User Manual
Table Of Contents
- Front_page_ErP2013
- TC_Clause
- 00_CONTENTS_ErP_2013
- 01_SYSTEM_DESCRIPTION_ErP2013(190313-draft_10C1a)
- 02_GENERAL_DATA_ErP2013(draft2D)
- 03_DIMENSIONAL_DATA_ErP2013(done)
- -DIMENSIONAL DATA
- MONOZONE / MULTIZONE Indoor Units
- MONOZONE / MULTIZONE Outdoor Units
- MONO SPLIT
- WALL TYPE: RAK-18PSA/25PSA/35PSA/18PSAN/25PSAN/35PSAN
- WALL TYPE: RAC-18WSA/25WSA/35WSA/18WSAN/25WSAN/35WSAN
- WALL TYPE: RAK-18PSPA/25PSPA/35PSPA
- WALL TYPE: RAC-18WSPA/25WSPA/35WSPA
- WALL TYPE: RAK-25PXA/35PXA/50PXA
- WALL TYPE: RAC-25WXA/35WXA
- WALL TYPE: RAC-50WXA
- WALL TYPE: RAK-18PPA/25PPA/35PPA
- WALL TYPE: RAC-18WPA/25WPA
- WALL TYPE: RAC-35WPA
- WALL TYPE: RAK-50PPA
- WALL TYPE: RAC-50WPA
- WALL TYPE : RAK-60PPA
- WALL TYPE: RAC-60WPA
- WALL TYPE: RAK-70PPA
- WALL TYPE: RAC-70WPA
- WALL TYPE: RAK-18PEA/25PEA/35PEA/50PEA
- WALL TYPE: RAC-18WEA/25WEA
- WALL TYPE: RAC-35WEA
- WALL TYPE: RAC-50WEA
- FLOOR TYPE: RAF-25PXA/35PXA/50PXA
- FLOOR TYPE: RAC-25FXA/35FXA
- FLOOR TYPE: RAC-50FXA
- FLOOR TYPE: RAF-25RPA/35RPA/50RPA
- FLOOR TYPE: RAC-25FPA/35FPA
- FLOOR TYPE: RAC-50FPA
- DUCT TYPE: RAD-50PPA/60PPA/70PPA
- DUCT TYPE: RAC-50DPA/60DPA/70DPA
- -DIMENSIONAL DATA
- 04_CAPACITIES_AND_SELECTION-ErP2013(DRAFT04)_3
- 05_WORKING_RANGE_ErP2013(23042012-done)
- 06_ELECTRICAL_DATA_ErP2013(Done)
- 07_A_ELECTRICAL_WIRING_DIAG-ErP2013(draft-03)
- ELECTRICAL WIRING DIAGRAM
- MONOZONE/MULTIZONE
- RAK-18QXA, RAK-25QXA, RAK-35QXA, RAK-50QXA
- RAK-18QPA, RAK-25QPA, RAK-35QPA, RAK-50QPA
- RAF-25QXA, RAF-35QXA, RAF-50QXA
- RAF-25RPA, RAF-35RPA, RAF-50RPA
- RAI-25RPA, RAI-35RPA, RAI-50RPA
- RAD-18RPA, RAD-25RPA, RAD-35RPA, RAD-50RPA
- RAC-25NPA, RAC-35NPA, RAC-50NPA
- RAM-36NP2A
- RAM-53NP2A
- RAM-53NP3A
- RAM-68NP3A
- RAM-70NP4A
- RAM-90NP5A
- RAM-130NP6A (OUTDOOR 1)
- RAM-130NP6A (OUTDOOR 2)
- MONO - SPLIT
- RAK-18PSA, RAK-25PSA, RAK-35PSA
- RAK-18PSAN, RAK-25PSAN, RAK-35PSAN
- RAC-18WSA, RAC-25WSA, RAC-35WSA, RAC-18WSAN, RAC-25WSAN, RAC-35WSAN
- RAK-18PSPA, RAK-25PSPA, RAK-35PSPA
- RAC-18WSPA, RAC-25WSPA, RAC-35WSPA
- RAK-25PXA, RAK-35PXA, RAK-50PXA
- RAC-25WXA, RAC-35WXA
- RAC-50WXA
- RAK-18PPA, RAK-25PPA, RAK-35PPA
- RAC-18WPA, RAC-25WPA
- RAC-35WPA
- RAK-50PPA
- RAC-50WPA
- RAK-60PPA
- RAC-60WPA
- RAK-70PPA
- RAC-70WPA
- RAK-18PEA, RAK-25PEA, RAK-35PEA, RAK-50PEA
- RAC-18WEA, RAC-25WEA
- RAC-35WEA
- RAC-50WEA
- RAF-25PXA, RAF-35PXA, RAF-50PXA
- RAC-25FXA, RAC-35FXA
