Chapter 13 Option
13 - 1
13.1 Digital Operetor
Digital Operator prepares NES1-OP,OPE-S/SR/SBK/SRmini and WOP. NES1-OP can be attached to
the NES1 inverter.Other than it,be the connection with the cable.
13.1.1 Attention at the time of the data setting
When Function code display restriction(b037) are set other than "00" (all indication), some functions are
not displayed.
When Software lock mode selection (b031) is validly set, cannot change the parameter.
The function of "-" cannot change a column of "Run Mode Edit" while driving.
It becomes modifiable mode while driving when I establish Software lock mode selection (b031) in “10”
13.1.2 Monitoring mode (Display of NES1-OP,OPE-S/SR/SBK/SRmini)
The initial state displays (d001) at the time of power activation by all means. When you fix it by any
display, please change setting of (b038).
“d” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
d001
Output
frequency
monitoring
0.00 to 99.99/100.0 to 400.0 (Hz)
d002
Output current
monitoring
0.0 to 655.3 (A)
d003
Rotation
direction
monitoring
F(forward rotation) / o(stopped) /
r(reverse rotation)
d004
PID feedback
monitoring
0.00 to 99.99/100.0 to 999.9/1000. to
9999./1000 to 9999(10000 to 99990)/
100 to 999(100000 to 999000)
d005
Intelligent input
terminal status
d006
Intelligent input
terminal status
d007
Scaled output
frequency
monitoring
0.00 to 99.99/100.0 to 999.9/
1000. to 9999./1000 to 3999
d013
Output voltage
monitoring
0.0 to 600.0(V)
d014
Input power
monitoring
0.0 to 999.9(kW)
d015
Cumulative
power
monitoring
0.0 to 999.9/1000. to 9999./
1000 to 9999(10000 to 99990)/
100 to 999(100000 to 999000)
d016
Cumulative
operation RUN
time
monitoring
0. to 9999./
1000 to 9999(10000 to 99990)/
100 to 999(100000 to 999000)(hr)
d017
Cumulative
power-on time
monitoring
0. to 9999./
1000 to 9999(10000 to 99990)/
100 to 999(100000 to 999000)(hr)
d018
Heat sink
temperature
monitoring
-020. to 120.0()
Example
terminal 1,2 : ON
terminal 3 to 5 : OFF
12 3 4 5
ON
OFF
Example
terminal 11 : ON
terminal relay : OFF
ON
OFF
relay 11