Table Of Contents
- Front_page_ErP2013
- TC_Clause
- 00_CONTENTS_ErP_2013
- 01_SYSTEM_DESCRIPTION_ErP2013(190313-draft_10C1a)
- 02_GENERAL_DATA_ErP2013(draft2D)
- 03_DIMENSIONAL_DATA_ErP2013(done)
- -DIMENSIONAL DATA
- MONOZONE / MULTIZONE Indoor Units
- MONOZONE / MULTIZONE Outdoor Units
- MONO SPLIT
- WALL TYPE: RAK-18PSA/25PSA/35PSA/18PSAN/25PSAN/35PSAN
- WALL TYPE: RAC-18WSA/25WSA/35WSA/18WSAN/25WSAN/35WSAN
- WALL TYPE: RAK-18PSPA/25PSPA/35PSPA
- WALL TYPE: RAC-18WSPA/25WSPA/35WSPA
- WALL TYPE: RAK-25PXA/35PXA/50PXA
- WALL TYPE: RAC-25WXA/35WXA
- WALL TYPE: RAC-50WXA
- WALL TYPE: RAK-18PPA/25PPA/35PPA
- WALL TYPE: RAC-18WPA/25WPA
- WALL TYPE: RAC-35WPA
- WALL TYPE: RAK-50PPA
- WALL TYPE: RAC-50WPA
- WALL TYPE : RAK-60PPA
- WALL TYPE: RAC-60WPA
- WALL TYPE: RAK-70PPA
- WALL TYPE: RAC-70WPA
- WALL TYPE: RAK-18PEA/25PEA/35PEA/50PEA
- WALL TYPE: RAC-18WEA/25WEA
- WALL TYPE: RAC-35WEA
- WALL TYPE: RAC-50WEA
- FLOOR TYPE: RAF-25PXA/35PXA/50PXA
- FLOOR TYPE: RAC-25FXA/35FXA
- FLOOR TYPE: RAC-50FXA
- FLOOR TYPE: RAF-25RPA/35RPA/50RPA
- FLOOR TYPE: RAC-25FPA/35FPA
- FLOOR TYPE: RAC-50FPA
- DUCT TYPE: RAD-50PPA/60PPA/70PPA
- DUCT TYPE: RAC-50DPA/60DPA/70DPA
- -DIMENSIONAL DATA
- 04_CAPACITIES_AND_SELECTION-ErP2013(DRAFT04)_3
- 05_WORKING_RANGE_ErP2013(23042012-done)
- 06_ELECTRICAL_DATA_ErP2013(Done)
- 07_A_ELECTRICAL_WIRING_DIAG-ErP2013(draft-03)
- ELECTRICAL WIRING DIAGRAM
- MONOZONE/MULTIZONE
- RAK-18QXA, RAK-25QXA, RAK-35QXA, RAK-50QXA
- RAK-18QPA, RAK-25QPA, RAK-35QPA, RAK-50QPA
- RAF-25QXA, RAF-35QXA, RAF-50QXA
- RAF-25RPA, RAF-35RPA, RAF-50RPA
- RAI-25RPA, RAI-35RPA, RAI-50RPA
- RAD-18RPA, RAD-25RPA, RAD-35RPA, RAD-50RPA
- RAC-25NPA, RAC-35NPA, RAC-50NPA
- RAM-36NP2A
- RAM-53NP2A
- RAM-53NP3A
- RAM-68NP3A
- RAM-70NP4A
- RAM-90NP5A
- RAM-130NP6A (OUTDOOR 1)
- RAM-130NP6A (OUTDOOR 2)
- MONO - SPLIT
- RAK-18PSA, RAK-25PSA, RAK-35PSA
- RAK-18PSAN, RAK-25PSAN, RAK-35PSAN
- RAC-18WSA, RAC-25WSA, RAC-35WSA, RAC-18WSAN, RAC-25WSAN, RAC-35WSAN
- RAK-18PSPA, RAK-25PSPA, RAK-35PSPA
- RAC-18WSPA, RAC-25WSPA, RAC-35WSPA
- RAK-25PXA, RAK-35PXA, RAK-50PXA
- RAC-25WXA, RAC-35WXA
- RAC-50WXA
- RAK-18PPA, RAK-25PPA, RAK-35PPA
- RAC-18WPA, RAC-25WPA
- RAC-35WPA
- RAK-50PPA
- RAC-50WPA
- RAK-60PPA
- RAC-60WPA
- RAK-70PPA
- RAC-70WPA
- RAK-18PEA, RAK-25PEA, RAK-35PEA, RAK-50PEA
- RAC-18WEA, RAC-25WEA
- RAC-35WEA
- RAC-50WEA
- RAF-25PXA, RAF-35PXA, RAF-50PXA
- RAC-25FXA, RAC-35FXA
- RAC-50FXA
- RAF-25RPA, RAF-35RPA, RAF-50RPA
- RAC-25FPA, RAC-35FPA
- RAC-50FPA
- RAD-50PPA, RAD-60PPA, RAD-70PPA
- RAC-50DPA, RAC-60DPA, RAC-70DPA
- MONOZONE/MULTIZONE
- ELECTRICAL WIRING DIAGRAM
- 08_REFRIGERANT_CYCLE_ErP2013(done)
- REFRIGERANT CYCLE
- Monozone/Multizone Indoor Units
- Monozone/Multizone Outdoor Units
- MONO SPLIT
- WALL TYPE: RAK-18PSA/25PSA/35PSA / RAC-18WSA/25WSA/35WSA
