Instruction Manual

Table Of Contents
Element Optional function
Individual
setting
Settings Setting conditions Description
CC
Not used
00
- Use at 00 conditions
01
Only for DX-Interface,
KPI-E4E and KPI-X4E:
High ventilation speed
00 Function disabled (factory setting)
This function sets the unit to run
in high fan speed regardless
the setting from remote control
switch.
01 Function enabled
Cd
Stop of indoor unit fan
during cooling Thermo-OFF
conditions
? NOTE
For model RPI(L/H)-FSRE and
RCD-FSR, this function is NOT
available.
O
00
Fan speed during cooling Thermo-OFF:
Low (factory setting)
The operation of the indoor
unit fan is stopped in cooling
Thermo-OFF conditions when
using the additional remote
temperature sensor THM-R2AE
(connected to THM4) or the
PC-ARFG2E-(B)(1-5)
temperature sensor.
C8 must be set to 01 to use the
Cd=01 setting.
01
Indoor unit fan is stopped during cooling
Thermo-OFF
CE
Stop of indoor unit fan
during heating Thermo-OFF
conditions (with remote
control switch temperature
sensor)
O
00
Fan speed setting during heating Thermo-
OFF: Low (factory setting)
The indoor unit uses the
PC-ARFG2E-(B)(1-5)
temperature sensor to monitor
the room temperature when the
fan is stopped (heating Thermo-
OFF fan stop sequence).
C8 must be set to 01 to use the
CE=01 setting.
Control by remote temperature
sensor connected to THM4 is
not permitted (use E8 function
in that case).
01
Indoor unit fan is stopped during heating
Thermo-OFF
(4)
(In case that automatic louver is set, the lou-
vers will keep operating in both Thermo-ON
and Thermo-OFF conditions)
CF
Modication of louver swing
angle
Models:
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
O
00 Standard (7 steps) (factory setting)
This function adjusts the angle
of the air outlet louver.
(Changes to the setting of this
function are applied after turning
the power supply off and on again,
or after the automatic louver has
made a full cycle in automatic
mode).
01
Cold draft prevention (5 steps)
(5)
(Cannot be set to the lower two steps; lower
2 steps cut off)
02
High ceilings (5 steps)
(5)
(Cannot be set the upper two steps; upper
2 steps cut off)
Models:
RPK-FSR(H)M
00
Standard (7 steps)
(5 steps for cooling / dry mode)
01
Cold draft prevention
(5 steps for heating and fan only)
(Cannot be set to the lower two steps,
lower 2 steps cut off)
02 Not used
d1
Management of indoor unit
operation after a power
supply cut off - option 1
O
00 Function disabled (factory setting)
When power supply is restored,
the indoor units controlled by
the wired remote control switch
are turned on regardless of their
ON/OFF status at the time of
the last power cut off.
01 Function enabled
d2 Not available
“- -”
permanent
d3
Management of indoor unit
operation after a power
supply cut off - option 2
O
00 Function disabled (factory setting)
When power supply is restored,
the indoor units controlled by
the wired remote control switch
are turned on automatically
ONLY if they were already ON
at the time of the last power
cut off.
If indoor units were OFF when
power was turned OFF, they
remain in OFF status when
power is restored.
01 Function enabled
SERVICE & INSTALLATION MENU
PMML0601 rev.0 - 07/202244