9
Function List
b Group: Fine-tuning Functions
: Allowed
[
X
: Not allowed
]
Function Code Name Range Default Unit
Run mode edit
Lo Hi
Electronic
thermal
b012 Electronic thermal setting
0.20 × Rated current to 1.00 × Rated current
Rated current
A
X
b212 Electronic thermal setting, 2nd motor
Rated current
A
X
b013 Electronic thermal characteristic
00 (reduced-torque characteristic)/ 01 (constant-torque characteristic)/ 02 (free setting)
01
-
X
b213 Electronic thermal characteristic, 2nd motor 01
-
X
b015 Free setting, electronic thermal frequency (1) 0 to Free setting, electronic thermal frequency (2) 0. Hz
X
b016 Free setting electronic thermal ~current1 0.00 to inverter rated current Amps 0.0 A
X
b017 Free setting, electronic thermal frequency (2)
Free setting, electronic thermal frequency (1) to Free setting, electronic thermal
frequency (3)
0. Hz
X
b018 Free setting electronic thermal ~current2 0.00 to inverter rated current Amps 0.0 A
X
b019 Free setting electronic thermal ~freq.3 Free setting, electronic thermal frequency (2) to 400.0 0. Hz
X
b020 Free setting electronic thermal ~current3 0.00 to inverter rated current Amps 0.0 A
X
Overload
restriction
b021 Overload restriction operation mode
00(Disable)/01(Enable)/02(Enable for during acceleration)
01
-
X
b221
Overload restriction operation mode, 2nd motor
01
-
X
b022 Overload restriction setting
0.20 × Rated current to 2.00 × Rated current
150% of
Rated
current
A
X
b222 Overload restriction setting, 2nd motor A
X
b023 Deceleration rate at overload restriction
0.1 to 999.9/1000. to 3000.
1.0 s
X
b223
Deceleration rate at overload restriction, 2nd motor
1.0 s
X
b024 Overload restriction operation mode 2
00 (disabling)/ 01 (enabling during acceleration and constant-speed operation)/
02 (enabling during constant-speed operation)
01
-
X
b025 Overload restriction level 2 setting 0.20 × rated current to 2.00×rated current
150% of Rated current
A
X
b026 Deceleration rate 2 at overload restriction 0.1 to 999.9/1000. to 3000. 1.0 s
X
b027 OC suppression selection 00 (OFF)/ 01 (ON) 01
-
X
b028
Current level of active freq. matching restart setting
0.20 × rated current to 2.00 × rated current
Rated current
A
X
b029 Deceleration rate of active freq. matching 0.1 to 999.9/1000. to 3000. 0.5 s
X
b030
Start freq to be used in case of active freq. Matching restart
00 (frequency at the last shutoff)/ 01 (maximum frequency)/ 02 (set frequency) 00
-
X
Lock b031 Software lock mode selection
00([SFT] input blocks all edits)/01([SFT] input blocks edits except F001 and Multispeed
parameters/02(No access to edits)/03(No access to edits except F001 and Multi-speed
parameters)/10(High-level access,including b031)
01
-
X
Others
b034 Run/power ON warning time
0. (Disabling the signal output) /1. to 9999. in units of 10 hours
1000 to 6553 in units of 100 hours
0. Hrs
X
b035 Rotation direction restriction 00( Enable for both dir)/ 01 (Enable for forward only)/ 02 (Enable for reverse only) 00
-
X X
b036 Reduced voltage start selection 0 (minimum reduced voltage start time) to 255 (maximum reduced voltage start time) 3
-
X
b037 Function code display restriction
0 (full display), 1 (function-specific display) , 3 (data comparison display),
4 (basicdisplay), 5(monitor display)
00
-
X
b038 Initial display selection
000(Func. code that SET key pressed last displayed.) /
001 to 060(d001 to d060 displayed) / 201(F001displayed) /
202(B display of LCD operator (In case of Digital operator, same 000 setting)
001
-
X
b050 Selection of the non stop operation
00(Disabled)/ 01 (enabling)/ 02 (nonstop operation at momentary power failure
(no restoration))/03 (nonstop operation at momentary power failure (restoration to be done))
00
-
X X
b051 DC bus voltage trigger level of ctrl. decel. 200V class:0.0 to 400.0, 400V class:0.0 to 800.0
220.0/440.0
V
X X
b052
Over-voltage threshold of ctrl. decel.
200V class:0.0 to 400.0, 400V class:0.0 to 800.0
360.0/720.0
V
X X
b053
Deceleration time of ctrl. decel.
