User Manual
Chapter 6 Operation
6 - 13
(3) Method to perform driving in FW/RV teraminal and perform frequency setting in volume resistor
This is the operation method using Run command is given by intelligent input terminal such as
FW(RV) function & Frequency setting is given by analog input such as O-L voltage. If you don't
need to change such as Accel&Decel time, optional Operator is not required.) Below diagram is to
set the external Freq. setting connecting H-O-L volume to supply O-L voltage.
■Setup
Function Name Code Data Note
Frequency source A001 01(Control circuit terminals) Default
Run command source A002 01(Control circuit terminals) Default
Input [1] function C001 00(FW)
Default
Input [2] function C002 01(RV)
The initial value of Acceleration/ Deceleration time is 10sec.
Please change the following parameters as needed.
Function Name Code Setting Range Note
Acceleration time F002 0.00 to 3600 sec. Default:10 sec.
Deceleration time F003 0.00 to 3600 sec. Default:10 sec.
* One of the following is required when changing parameters on NE-S1 series inverters.
a) Dedicated operator (NES1-OP) b) Digital operator c) 5-line LCD operator
d) Modbus e) PC programming tool (ProDriveNext)
■Control circuit terminals wiring (Sink logic)
Note)
The above is a method to perform
analog input(O/OI) by voltage input. It
is necessary for SW6 on the board to
be set for volta
g
e in
p
ut
(
default
)
. →
P24PLCL 1 2 L O/OI H
FW RV
Frequency setting
resistor