User Manual

Chapter 13 Option
13 - 33
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Units
A292
(Accel.time2-
M2)
Acceleration time (2),
2
nd
motor
acceleration, range
is:
0.00 to 3600.00
seconds.
10.00
s
A093
(Decel.time2)
Deceleration time (2)
Duration of 2
nd
segment of
deceleration, range
is:
0.00 to 3600.00
seconds.
10.00
s
A293
(Decel.time2-
M2)
Deceleration time (2),
2
nd
motor
10.00
s
A094
(Acc2/Dec2
sel)
Select method to switch
to Acc2/Dec2 profile
Three options for
switching from 1st to
2nd accel/decel:
002CH input from
terminal
01Transition
frequency
02Forward and
reverse
00
A294
(Acc2/Dec2
sel-M2)
Select method to switch
to Acc2/Dec2 profile,
2
nd
motor
00
A095
(Acc1-2 FQ)
Acc1 to Acc2 frequency
transition point
Output frequency at
which Accel1
switches to Accel2,
range is 0.00 to
400.00 Hz
0.00
Hz
A295
(Acc1-2
FQ-M2)
Acc1 to Acc2 frequency
transition point, 2
nd
motor
0.00
Hz
A096
(Dec1-2 FQ)
Dec1 to Dec2
frequency transition
point
Output frequency at
which Decel1
switches to Decel2,
range is 0.00 to
400.00 Hz
0.00
Hz
A296
(Dec1-2
FQ-M2)
Dec1 to Dec2
frequency transition
point, 2
nd
motor
0.00
Hz
A097
(Accel.curve
select)
Acceleration curve
selection
Set the
characteristic curve
of Acc1 and Acc2,
five options:
00linear
01S-curve
02U-curve
03Inverse
U-curve
00
A098
(Decel.curve
select)
Deceleration curve
selection
Set the
characteristic curve
of Dec1 and Dec2,
options are same as
above (A097)
00
A131
(Accel.curve
const)
Acceleration curve
constant
Range is 1 to 10
2
A132
(Decel.curve
const)
Deceleration curve
constant
Range is 1 to 10
2