User Manual

Chapter 8 Communication Functions
8 - 31
(4) Registers (group B)
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
1301h
Restart mode on power failure /
under-voltage trip
b001 R/W
0 (tripping), 1 (starting with 0 Hz), 2
(starting with matching frequency), 3
(tripping after deceleration and stopping
with matching frequency)
-
1302h
Allowable unde
r
-voltage power
failure time
b002 R/W 3 to 250 0.1 [s]
1303h
Retry wait time before motor
restart
b003 R/W 3 to 1000 0.1 [s]
1304h
Instantaneous power
failure/under-voltage trip alarm
enable
b004 R/W
0 (disabling), 1 (enabling), 2 (disabling
during stopping and decelerating to
stop)
-
1305h
Number of restarts on power
failure/unde
r
-voltage trip events
b005 R/W 0 (16 times), 1 (unlimited) -
1306h
(Reserved) - - -
-
1307h
(Reserved) - - -
-
1308h Restart frequency threshold b007 R/W 0 to 40000 0.01 [Hz]
1309h
Restart mode on over voltage /
over current
b008 R/W
0 (tripping), 1 (starting with 0 Hz), 2
(starting with matching frequency), 3
(tripping after deceleration and stopping
with matching frequency)
-
130Ah
(Reserved) - - -
-
130Bh
Number of retry on over voltage /
over current
b010 R/W 1 to 3 1 [times]
130Ch
Retry wait time on over voltage /
over current
b011 R/W 3 to 1000 0.1 [s]
130Dh Level of electronic thermal b012 R/W 2000 to 10000 0.01 [%]
130Eh Electronic thermal characteristic b013 R/W
0 (reduced-torque characteristic), 1
(constant-torque characteristic), 2 (free
setting)
-
130Fh (Reserved) - - Inaccessible -
1310h
Free setting, electronic thermal
frequency (1)
b015 R/W 0 to 400 1 [Hz]
1311h
Free setting, electronic thermal
current (1)
b016 R/W 0 to 10000 0.01 [%]
1312h
Free setting, electronic thermal
frequency (2)
b017 R/W 0 to 400 1 [Hz]
1313h
Free setting, electronic thermal
current (2)
b018 R/W 0 to 10000 0.01 [%]
1314h
Free setting, electronic thermal
frequency (3)
b019 R/W 0 to 400 1 [Hz]
1315h
Free setting, electronic thermal
current (3)
b020 R/W 0 to 10000 0.01 [%]
1316h
Overload restriction operation
mode
b021 R/W
0 (disabling), 1 (enabling during
acceleration and constant-speed
operation), 2 (enabling during
constant-speed operation)
-
1317h Overload restriction level b022 R/W 2000 to 20000 0.01 [%]
1318h
Deceleration rate at overload
restriction
b023 R/W 1 to 30000
0.1 [s]
1319h
Overload restriction operation
mode (2)
b024 R/W
0 (disabling), 1 (enabling during
acceleration and constant-speed
operation), 2 (enabling during
constant-speed operation)
-
131Ah Overload restriction level 2 b025 R/W 2000 to 20000 0.01 [%]
131Bh
Deceleration rate at overload
restriction (2)
b026 R/W 1 to 30000
0.1 [s]
131Ch Over current suppression enable b027 R/W 0 (disabling), 1 (enabling) -
131Dh
Current level of active freq.
matching
b028 R/W 1000 to 20000 0.01 [%]
131Eh
Deceleration rate of active freq.
matching
b029 R/W 1 to 30000