User Manual

Chapter 13 Option
13 - 39
“b” Function
Run
Mode
Edit
Default
s
Func.
Code
(WOP)
Name Description
Initial dat
a
standard
200/400
Initial dat
a
CHN
200/400
Initial dat
a
EU
200/400
Uni
t
s
b027
(OC
suppress
select)
OC suppression
selection *
Two option codes:
00Disabled
01Enabled
01
b028
(Curnt Active
F-match)
Current level of
active freq. matching
Sets the current level of
active freq. matching
restart, range is
0.2*inverter rated current
to 2.0*inverter rated
current, resolution 0.1
seconds.
Rated
current
A
b029
(Decel.rate
act.F-match)
Deceleration rate of
active freq. matching
Sets the deceleration rate
when active freq.
matching restart, range is
0.1 to 3000.0, resolution
0.1 seconds.
0.5
s
b030
(Start FQ
act.F-match)
Start freq. of active
freq. matching
Three option codes:
00freq at previous
shutoff
01start from max. Hz
02start from set
frequency
00
b031
(Softlock
select)
Software lock mode
selection
Prevents parameter
changes, in five options,
option codes:
00all parameters
except b031 are locked
when [SFT] terminal is
ON
01all parameters
except b031 and output
frequency F001 are
locked when [SFT]
terminal is ON
02all parameters
except b031 are locked
03all parameters
except b031 and output
frequency F001are
locked
10High level access
including b031
See appendix C for the
accessible parameters in
this mode.
01 10 01
b034
(RNT/ONT
time)
Run/power ON
warning time
Range is,
0:Warning disabled
1 to 65535 hrs
0.
Hrs.
b035
(Rotation
restrction)
Rotation direction
restriction
Three option codes:
00No restriction
01Reverse rotation is
restricted
02Forward rotation is
restricted
00