Instruction Manual
Table Of Contents
- 1 Safety summary
- 2 Switch Names and Functions
- 3 Operation
- 4 Icon Description
- 5 Function Menu
- 5.1 Simple Timer Setting
- 5.2 Operation Schedule Setting
- 5.3 Power Savings Setting
- 5.4 Night Quiet Operation
- 5.5 Power Saving/Night Quiet Schedule Setting
- 5.6 Power Consumption Display
- 5.7 Autoboost (QUICK MODE) Setting
- 5.8 Comfort Setting
- 5.9 Motion sensor setting
- 5.10 Setback Setting
- 5.11 Elevating Grille
- 5.12 Filter Reminder Reset Setting
- 5.13 FrostWash
- 5.14 Individual Louver Setting
- 5.15 Cancel Individual Louver Setting
- 5.16 Louver Open/Close
- 5.17 Ventilation
- 5.18 Total Heat Exchanger Setting
- 6 Service & installation menu
- 6.1 Installation menu
- 6.1.1 Test Run
- 6.1.2 Function selection
- 6.1.3 Thermistor Selection
- 6.1.4 Input / Output Setting
- 6.1.5 Thermistor Calibration in Controller
- 6.1.6 Fan Speed at Cooling Thermo-OFF
- 6.1.7 Fan Speed at Heating Thermo-OFF
- 6.1.8 Indoor Unit Address Change
- 6.1.9 Address Check Operation
- 6.1.10 Address Initialization
- 6.1.11 Setting Initialization
- 6.1.12 Main Remote Setting
- 6.1.13 Priority Setting
- 6.1.14 Cancel Preheating Control
- 6.1.15 Elevating grille Setting
- 6.1.16 Power Up Setting
- 6.1.17 Setback Trigger Unit
- 6.1.18 Refrigerant Leak Sensor Setting
- 6.2 Service menu
- 6.3 Check Menu
- 6.1 Installation menu
- 7 Screen Display Setting menu
- 8 Contact Information menu
- 9 Hotel Mode Setting
- 10 In Alarm Condition
5.13 FROSTWASH
FrostWash is available when applicable outdoor units and
indoor units are connected. To use this function in VRF system,
outdoor unit function selection item “F1” need to be congured
on outdoor units.
Please congure function selection F1 on the outdoor units, and
then set the wired remote controller.
Please contact the distributor or service personnel for availability
and conguration of this function.
5.13.1 About FrostWash
• Regarding the noise upon freezing and defrosting
- Cracking noise may be heard during the freezing or
defrosting phase due to temperature change. Refrigerant
ow noise may also be heard. The noise may be
heard relatively louder in a quiet environment. It is
recommended to set the “Auto-FrostWash Schedule”
when the room is not occupied.
- Choose not to use the FrostWash function in places such
as hotel rooms and hospitals, where consistent quietness
is expected.
• Ice fog may come out from air outlet during the FrostWash
operation.
• Ice fog could happen in a humid environment such as the
room humidier is used in a small room.
• FrostWash is available when the outside temperature is in
the range of (1°C - 43°C), and the indoor temperature is in
the range of (15°C - 30°C).
• Also refer to technical documents of outdoor units because
outdoor temperature range may vary depending on outdoor
units’ type.
• The temperature around the indoor unit may drop slightly
during FrostWash operation.
5.13.2 Start FrostWash
Generate frost on the coil and then melt the frost to wash the
coil.
FrostWash setting is not enabled as factory setting. This function
has to be activated from the outdoor unit rst (refer to
“5.13.5 FrostWash Setting” for more information) and then
controlled from the wired controller.
Preparation
(Fan mode)
Start FrostWash
Freezing, defrosting, drying
heat exchanger
FrostWash Completed
Stop Automatically
Approx. 3 min.*
*1: change according
to the outdoor unit
*2: change according to indoor temperature
and outdoor temperature
Approx. 10 min. to 35 min.*
Start FrostWash
Approx. 10 min to 35 min.
*2
*1: Change according
to the outdoor unit.
*2: Change according to indoor temperature
and outdoor temperature
FrostWash Completed
Stop Automatically
Approx. 3 min
*1
Preparation
(Fan mode)
Freezing, defrosting, drying heat
exchanger
• Press “OK” on the wired controller to cancel FrostWash in
the middle of an operation.
• After a cancellation, frost on the heat exchanger needs to
be defrosted and the heat exchanger needs to be dried. The
system cannot start operation for at least 8 minutes after
cancellation.
• You cannot start another FrostWash immediately
after a FrostWash operation completes. Run either
cooling operation, heating operation or dry operation
for approx. 60 minutes. Then, start another FrostWash
operation.
? NOTE
Do not open or remove the air inlet grille during the FrostWash operation.
It may cause injury or damage of units.
FUNCTION MENU
PMML0601 rev.0 - 07/202228