User Manual

Chapter 13 Option
13 - 38
“b” Function
Run
Mode
Edit
Default
s
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Uni
t
s
b019
(Free
E.Thermal
FQ-3)
Free setting
electronic thermal
~freq.3
Range is b017 to 400Hz
0
Hz
b020
(Free
E.Thermal
I-3)
Free setting
electronic thermal
~current3
Range is 0.00 to inverter
rated current Amps
0.00
A
b021
(OL restrict
mode)
Overload restriction
operation mode
Select the operation
mode during overload
conditions, three options,
option codes:
00Disabled
01Enabled for
acceleration and constant
speed
02Enabled for constant
speed only
01
b221
(OL restrict
mode-M2)
Overload restriction
operation mode, 2
nd
motor
01
b022
(OL restrict
level)
Overload restriction
level
Sets the level of overload
restriction, between 20%
and 200% of the rated
current of the inverter,
setting resolution is 1% of
rated current
Rated
current
x 1.50
A
b222
(OL restrict
level-M2)
Overload restriction
level,
2
nd
motor
Rated
current
x 1.50
A
b023
(Decel.rate
OL restrict)
Deceleration rate at
overload restriction
Sets the deceleration rate
when inverter detects
overload, range is 0.1 to
3000.0, resolution 0.1
seconds.
1.0
s
b223
(Decel.rate
OL rstr-M2)
Deceleration rate at
overload restriction,
2
nd
motor
1.0
s
b024
(OL restrict 2
mode)
Overload restriction
operation mode 2
Select the operation
mode during overload
conditions, three options,
option codes:
00Disabled
01Enabled for
acceleration and constant
speed
02Enabled for constant
speed only
01
b025
(OL restrict 2
level)
Overload restriction
level 2
Sets the level of overload
restriction, between 20%
and 200% of the rated
current of the inverter,
setting resolution is 1% of
rated current
Rated
current
x 1.50
A
b026
(Decel.rate
OL 2 rstr)
Deceleration rate 2 at
overload restriction
Sets the deceleration rate
when inverter detects
overload, range is 0.1 to
3000.0, resolution 0.1
seconds.
1.0
s