Brochure

8
Function List
A Group: Standard Functions
: Allowed
[
X
: Not allowed
]
Function Code Name Range Default Unit
Run mode edit
Lo Hi
V/f
Characteristic
A044 V/f characteristic curve selection 00(VC)/01(VP)/02(free V/ f ) 00 -
X X
A244 V/f characteristic curve selection, 2nd motor 00(VC)/0(VP)/02(free V/ f ) 00 -
X X
A045 V/f gain
20. to 100.
100. %
A245 V/f gain, 2nd motor 100. %
A046
Voltage compensation gain for automatic torque boost
0. to 255.
100.
-
A246
Voltage compensation gain for automatic torque boost, 2nd motor
100.
-
A047
Slip compensation gain for automatic torque boost
0. to 255.
100.
-
A247
Slip compensation gain for automatic torque boost,
2nd motor
100.
-
DC braking
A051 DC braking enable 00(Disable)/01(Enable)/02(output freq < [A052]) 00
-
X
A052 DC braking frequency setting 0.00 to 60.00 0.50 Hz
X
A053 DC braking wait time 0.0 to 5.0 0.00 s
X
A054 DC braking force during deceleration 0 to 100 50 %
X
A055 DC braking time for deceleration 0.0 to 10.0 0.5 s
X
A056
DC braking / edge or level detection for [DB] input
00(Edge)/01(Level) 01
-
X
A057 DC braking force at start 0. to 100. 0. %
X
A058 DC braking time at start 0.0 to 10.0 0.0 s
X
A059 Carrier frequency during DC braking 2.0 to 15.0 2.0 kHz
X
Frequency
Upper/Lower
Limit
and
Jump
Frequency
A061 Frequency upper limit setting 0.00/Freq. lower limit setting to maximum freq. 0.00 Hz
X
A261 Frequency upper limit setting, 2nd motor 0.00/Freq. lower limit setting (2nd) to maximum freq. (2nd) 0.00 Hz
X
A062 Frequency lower limit setting 0.00/Start freq. to freq. upper limit setting 0.00 Hz
X
A262 Frequency lower limit setting, 2nd motor 0.00/Start freq. (2nd) to freq. upper limit setting (2nd) 0.00 Hz
X
A063 Jump freq. (center) 1 0.00 to 99.99/100.0 to 400.0 0.00 Hz
X
A064 Jump (hysteresis) frequency setting 1 0.00 to 10.00 0.50 Hz
X
A065 Jump freq. (center) 2 0.00 to 99.99/100.0 to 400.0 0.00 Hz
X
A066 Jump (hysteresis) frequency setting 2 0.00 to 10.00 0.50 Hz
X
A067 Jump freq. (center) 3 0.00 to 99.99/100.0 to 400.0 0.00 Hz
X
A068
Jump (hysteresis) frequency setting 3PID Enable
0.00 to 10.00 0.50 Hz
X
A069 Acceleration hold frequency 0.00 to 99.99/100.0 to 400.0 0.00 Hz
A070 Acceleration hold time setting 0.0 to 60.0 0.0 s
X
PID Control
A071 PID Enable 00(Disable)/01(Enable)/02(Enabling inverted data output) 00
-
X
A072 PID proportional gain 0.00 to 25.00 1.00
-
A073
PID integral time constant
0.0 to 999.9/1000. to 3600. 1.0 s
A074
PID derivative time constant
0.00 to 99.99/100.0 0.00 s
A075 PV scale conversion 0.01 to 99.99 1.00
-
X
A076 PV source setting 01 (Analog1)/02(Modbus)/10 (operation result output) 01
-
X
A077 Reverse PID action 00(OFF)/01(ON) 00
-
X
A078 PID output limit 0.0 to 100.0 0.0 %
X
AVR function
A081 AVR function select
00 (always on)/ 01 (always off)/ 02 (off during deceleration)
02
-
X X
A281 AVR function select, 2nd motor 02
-
X X
A082 AVR voltage select
200V class: 200/215/220/230/240, 400V class:380/400/415/440/480
200/400 V
X X
A282 AVR voltage select, 2nd motor 200/400 V
X X
A083 AVR filter time constant 0.000 to 1.000 0.030 s
X
A084 AVR deceleration gain 50. to 200. 100. %
Automatic
Energy Saving
A085 Operation mode selection 00(Normal)/01(Energy-saver) 00
-
X X
A086 Energy saving mode tuning 0.0 to 100.0 50.0 %
Operation
mode and
acc./dec.
function
A092 Acceleration time (2)
0.00 to 99.99/100.0 to 999.9/1000. to 3600.
