User Manual

Chapter 13 Option
13 - 14
“b” Function
Run
Mode
Edit
Default
s
Func.
Code
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
b031
Software
lock
mode
selection
Prevents parameter changes, in five options,
option codes:
00all parameters except b031 are locked
when [SFT] terminal is ON
01all parameters except b031 and output
frequency F001 are locked
when [SFT] terminal is ON
02all parameters except b031 are locked
03all parameters except b031 and output
frequency F001 are locked
10High level access including b031
See appendix C for the accessible
parameters in this mode.
01 10 01
b034
Run/pow
er ON
warning
time
Range is,
0.:Warning disabled
1. to 9999.:
10~99,990 hrs (unit: 10)
1000 to 6553:
100,000~655,350 hrs (unit: 100)
0.
Hrs.
b035
Rotation
direction
restriction
Three option codes:
00No restriction
01Reverse rotation is restricted
02Forward rotation is restricted
00
b036
Reduced
voltage
start
selection
Set range, 0 (disabling the function), 1 (approx.
4ms) to 250 (approx. 1s)
3
b037
Function
code
display
restriction
Five option codes:
00Full display
01Function-specific display
03Data comparison display
04Basic display
05Monitor display only
00
b038
Initial
display
selection
000Func. code that SET key pressed last
displayed.(*)
001~060d001~d060 displayed
201F001displayed
202B display of LCD operator
(In case of Digital operator, same 000setting)
001
b050
Controlle
d
decelerati
on on
power
loss
Four option codes:
00Disabled
01Decelerates to a stop
02Decelerates to a stop with DC bus voltage
controlled
03Decelerates to a stop with DC bus voltage
controlled, then restart
00
b051
DC bus
voltage
trigger
level of
ctrl.
decel.
Setting of DC bus voltage to start controlled
decel. operation. Range is 0.0 to 400.0(200V
class inverter settings),0.0 to 800(400V class
inverter settings)
220.0/
440.0
V
b052
Over-volt
age
threshold
of ctrl.
decel.
Setting the OV-LAD stop level of controlled
decel. operation. Range is 0.0 to 400.0(200V
class inverter settings),0.0 to 800(400V class
inverter settings)
360.0/
720.0
V