- RAC-50FXA
- RAF-25RPA, RAF-35RPA, RAF-50RPA
- RAC-25FPA, RAC-35FPA
- RAC-50FPA
- RAD-50PPA, RAD-60PPA, RAD-70PPA
- RAC-50DPA, RAC-60DPA, RAC-70DPA
- MONOZONE/MULTIZONE
- ELECTRICAL WIRING DIAGRAM
- 08_REFRIGERANT_CYCLE_ErP2013(done)
- REFRIGERANT CYCLE
- Monozone/Multizone Indoor Units
- Monozone/Multizone Outdoor Units
- MONO SPLIT
- WALL TYPE: RAK-18PSA/25PSA/35PSA / RAC-18WSA/25WSA/35WSA
- WALL TYPE: RAK-18PSAN/25PSAN/35PSAN / RAC-18WSAN/25WSAN/35WSAN
- WALL TYPE: RAK-18PSPA/25PSPA/35PSPA / RAC-18WSPA/25WSPA/35WSPA
- WALL TYPE: RAK-25PXA / RAC-25WXA
- WALL TYPE: RAK-35PXA / RAC-35WXA
- WALL TYPE: RAK-50PXA / RAC-50WXA
- WALL TYPE: RAK-18PPA/25PPA / RAC-18WPA/25WPA
- WALL TYPE: RAK-35PPA / RAC-35WPA
- WALL TYPE: RAK-50PPA / RAC-50WPA
- WALL TYPE: RAK-60PPA / RAC-60WPA
- WALL TYPE: RAK-70PPA / RAC-70WPA
- WALL TYPE: RAK-18PEA/25PEA / RAC-18WEA/25WEA
- WALL TYPE: RAK-35PEA / RAC-35WEA
- WALL TYPE: RAK-50PEA / RAC-50WEA
- FLOOR TYPE: RAF-25PXA/35PXA / RAC-25FXA/35FXA
- FLOOR TYPE: RAF-50PXA / RAC-50FXA
- FLOOR TYPE: RAF-25RPA / RAC-25FPA
- FLOOR TYPE: RAF-35RPA / RAC-35FPA
- FLOOR TYPE: RAF-50RPA / RAC-50FPA
- DUCT TYPE: RAD-50PPA/60PPA / RAC-50DPA/60DPA
- DUCT TYPE: RAD-70PPA / RAC-70DPA
- REFRIGERANT CYCLE
- 09_REMOTE_CONTROLLERS_OPERA-ErP2013(draft-03D)
- 10_UNITS_INSTALLATION-ErP2013(draft04A)
- UNITS INSTALLATION
- 10.1 INSTALLATION OF INDOOR UNIT
- INSTALLATION OF OUTDOOR UNIT
- FINAL STAGE OF INSTALLATION
- UNITS INSTALLATION
- 11_REFRIGERANT_PIPING_ErP2013(done)
- 12_DRAIN_PIPING_ErP2013(done)
- 13_ELECTRICAL_WIRING-ErP2013(draft01)
- ELECTRICAL WIRING
- General Check
- Electrical wiring for MONOZONE/MULTIZONE Unit
- Procedures of Wiring
- Electrical Wiring for Outdoor unit
- Electrical Wiring for Wall Type Indoor unit
- Electrical Wiring for Floor Type Indoor unit
- Electrical Wiring for 4 Way Ceiling Cassette Type Indoor unit (RAI-25RPA/RAI-35RPA/RAI-50RPA)
- Electrical Wiring for Duct Type Indoor unit (RAD-18RPA/RAD-25RPA/RAD-35RPA/RAD-50RPA/RAD-50PPA/RAD-60PPA/RAD-70PPA)
- Electrical wiring for SINGLE INVERTER Unit
- ELECTRICAL WIRING
- 14_TROUBLESHOOTING_ErP2013(done)
- TROUBLESHOOTING
- PRECAUTIONS FOR TROUBLE SHOOTING
- MONOZONE RAC-25NPA / 35NPA / 50NPA
- MULTIZONE RAM-36NP2A
- MULTIZONE/MONO SPLIT RAM-53NP2A / 53NP3A / 68NP3A / 70NP4A , MONO SPLIT RAF-50PXA/RAC-50FXA
- MULTIZONE RAM-90NP5A
- MULTIZONE RAM-130NP6A
