Alarm RLY active
state)
Alarm relay active
state
01
C038
(LOC out mode
select)
Output mode of low
current detection
Two option codes:
00During
acceleration,
deceleration and
constant speed
01During constant
speed only
01
C039
(LOC out level)
Low current
detection level
Set the level of low
load detection,
range is 0.00 to
2.00*inverter rated
current
Rated
current
A
C040
(Overload warn
mode)
Output mode of
overload warning
Two option codes:
00During accel.,
decel. and constant
speed
01During constant
speed only
01
C041
(Overload warn
level)
Overload warning
level
Sets the overload
warning signal level
between 0% and
Rated
current
x 1.15