- WALL TYPE: RAK-18PSAN/25PSAN/35PSAN / RAC-18WSAN/25WSAN/35WSAN
- WALL TYPE: RAK-18PSPA/25PSPA/35PSPA / RAC-18WSPA/25WSPA/35WSPA
- WALL TYPE: RAK-25PXA / RAC-25WXA
- WALL TYPE: RAK-35PXA / RAC-35WXA
- WALL TYPE: RAK-50PXA / RAC-50WXA
- WALL TYPE: RAK-18PPA/25PPA / RAC-18WPA/25WPA
- WALL TYPE: RAK-35PPA / RAC-35WPA
- WALL TYPE: RAK-50PPA / RAC-50WPA
- WALL TYPE: RAK-60PPA / RAC-60WPA
- WALL TYPE: RAK-70PPA / RAC-70WPA
- WALL TYPE: RAK-18PEA/25PEA / RAC-18WEA/25WEA
- WALL TYPE: RAK-35PEA / RAC-35WEA
- WALL TYPE: RAK-50PEA / RAC-50WEA
- FLOOR TYPE: RAF-25PXA/35PXA / RAC-25FXA/35FXA
- FLOOR TYPE: RAF-50PXA / RAC-50FXA
- FLOOR TYPE: RAF-25RPA / RAC-25FPA
- FLOOR TYPE: RAF-35RPA / RAC-35FPA
- FLOOR TYPE: RAF-50RPA / RAC-50FPA
- DUCT TYPE: RAD-50PPA/60PPA / RAC-50DPA/60DPA
- DUCT TYPE: RAD-70PPA / RAC-70DPA
- REFRIGERANT CYCLE
- 09_REMOTE_CONTROLLERS_OPERA-ErP2013(draft-03D)
- 10_UNITS_INSTALLATION-ErP2013(draft04A)
- UNITS INSTALLATION
- 10.1 INSTALLATION OF INDOOR UNIT
- INSTALLATION OF OUTDOOR UNIT
- FINAL STAGE OF INSTALLATION
- UNITS INSTALLATION
- 11_REFRIGERANT_PIPING_ErP2013(done)
- 12_DRAIN_PIPING_ErP2013(done)
- 13_ELECTRICAL_WIRING-ErP2013(draft01)
- ELECTRICAL WIRING
- General Check
- Electrical wiring for MONOZONE/MULTIZONE Unit
- Procedures of Wiring
- Electrical Wiring for Outdoor unit
- Electrical Wiring for Wall Type Indoor unit
- Electrical Wiring for Floor Type Indoor unit
- Electrical Wiring for 4 Way Ceiling Cassette Type Indoor unit (RAI-25RPA/RAI-35RPA/RAI-50RPA)
- Electrical Wiring for Duct Type Indoor unit (RAD-18RPA/RAD-25RPA/RAD-35RPA/RAD-50RPA/RAD-50PPA/RAD-60PPA/RAD-70PPA)
- Electrical wiring for SINGLE INVERTER Unit
- ELECTRICAL WIRING
- 14_TROUBLESHOOTING_ErP2013(done)
- TROUBLESHOOTING
- PRECAUTIONS FOR TROUBLE SHOOTING
- MONOZONE RAC-25NPA / 35NPA / 50NPA
- MULTIZONE RAM-36NP2A
- MULTIZONE/MONO SPLIT RAM-53NP2A / 53NP3A / 68NP3A / 70NP4A , MONO SPLIT RAF-50PXA/RAC-50FXA
- MULTIZONE RAM-90NP5A
- MULTIZONE RAM-130NP6A
- MONO SPLIT RAK-18/25/35PSA / RAC-18/25/35WSA , RAK-18/25/35PSAN / RAC-18/25/35WSAN , RAK-18/25/35PSPA / RAC-18/25/35WSPA
- MONO SPLIT RAK-18/25/35PPA / RAC-18/25/35WPA , RAK-18/25/35/50PEA / RAC-18/25/35/50WEA , RAF-25/35RPA / RAC-25/35FPA
- MONO SPLIT RAK-50/60/70PPA / RAC-50/60/70WPA
- MONO SPLIT RAF-50RPA / RAC-50FPA
- MONO SPLIT RAF-25/35PXA / RAC-25/35FXA
- MONO SPLIT RAD-50/60/70PPA / RAC-50/60/70DPA
- DISCHARGE PROCEDURE AND POWER SHUT OFF METHOD FOR POWER CIRCUIT
- MONOZONE RAC-25NPA / 35NPA / 50NPA & MULTIZONE RAM-36NP2A / 53NP2A / 53NP3A / 68NP3A / 70NP4A / 130NP6A & MONO SPLIT RAF-50PXA / RAC-50FXA, RAD-50/60/70PPA / RAC-50/60/70DPA
- MULTIZONE RAM-90NP5A
- MONO SPLIT RAK-18/25/35PSA / RAC-18/25/35WSA, RAK-18/25/35PSAN / RAC-18/25/35WSAN , RAK-18/25/35PSPA / RAC-18/25/35WSPA