- MONO SPLIT RAK-18/25/35PSA / RAC-18/25/35WSA , RAK-18/25/35PSAN / RAC-18/25/35WSAN , RAK-18/25/35PSPA / RAC-18/25/35WSPA
- MONO SPLIT RAK-18/25/35PPA / RAC-18/25/35WPA , RAK-18/25/35/50PEA / RAC-18/25/35/50WEA , RAF-25/35RPA / RAC-25/35FPA
- MONO SPLIT RAK-50/60/70PPA / RAC-50/60/70WPA
- MONO SPLIT RAF-50RPA / RAC-50FPA
- MONO SPLIT RAF-25/35PXA / RAC-25/35FXA
- MONO SPLIT RAD-50/60/70PPA / RAC-50/60/70DPA
- DISCHARGE PROCEDURE AND POWER SHUT OFF METHOD FOR POWER CIRCUIT
- MONOZONE RAC-25NPA / 35NPA / 50NPA & MULTIZONE RAM-36NP2A / 53NP2A / 53NP3A / 68NP3A / 70NP4A / 130NP6A & MONO SPLIT RAF-50PXA / RAC-50FXA, RAD-50/60/70PPA / RAC-50/60/70DPA
- MULTIZONE RAM-90NP5A
- MONO SPLIT RAK-18/25/35PSA / RAC-18/25/35WSA, RAK-18/25/35PSAN / RAC-18/25/35WSAN , RAK-18/25/35PSPA / RAC-18/25/35WSPA
- MONO SPLIT RAK-18/25/35PPA / RAC-18/25/35WPA, RAK-18/25/35/50PEA / RAC-18/25/35/50WEA , RAF-25/35PXA / RAC-25/35FXA RAF-50RPA / RAC-50FPA
- MONO SPLIT RAK-50/60/70PPA / RAC-50/60/70WPA
- MONO SPLIT RAF-25/35RPA / RAC-25/35FPA
- PRELIMINARY CHECK ON INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING
- CHECKING THE INDOOR UNIT ELECTRICAL PARTS
- No power is detected (no operation)
- Indoor fan does not operate (others are normal) – RAK-25/35/50PXA, RAK-18/25/35/50/70PPA, RAK-18/25/35/50PEA, RAF-25/35/50RPA, RAF-25/35/50PXA, RAD-50/60/70PPA
- Air deflector does not move (others are normal)
- Check the control P.W.B. (power circuit) – RAK-25/35PXA, RAK-18/25/35PPA, RAK-18/25/35/50PEA, RAF-25/35/50RPA, RAF-25/35PXA
- Checking the remote controller
- Outdoor unit does not operate (but receives remote infrared signal)
- All systems stop from several seconds to several minutes after operation is started (all indicators are also off)
- CHECKING OUTDOOR UNIT ELECTRICAL PARTS
- CHECKING BETWEEN GAS LEAKAGE AND COMPRESSOR FAULTY
- TROUBLESHOOTING WHEN INDOOR TIMER LAMP BLINKS
- TROUBLESHOOTING WHEN OUTDOOR LED LAMP BLINKS
- MONOZONE RAC-25NPA / 35NPA / 50NPA
- MULTIZONE
- COMMUNICATION ERROR DIAGNOSIS MULTIZONE RAM- 53NP3A / 68NP3A / 70NP4A / 130NP6A
- COMMUNICATION ERROR DIAGNOSIS MULTIZONE RAM-90NP5A
- MONO SPLIT(RAC-18/25/35WPA, RAC-25/35WXA, RAC-25/35FXA)
- MONO SPLIT (RAC-50WXA, RAC-50FXA
- MONO SPLIT (RAC-50/60/70WPA, RAC-50/60/70DPA)
- CHECKING POWER MODULE
- THERMISTOR
- PRECAUTIONS FOR TROUBLE SHOOTING
- TROUBLESHOOTING
- 15_MISC_Notes_split_ErP2013(done)
- MISCELLANEOUS NOTE
- INSTALLATION AT COLD REGIONS OR SNOWFALL REGIONS.