0.01 to 300.0 1.00 s
X X
b054 Frequency width of quick deceleration setting 0.00 to 10.00 0.00 Hz
X X
b060 Maximum-limit level of window comparators 0 to 100 100. %
b061 Minimum-limit level of window comparators 0 to 100 0. %
b062 Hysteresis width of window comparators 0 to 10 0. %
b070 Operation level at O/OI disconnection 0. to 100., or “no” (ignore) no
-
X
b078 Watt-hour clearance 00(OFF)/01(CLR)(press STR then clear) 00
-
b079 Watt-hour display gain 1.to1000. 1.
-
b082 Start frequency adjustment 0.01 to 9.99 0.50 Hz
X
b083 Carrier frequency setting 2.0 to 15.0 *1 2.0 kHz
X
b084
Initialization mode
(parameters or trip history)
00(disabling)/ 01 (clearing the trip history)/ 02 (initializing the data)/
03 (clearing the trip history and initializing the data)
00
-
X X
b085 Country code for initialization 00 (Mode1)/ 01(Mode2) 00
-
X X
b086 Frequency scaling conversion factor 0.01 to 99.99 1.00
-
b087 STOP key enable 00:ON(Enable)/01:OFF(Disable)/02:Only RESET(Disable for stop) 00
-
X
b088 Restart mode after FRS 00(Restart from 0Hz)/01(Restart with frequency detection) 00
-
X
b089 Automatic carrier frequency reduction
00(disabling)/ 01(enabling( output current controlled))/
02(enabling( fin temperature controlled))
00
-
X X
b091 Stop mode selection 00(Deceleration and stop)/01(Free-run stop) 00
-
X
b094 Initialization target data setting 00(All parameters)/01(All parameters except in/output terminals and communication) 00
-
X X
b100 Free-setting V/F freq. (1) 0. to b102 0. Hz
X X
b101 Free-setting V/F volt. (1) 200V class:0.0 to 300.0, 400V class:0.0 to 600.0 0.0 V
X X
b102 Free-setting V/F freq. (2) b100 to b104 0. Hz
X X
b103 Free-setting V/F volt. (2) 200V class:0.0 to 300.0, 400V class:0.0 to 600.0 0.0 V
X X
b104 Free-setting V/F freq. (3) b102 to b106 0. Hz
X X
b105 Free-setting V/F volt. (3) 200V class:0.0 to 300.0, 400V class:0.0 to 600.0 0.0 V
X X
b106 Free-setting V/F freq. (4) b104 to b108 0. Hz
X X
b107 Free-setting V/F volt. (4) 200V class:0.0 to 300.0, 400V class:0.0 to 600.0 0.0 V
X X
b108 Free-setting V/F freq. (5) b106 to b110 0.0 Hz
X X
b109 Free-setting V/F volt. (5) 200V class:0.0 to 300.0, 400V class:0.0 to 600.0 0 V
X X
b110 Free-setting V/F freq. (6) b108 to b112 0. Hz
X X
b111 Free-setting V/F volt. (6) 200V class:0.0 to 300.0, 400V class:0.0 to 600.0 0.0 V
X X
b112 Free-setting V/F freq. (7) b110 to 400 0. Hz
X X
b113 Free-setting V/F volt. (7) 200V class:0.0 to 300.0, 400V class:0.0 to 600.0 0.0 V
X X
b130 Over-voltage LADSTOP enable 00 (OFF)/ 01 (V-count)/ 02 (Accel)/ 03(Acc/Dcc) 00
-
X
b131 Decel. overvolt. suppress level 200V class:330. to 390. , 400V class:660. to 780. 360/720 V
X
b132 DC bus AVR constant setting 0.10 to 30.00 1.00 s
X
b133 DC bus AVR for decel. Proportional-gain 0.00 to 5.00 0.20
-
b134 DC bus AVR for decel. Integral-time 0.0 to 150.0 1.0 s
b150 Panel Display selection 001 to 050 001
-
b160 1st data of d050 001 to 018 001
-
b161 2nd parameter of Double Monitor 001 to 018 002
-
b163 Data change mode selection of d001 and d007 00 (OFF)/ 01 (ON) 01
-
b164 Automatic return to the initial display 00 (OFF)/ 01 (ON) 00
-
b165 Ex. operator com. loss action
00 (trip)/01 (trip after deceleration to a stop)/02 (Ignore)/03 (coasting (FRS))/
04 (decelerates to a stop)
02
-
b166 Data Read/Write select 00 (Read/Write OK)/01 (Protected) 00
-
X
b180 Initialization trigger 00 (initialization disable)/01 (perform initialization) 00
-
X
X
Note 1:
Carrier derating required for aambient temperature higher than 40℃(022SB:temperature higher than 30℃), no freezing.