10.00 s
A292 Acceleration time (2),2nd motor 10.00 s
A093 Deceleration time (2)
0.00 to 99.99/100.0 to 999.9/1000. to 3600.
10.00 s
A293 Deceleration time (2),2nd motor 10.00 s
A094 Select method to switch to Acc2/Dec2 profile 00 (switching by 2CH terminal)/ 01 (switching by setting)/ 02 (Forward and reverse) 00
-
X X
A294
Select method to switch to Acc2/Dec2 profile,
2nd motor
00 (switching by 2CH terminal)/ 01 (switching by setting)/ 02 (Forward and reverse) 00
-
X X
A095 Acc1 to Acc2 frequency transition point
0.00 to 99.99/100.0 to 400.0
0.00 Hz
X X
A295
Acc1 to Acc2 frequency transition point, 2nd motor
0.00 Hz
X X
A096 Dec1 to Dec2 frequency transition point
0.00 to 99.99/100.0 to 400.0
0.00 Hz
X X
A296
Dec1 to Dec2 frequency transition point, 2nd motor
0.00 Hz
X X
A097 Acceleration curve selection 00(Linear)/01(S-curve)/ 02 (U curve)/ 03 (inverted-U curve) 00
-
X X
A098 Deceleration curve selection 00(Linear)/01(S-curve)/ 02 (U curve)/ 03 (inverted-U curve) 00
-
X X
A131
Acceleration curve constant setting (for S, U, Inverse U)
1 to 10 2
-
X
A132
Deceleration curve constant setting (for S, U, Inverse U)
1 to 10 2
-
X
Frequency
caluculation
A141 A input select for calculate function
00(Digital operator)/01(Keypad potentiometer)  
02(input via Analog1)/04 (external communication)
00
-
X
A142 B input select for calculate function 02
-
X
A143 Calculation symbol 00(A141+A142)/01(A141-A142)/02(A141× A142) 00
-
X
A145 ADD frequency 0.00 to 99.99/100.0 to 400.0 0.00 Hz
X
A146 ADD direction select 00 (frequency command + A145)/ 01(frequency command - A145) 00
-
X
A154 Deceleration hold frequency 0.00 to 99.99/100.0 to 400.0 0.00 Hz
X
A155 Deceleration hold time setting 0.0 to 60.0 0 s
X
A156 PID sleep function action threshold 0.00 to 99.99/100.0 to 400.0 0.00 Hz
X
A157 PID sleep function action delay time 0.0 to 25.5 0.0 s
X
A158 PID sleep function return threshhold 0.00 to 99.99/100.0 to 400.0 0.00 Hz
X
A161
[VR] input active range start frequency
0.00 to 99.99/100.0 to 400.0 0.00 Hz
A162
[VR] input active range end frequency
0.00 to 99.99/100.0 to 400.0 0.00 Hz
A163
[VR] input active range start %
0. to [VR] input active range end 0. %
A164
[VR] input active range end %
[VR] input active range start to 100. 100. %
A165
Option operator
input start frequency enable 00(A161)/01(0Hz) 01
-
X
b Group: Fine-tuning Functions
: Allowed
[
X
: Not allowed
]
Function Code Name Range Default Unit
Run mode edit
Lo Hi
Restart after
instantaneous
power failure
b001 Selection of automatic restart mode
00 (tripping)/ 01 (starting with 0 Hz)/ 02 (starting with matching frequency)/
03 (tripping after deceleration and stopping with matching frequency)
00
-
X
b002 Allowable under-voltage power failure time 0.3 to 25.0 1.0 s
X
b003 Retry wait time before motor restart 0.3 to 100.0 1.0 s
X
b004 Under-voltage trip alarm enable 00 (OFF)/ 01 (ON)/ 02 (disabling during stopping and decelerating to stop) 00
-
X
b005 Under-voltage trip events 00 (16 times)/ 01 (No limit) 00
-
X
b007 Restart frequency threshold 0.00 to 400.00 0.50 Hz
X
b008 Selection of retry after tripping
00 (tripping)/ 01 (starting with 0 Hz)/ 02 (starting with matching frequency)/ 03 (tripping
after deceleration and stopping with matching frequency)
00
-
X
b010 Selection of retry count after undervoltage 1 to 3 3 times
X
b011
Start frequency to be used in case of frequency pull-in restart
0.3 to 100.0 1.0 s
X