User Manual

Chapter 13 Option
13 - 25
Note) Mark “” in [ Run Mode Edit] shows the accessible parameters when b031 is set “10”, high level access.
“F” Function
Run
Mode
Edit
Defaults
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
F001
(Set
Frequency)
Output frequency setting
Standard default
target frequency
that determines
constant motor
speed, range is
0.00 / start
frequency to
maximum
frequency (A004)
0.00 Hz
F002
(Accel.time1)
Acceleration time (1)
Standard default
acceleration,
range is 0.00 to
3600.00 seconds.
10.00 s
F202
(Accel.time1-
M2)
Acceleration time (1),
2
nd
motor
10.00 s
F003
(Decel.time1)
Deceleration time (1)
Standard default
deceleration,
range is 0.00 to
3600.00 seconds.
10.00 s
F203
(Decel.time1-
M2)
Deceleration time (1),
2
nd
motor
10.00 s
F004
(RUN key
direction)
Keypad RUN key routing
Two options;
select codes:
00Forward
01 Reverse
00