User Manual

Chapter 13 Option
13 - 7
A
” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
A061
Frequency
upper limit
Sets a limit on output frequency less than
the maximum frequency (A004).
Range is from frequency lower limit
(A062) to maximum frequency (A004).
0.00 setting is disabled
>0.00 setting is enabled
0.00
Hz
A261
Frequency
upper limit,
2nd motor
Sets a limit on output frequency less than
the maximum frequency (A204).
Range is from frequency lower limit
(A262) to maximum frequency (A204).
0.00 setting is disabled
>0.00 setting is enabled
0.00
Hz
A062
Frequency
lower limit
Sets a limit on output frequency greater
than zero.
Range is start frequency (b082) to
frequency upper limit (A061)
0.00 setting is disabled
>0.00 setting is enabled
0.00
Hz
A262
Frequency
lower limit,
2nd motor
Sets a limit on output frequency greater
than zero.
Range is start frequency (b082) to
frequency upper limit (A261)
0.00 setting is disabled
>0.00 setting is enabled
0.00
Hz
A063
A065
A067
Jump freq.
(center) 1
to 3
Up to 3 output frequencies can be defined
for the output to jump past to avoid motor
resonances (center frequency)
Range is 0.00 to 400.0 Hz
0.00
0.00
0.00
Hz
A064
A066
A068
Jump freq.
width
(hysteresis)
1 to 3
Defines the distance from the center
frequency at which the jump around
occurs Range is 0.00 to 10.00 Hz
0.50
0.50
0.50
Hz
A069
Acceleratio
n hold
frequency
Sets the frequency to hold acceleration,
range is 0.00 to 400.00Hz
0.00
Hz
A070
Acceleratio
n hold time
Sets the duration of acceleration hold,
range is 0.0 to 60.0 seconds.
0.0
s
A071
PID enable
Enables PID function,
three option codes:
00PID Disable
01PID Enable
02PID Enable with reverse output
00
A072
PID
proportiona
l gain
Proportional gain has a range of
0.00 to 25.00
1.00
A073
PID integral
time
constant
Integral time constant has a range of
0.0 to 3600.0 seconds.
1.0
s
A074
PID
derivative
time
constant
Derivative time constant has a range of
0.00 to 100.00 seconds.
0.00
s
A075
PV scale
conversion
Process Variable (PV), scale factor
(multiplier), range of 0.01 to 99.99
1.00