GENERAL DATA
2-20
2.2.10. WALL TYPE (RAC-18WPA/25WPA/35WPA)
OUTDOOR
UNIT
RAC-18WPA
RAC-25WPA
RAC-35WPA
Minimum / Maximum indoor units
connectable
-
-
-
Minimum / Maximum connected
capacity
-
-
-
Nominal Cooling capacity (min - max)
kW
2.00 (0.90 - 2.50)
2.50 (0.90 - 3.10)
3.50 (0.90- 4.00)
Nominal Heating capacity (min - max)
kW
2.50 (0.90 - 3.20)
3.40 (0.90- 4.40)
4.20 (0.90- 5.00)
Nominal cooling power input (min -
max)
kW
0.55 (0.25 - 1.01)
0.70 (0.25 - 1.29)
1.090 (0.25 - 1.46)
Nominal heating power input (min -
max)
kW
0.58 (0.25 - 0.97)
0.88 (0.25 - 1.25)
1.100(0.25 - 1.70)
EER / COP
3.64/4.31
3.57/3.86
3.21/3.82
SEER / SCOP
5.8/4.2
5.8/4.2
5.9/4.3
Energy class (SEER/SCOP)
A+/A+
A+/A+
A+/A+
Noise level cooling (sound pressure)
dB(A)
46
48
49
Noise level heating (sound pressure)
dB(A)
47
49
50
Noise level (sound power)
dB(A)
60
62
63
Air flow (Cooling / Heating)
m
3
/h
1860 / 1620
1860 / 1620
1920 / 1620
Static pressure (nominal conditions,
maximum)
Pa
-
-
-
Dimensions (H x W x D)
mm
505x700x258
505x700x258
548×750×288
Weight
kg
27.0
27.0
36.0
Colour (Munsell Code)
Beige (5Y 7/2)
Power supply
230V / 1Ph / 50Hz
230V / 1Ph / 50Hz
230V / 1Ph / 50Hz
Recommended fuse size
A
15
15
15
Starting current
A
5.0
5.0
5.0
Running current
A
2.65/2.84
3.58/4.25
5.00/5.03
Cable section
mm
2
3x1.50
3x1.50
3x1.50
Interconnection between indoor unit
and outdoor unit
mm
2
2x0.75
2x0.75
2x0.75
Piping diameter (Liq / Gas)
1/4” - 3/8”
1/4” - 3/8”
1/4” - 3/8”
Minimum piping length
m
5.0
5.0
5.0
Maximum piping length / height
difference
m
20 / 10
20 / 10
20 / 10
Current quantity of refrigerant /
Chargeless
kg
0.82
0.82
1.00
Chargeless / Additional refrigerant
charge
m / g/m
20/-
20/-
20/-
Working range (cooling / heating)
°C
-1043/
-1521
-1043/
-1521
-1043/
-1521
Refrigerant
R410A
R410A
R410A
Condenser Fan
Propeller Fan
Compressor
Type
ROTARY
ROTARY
ROTARY
Oil Type
α68HES-H
α68HES-H
α68HES-H
Oil Charge
ml
320±20
320±20
320±20
Coil Resistance
0.75 at 25C
0.75 at 25C
0.75 at 25C
Quantity
1
1
1
NOTE:
1. The Sound Pressure Level is based on the following conditions:
- 1 meter from the unit front surface and 1 meter from floor level
The above data was measured in an anechoic chamber. Please take into consideration reflected sound of your specific
site