Instruction Manual
Table Of Contents
- 1 Safety summary
- 2 Switch Names and Functions
- 3 Operation
- 4 Icon Description
- 5 Function Menu
- 5.1 Simple Timer Setting
- 5.2 Operation Schedule Setting
- 5.3 Power Savings Setting
- 5.4 Night Quiet Operation
- 5.5 Power Saving/Night Quiet Schedule Setting
- 5.6 Power Consumption Display
- 5.7 Autoboost (QUICK MODE) Setting
- 5.8 Comfort Setting
- 5.9 Motion sensor setting
- 5.10 Setback Setting
- 5.11 Elevating Grille
- 5.12 Filter Reminder Reset Setting
- 5.13 FrostWash
- 5.14 Individual Louver Setting
- 5.15 Cancel Individual Louver Setting
- 5.16 Louver Open/Close
- 5.17 Ventilation
- 5.18 Total Heat Exchanger Setting
- 6 Service & installation menu
- 6.1 Installation menu
- 6.1.1 Test Run
- 6.1.2 Function selection
- 6.1.3 Thermistor Selection
- 6.1.4 Input / Output Setting
- 6.1.5 Thermistor Calibration in Controller
- 6.1.6 Fan Speed at Cooling Thermo-OFF
- 6.1.7 Fan Speed at Heating Thermo-OFF
- 6.1.8 Indoor Unit Address Change
- 6.1.9 Address Check Operation
- 6.1.10 Address Initialization
- 6.1.11 Setting Initialization
- 6.1.12 Main Remote Setting
- 6.1.13 Priority Setting
- 6.1.14 Cancel Preheating Control
- 6.1.15 Elevating grille Setting
- 6.1.16 Power Up Setting
- 6.1.17 Setback Trigger Unit
- 6.1.18 Refrigerant Leak Sensor Setting
- 6.2 Service menu
- 6.3 Check Menu
- 6.1 Installation menu
- 7 Screen Display Setting menu
- 8 Contact Information menu
- 9 Hotel Mode Setting
- 10 In Alarm Condition
Element Optional function
Individual
setting
Settings Setting conditions Description
rC
Maximum outdoor
temperature to allow
operation mode switch to
heating in auto cooling/
heating with dual set point
X
00 Disabled
If outdoor ambient temperature
is higher than rC, there is no
mode transition to heating
in automatic cooling/heating
operation mode, even if room
temperature reaches the
setpoint to switch operation
mode from cooling to heating.
01 20.0°C
02 21.0°C
03 22.0°C
·
·
·
·
·
·
21 40.0°C
22 0.0°C
23 1.0°C
24 2.0°C
·
·
·
·
·
·
41 19.0°C
rd
Minimum outdoor
temperature to allow
operation mode switch to
cooling in auto cooling/
heating with dual set point
X
00 Disabled
If outdoor ambient temperature
is lower than rd, there is no
mode transition to cooling
in automatic cooling/heating
operation mode, even if room
temperature reaches the
setpoint to switch operation
mode from heating to cooling.
01 10.0°C
02 11.0°C
03 12.0°C
·
·
·
·
·
·
31 40.0°C
32 -20.0°C
33 -19.0°C
34 -18.0°C
·
·
·
·
·
·
61 9.0°C
rE
Temperature for the
beginning of heating in
setback
X
00 15.0°C
If room temperature becomes
lower than this setting, indoor
unit operation is resumed in
heating mode by the setback
function.
01 16.0°C
02 17.0°C
03 18.0°C
04 19.0°C
05 10.0°C
06 11.0°C
07 12.0°C
08 13.0°C
09 14.0°C
rF
Temperature for the
beginning of cooling in
setback
X
00 26.0°C
If room temperature becomes
higher than this setting, indoor
unit operation is resumed in
cooling mode by the setback
function.
01 27.0°C
02 28.0°C
03 29.0°C
04 30.0°C
05 31.0°C
06 32.0°C
07 33.0°C
08 34.0°C
09 35.0°C
10 25.0°C
S1 Not used -
00
- Use at 00 conditions
01
S2 Not used -
00
- Use at 00 conditions
01
SERVICE & INSTALLATION MENU
PMML0601 rev.0 - 07/202256