- INSTALLATION POINTS ON OUTDOOR UNITS IN COLD OR SNOWFALL REGIONS.
- Installation place of Cold and Snowfall Regions
- Considerations to the Seasonal Winds and Snowfall
- Considerations to Snowfall / Snow Buildup
- Considerations to Sliding Snow from Roof or SNOWFALL
- As to Proper Drainage of Defrosting WATER
- Request to cut Net attached to Rear side of Outdoor Unit
- Installation of HOT PIPE
- H-LINK ADAPTOR
- MISCELLANEOUS NOTE
- Back_page(new)
GENERAL DATA
2-20
2.2.10. WALL TYPE (RAC-18WPA/25WPA/35WPA)
OUTDOOR
UNIT
RAC-18WPA
RAC-25WPA
RAC-35WPA
Minimum / Maximum indoor units
connectable
-
-
-
Minimum / Maximum connected
capacity
-
-
-
Nominal Cooling capacity (min - max)
kW
2.00 (0.90 - 2.50)
2.50 (0.90 - 3.10)
3.50 (0.90- 4.00)
Nominal Heating capacity (min - max)
kW
2.50 (0.90 - 3.20)
3.40 (0.90- 4.40)
4.20 (0.90- 5.00)
Nominal cooling power input (min -
max)
kW
0.55 (0.25 - 1.01)
0.70 (0.25 - 1.29)
1.090 (0.25 - 1.46)
Nominal heating power input (min -
max)
kW
0.58 (0.25 - 0.97)
0.88 (0.25 - 1.25)
1.100(0.25 - 1.70)
EER / COP
3.64/4.31
3.57/3.86
3.21/3.82
SEER / SCOP
5.8/4.2
5.8/4.2
5.9/4.3
Energy class (SEER/SCOP)
A+/A+
A+/A+
A+/A+
Noise level cooling (sound pressure)
dB(A)
46
48
49
Noise level heating (sound pressure)
dB(A)
47
49
50
Noise level (sound power)
dB(A)
60
62
63
Air flow (Cooling / Heating)
m
3
/h
1860 / 1620
1860 / 1620
1920 / 1620
Static pressure (nominal conditions,
maximum)
Pa
-
-
-
Dimensions (H x W x D)
mm
505x700x258
505x700x258
548×750×288
Weight
kg
27.0
27.0
36.0
Colour (Munsell Code)
Beige (5Y 7/2)
Power supply
230V / 1Ph / 50Hz
230V / 1Ph / 50Hz
230V / 1Ph / 50Hz
Recommended fuse size
A
15
15
15
Starting current
A
5.0
5.0
5.0
Running current
A
2.65/2.84
3.58/4.25
5.00/5.03
Cable section
mm
2
3x1.50
3x1.50
3x1.50
Interconnection between indoor unit
and outdoor unit
mm
2
2x0.75
2x0.75
2x0.75
Piping diameter (Liq / Gas)
1/4” - 3/8”
1/4” - 3/8”
1/4” - 3/8”
Minimum piping length
m
5.0
5.0
5.0
Maximum piping length / height
difference
m
20 / 10
20 / 10
20 / 10
Current quantity of refrigerant /
Chargeless
kg
0.82
0.82
1.00
Chargeless / Additional refrigerant
charge
m / g/m
20/-
20/-
20/-
Working range (cooling / heating)
°C
-10℃—43℃/
-15℃—21℃
-10℃—43℃/
-15℃—21℃
-10℃—43℃/
-15℃—21℃
Refrigerant
R410A
R410A
R410A
Condenser Fan
Propeller Fan
Compressor
Type
ROTARY
ROTARY
ROTARY
Oil Type
α68HES-H
α68HES-H
α68HES-H
Oil Charge
ml
320±20
320±20
320±20
Coil Resistance
0.75 at 25C
0.75 at 25C
0.75 at 25C
Quantity
1
1
1
NOTE:
1. The Sound Pressure Level is based on the following conditions:
- 1 meter from the unit front surface and 1 meter from floor level
The above data was measured in an anechoic chamber. Please take into consideration reflected sound of your specific
site