Instruction Manual
Table Of Contents
- 1 Safety summary
- 2 Switch Names and Functions
- 3 Operation
- 4 Icon Description
- 5 Function Menu
- 5.1 Simple Timer Setting
- 5.2 Operation Schedule Setting
- 5.3 Power Savings Setting
- 5.4 Night Quiet Operation
- 5.5 Power Saving/Night Quiet Schedule Setting
- 5.6 Power Consumption Display
- 5.7 Autoboost (QUICK MODE) Setting
- 5.8 Comfort Setting
- 5.9 Motion sensor setting
- 5.10 Setback Setting
- 5.11 Elevating Grille
- 5.12 Filter Reminder Reset Setting
- 5.13 FrostWash
- 5.14 Individual Louver Setting
- 5.15 Cancel Individual Louver Setting
- 5.16 Louver Open/Close
- 5.17 Ventilation
- 5.18 Total Heat Exchanger Setting
- 6 Service & installation menu
- 6.1 Installation menu
- 6.1.1 Test Run
- 6.1.2 Function selection
- 6.1.3 Thermistor Selection
- 6.1.4 Input / Output Setting
- 6.1.5 Thermistor Calibration in Controller
- 6.1.6 Fan Speed at Cooling Thermo-OFF
- 6.1.7 Fan Speed at Heating Thermo-OFF
- 6.1.8 Indoor Unit Address Change
- 6.1.9 Address Check Operation
- 6.1.10 Address Initialization
- 6.1.11 Setting Initialization
- 6.1.12 Main Remote Setting
- 6.1.13 Priority Setting
- 6.1.14 Cancel Preheating Control
- 6.1.15 Elevating grille Setting
- 6.1.16 Power Up Setting
- 6.1.17 Setback Trigger Unit
- 6.1.18 Refrigerant Leak Sensor Setting
- 6.2 Service menu
- 6.3 Check Menu
- 6.1 Installation menu
- 7 Screen Display Setting menu
- 8 Contact Information menu
- 9 Hotel Mode Setting
- 10 In Alarm Condition
6.1.10 Address Initialization
This function can be used to initialize the indoor units addresses,
cancelling the settings done with the “Indoor Unit Address
Change” function.
Using this function, the indoor units addresses will be restored
as the addresses set physically on the indoor units PCB by DSW
setting. In case DSW settings have not been done, temporary
automatic addresses will be attributed to the units.
? NOTE
• After the indoor address is initialized, turn off the power of the indoor
unit. After all indicators on the remote controller are OFF, turn ON the
power of the indoor unit again.
• Address initialization cannot be performed for indoor units that are
not connected physically to the remote controller through the A/B
terminals (remote controller without remote control line).
1 Select “Address Initialization”on the “Installation Menu”
screen and press “OK”.
2 Press “ ”, “ ”, “ ” or “ ” to select the indoor unit. Press “OK”.
? NOTE
• Only the indoor units compatible with “Address initialization” function
can be selected.
• Even if “All” is selected, the address of the indoor unit that does not
support the Address Initialization function cannot be initialized.
3 Select “Yes” and press “OK”. The address initialization
processing starts.
? NOTE
When the indoor unit address is changed successfully, connection
checking process starts.
4 Select “Complete” and press “OK”.
5 Step5. To initialize another indoor unit address, select
“Continue” and press “OK” to return to Step2.