Chapter 7 Explanation of Functions
7 - 12
7.3 Setting the intelligent I/O terminal function
7.3.1 Intelligent input terminal setting
You can assign the functions described below to intelligent in put terminals [1] to [5]. To assign the desired
functions to the terminals, specify the desired data listed in the table below for terminal settings "C001" to
"C005". For example, "C001" corresponds to intelligent input terminal [1].
You can select the a-contact or b-contact input for individual intelligent input terminals.
You can assign one function only to an intelligent input terminal. If you have attempted to assign a function
to two or more intelligent input terminals, the function is assigned to only the terminal to which you have
last attempted assignment. Function data "NO" (no assign) is assigned to other terminals, and those
terminals are ineffective in terms of functions.
After assigning the desired functions to intelligent input terminals [1] to [5], confirm that the assigned
functions have been stored on the inverter.
Function code Data Description Reference item Page
C001 to C005
00 FW: Forward RUN command Operation command
01 RV: Reverse RUN command Operation command
02 CF1: Multispeed 1 setting (binary operation)
Multispeed operation function (Binary) 7-28
03 CF2: Multispeed 2 setting (binary operation)
04 CF3: Multispeed 3 setting (binary operation)
06 JG: Jogging Jogging operation function 7-25
07 DB: External DC braking DC braking (external DC braking) function 7-41
08 SET: Set 2nd motor data 2nd motor control function 7-40
09 2CH: 2-stage acceleration/deceleration 2-stage acceleration/deceleration function 7-29
11 FRS: Free-run stop Free-run stop function 7-56
12 EXT: External trip External trip function 7-66
13 USP: Unattended start protection Unattended start protection function 7-57
15 SFT: Software lock (control circuit terminal block) Software lock function 7-45
18 RS: Reset Reset 7-55
20 STA: Starting by 3-wire input
3-wire input function 7-23
21 STP: Stopping by 3-wire input
22 F/R: Forward/reverse switching by 3-wire input
23 PID: PID disable
PID function 7-34
24 PIDC: PID reset
27 UP: Remote control UP function
Remote control (UP/DWN) function (bit) 7-32
28 DWN: Remote control DOWN function
29 CLR: Remote control data clearing
31 OPE: Forcible operation Forcible-operation function 7-45
32 SF1: Multispeed 1 setting (bit operation)
Multispeed operation function 7-28
33 SF2: Multispeed 2 setting (bit operation)
34 SF3: Multispeed 3 setting (bit operation)
39 OLR: Overload restriction selection Overload restriction function 7-63
50 ADD: Trigger for frequency addition (A145) Frequency addition function 7-32
51 F-TM: Forcible-terminal operation Forcible-terminal operation function 7-46
53 KHC: Cumulative power clearance Cumulative power monitoring function 7-3
65 AHD: Analog command holding Analog command holding function 7-17
83 HLD:Retatin output frequency Retatin output frequency function 7-27
84 ROK:Permission of Run command Permission of Run command function 7-27
86 DISP:Display limitation Display limitation function 7-47
no NO: Allocation none - -
7.3.2 Input terminal a/b (NO/NC) selection
The input terminal a/b (NO/NC) selection function allows you to specify a-contact or b-contact input for
each of the intelligent input terminals [1] to [5].
An a-contact turns on the input signal when closed and turns it off when opened.
An b-contact turns on the input signal when opened and turns it off when closed.
The terminal to which the reset (RS) function is assigned functions only as an a-contact.
Item Function code Data Description
Terminal active state C011 to C015
00 a-contact (NO)
01 b-contact (NC)