Chapter 8 Communication Functions
8 - 34
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
1375h to
1384h
(Reserved) - - - -
1385h
Deceleration over voltage
suppression enable
b130 R/W
0 (disabling), 1 (enabling), 2 (enabling
with acceleration), 3(when Const/Dec)
-
1386h Decel. over volt. suppress level b131 R/W
200 V class: 330 to 390 (V)
400 V class: 660 to 780 (V)
1 [V]
1387h Decel. over volt. suppress const. b132 R/W 10 to 3000 0.01 [s]
1388h
Decel. overvolt. suppress
propotional gain
b133 R/W 0 to 500 0.01
1389h
Decel. overvolt. suppress Integ
r
al
time
b134 R/W 0 to 1500 0.1 [s]
138Ah to
1398h
(Reserved) - - - -
1399h Display ex.operator connected b150 R/W
1 to 60h(BCD) (d001 to d060)
[exe. 15h : d015]
-
139Ah to
13A2h
(Reserved) - - -
-
13A3h
1st parameter of Dual
Monitor
b160 R/W
1 to 18h(BCD) (d001 to d018)
[exe. 15h : d015]
-
13A4h
2nd parameter of Dual
Monitor
b161 R/W
1 to 18h(BCD) (d001 to d018)
[exe. 15h : d015]
-
13A5h
(Reserved) - - -
-
13A6h
Freq. set in monitoring
b163 R/W 0 (disabling), 1 (enabling) -
13A7h
Automatic return to the initial
display
b164 R/W
0 (disabling), 1 (enabling)
-
13A8h
Ex. operator com. loss action
b165 R/W
0 (tripping), 1 (tripping after
decelerating and stopping the motor), 2
(ignoring errors),
3 (stopping the motor after
free-running),
4 (decelerating and stopping the motor)
-
13A9h Data Read/Write select b166 R/W 0 (Read/Write OK) / 1 (Protected)
-
13AAh to
13B6h
(Reserved) - - -
-
13B7h
Initialization trigger
b180 R/W
0 (disabling), 1 (enabling)
-
13B8h to
1400h
unused - - Inaccessible -