Output Function Summary Table – This table shows all functions for the logical outputs (terminals [11]
and [AL]) at a glance. Detailed descriptions of these functions, related parameters and settings, and
example wiring diagrams are in “Using Intelligent Output Terminals” in chapter 4.
Output Function Summary Table
Option
Code
Termina
l
Symbol
Function Name Description
00
RUN Run Signal ON When the inverter is in Run Mode
OFF When the inverter is in Stop Mode
01
FA1 Frequency Arrival
Type 1–Constant
Speed
ON When output to motor is at the set frequency
OFF
When output to motor is OFF, or in any acceleration
or deceleration ramp
02
FA2 Frequency Arrival
Type 2–Over
frequency
ON
When output to motor is at or above the set freq.,
even if in accel () or decel () ramps
OFF
When output to motor is OFF, or at a level below the
set frequency
03
OL Overload Advance
Notice Signal 1
ON
When output current is more than the set threshold
() for the overload signal
OFF
When output current is less than the set threshold for
the deviation signal
04
OD Output Deviation for
PID Control
ON
When PID error is more than the set threshold for the
deviation signal
OFF
When PID error is less than the set threshold for the
deviation signal
05
AL Alarm Signal
ON
When an alarm signal has occurred and has not been
cleared
OFF
When no alarm has occurred since the last cleaning
of alarm(s)
06
FA3 Frequency Arrival
Type 3–Set
frequency
ON
When output to motor is at the set frequency, during
accel () and decel ().
OFF
When output to motor is OFF, or is not at a level of the
set frequency
09
UV Undervoltage ON Inverter is in Undervoltage
OFF Inverter is not in Undervoltage
11
RNT Run Time Expired
ON
Total running time of the inverter exceeds the
specified value
OFF
Total running time of the inverter does not exceed the
specified value
12
ONT Power ON time
Expired
ON
Total power ON time of the inverter exceeds the
specified value
OFF
Total power ON time of the inverter does not exceed
the specified value
13
THM Thermal Warning
ON
Accumulated thermal count exceeds the  set
value
OFF
Accumulated thermal count does not exceed the
 set value
21
ZS Zero Hz Speed
Detection Signal
ON
Output frequency falls below the threshold specified
in 
OFF
Output frequency is higher than the threshold
specified in 
27
ODc Analog Voltage
Input Disconnect
Detection
ON
When the [O] input value <  setting (signal loss
detected)
OFF
When no signal loss is detected
31
FBV PID Second Stage
Output ON
Transitions to ON when the inverter is in RUN Mode
and the PID Process Variable (PV) is less than the
Feedback Low Limit ()
OFF
Transitions to OFF when the PID Process Variable
(PV) exceeds the PID High Limit (), and
transitions to OFF when the inverter goes from Run