User Manual

Chapter 6 Operation
6 - 12
(2) Method to perform driving in RUN/STOP/RESET key and perform frequency setting in volume
resistor
This is the operation method using Run command is given by "RUN/STOP/RESET key" &
Frequency setting is given by analog input such as O-L voltage, Accel&Decel time is 10 seconds. (If
you don't need to change such as Accel&Decel time, optional Operator is not required.) Below
diagram is to set the external Freq. setting connecting H-O-L volume to supply O-L voltage.
Setup
Function Name Code Data Note
Frequency source A001 01Control circuit terminals Default
The initial value of Acceleration/ Deceleration time is 10sec.
Please change the following parameters as needed.
Function Name Code Setting Range Note
Acceleration time F002 0.00 to 3600 sec. default10 sec.
Deceleration time F003 0.00 to 3600 sec. default10 sec.
* One of the following is required when changing parameters on NE-S1 series inverters.
a) Dedicated operator (NES1-OP) b) Digital operator c) 5-line LCD operator
d) Modbus e) PC programming tool (ProDriveNext)
Control circuit terminals wiring (Sink logic)
P24PLC L O/OI H
Frequency setting
resistor
Note)
The above is a method to perform
analog input(O/OI) by voltage input. It
is necessary for SW6 on the board to
be set for volta
g
e in
p
ut
(
default
)
.