- MONO SPLIT RAK-18/25/35PPA / RAC-18/25/35WPA, RAK-18/25/35/50PEA / RAC-18/25/35/50WEA , RAF-25/35PXA / RAC-25/35FXA RAF-50RPA / RAC-50FPA
- MONO SPLIT RAK-50/60/70PPA / RAC-50/60/70WPA
- MONO SPLIT RAF-25/35RPA / RAC-25/35FPA
- PRELIMINARY CHECK ON INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING
- CHECKING THE INDOOR UNIT ELECTRICAL PARTS
- No power is detected (no operation)
- Indoor fan does not operate (others are normal) – RAK-25/35/50PXA, RAK-18/25/35/50/70PPA, RAK-18/25/35/50PEA, RAF-25/35/50RPA, RAF-25/35/50PXA, RAD-50/60/70PPA
- Air deflector does not move (others are normal)
- Check the control P.W.B. (power circuit) – RAK-25/35PXA, RAK-18/25/35PPA, RAK-18/25/35/50PEA, RAF-25/35/50RPA, RAF-25/35PXA
- Checking the remote controller
- Outdoor unit does not operate (but receives remote infrared signal)
- All systems stop from several seconds to several minutes after operation is started (all indicators are also off)
- CHECKING OUTDOOR UNIT ELECTRICAL PARTS
- CHECKING BETWEEN GAS LEAKAGE AND COMPRESSOR FAULTY
- TROUBLESHOOTING WHEN INDOOR TIMER LAMP BLINKS
- TROUBLESHOOTING WHEN OUTDOOR LED LAMP BLINKS
- MONOZONE RAC-25NPA / 35NPA / 50NPA
- MULTIZONE
- COMMUNICATION ERROR DIAGNOSIS MULTIZONE RAM- 53NP3A / 68NP3A / 70NP4A / 130NP6A
- COMMUNICATION ERROR DIAGNOSIS MULTIZONE RAM-90NP5A
- MONO SPLIT(RAC-18/25/35WPA, RAC-25/35WXA, RAC-25/35FXA)
- MONO SPLIT (RAC-50WXA, RAC-50FXA
- MONO SPLIT (RAC-50/60/70WPA, RAC-50/60/70DPA)
- CHECKING POWER MODULE
- THERMISTOR
- PRECAUTIONS FOR TROUBLE SHOOTING
- TROUBLESHOOTING
- 15_MISC_Notes_split_ErP2013(done)
- MISCELLANEOUS NOTE
- INSTALLATION AT COLD REGIONS OR SNOWFALL REGIONS.
- INSTALLATION POINTS ON OUTDOOR UNITS IN COLD OR SNOWFALL REGIONS.
- Installation place of Cold and Snowfall Regions
- Considerations to the Seasonal Winds and Snowfall
- Considerations to Snowfall / Snow Buildup
- Considerations to Sliding Snow from Roof or SNOWFALL
- As to Proper Drainage of Defrosting WATER
- Request to cut Net attached to Rear side of Outdoor Unit
- Installation of HOT PIPE
- H-LINK ADAPTOR
- MISCELLANEOUS NOTE
- Back_page(new)
![](/manual/hitachi/rak25pxa/user-manual-english/images/img-595.png)
UNITS INSTALLATION
10-13
CAUTION
• A circuit breaker or fuse must be installed. Without a
circuit breaker or fuse, the danger of electric shock
exists. A main switch with a contact gap of more
than 3.5mm has to be installed in the power supply
line to the outdoor unit.
• Do not install the unit near a location where there is
a flammable gas. The indoor unit may catch fire if
flammable gas leaks around it.
• Be sure to tighten the flare nut to the specified
torque using a toque wrench. If the flare nut is
tightened excessively, it may crack as time elapses,
causing the refrigerant leakage.
• Please ensure smooth flow of water when installing
the drain hose.
• Piping shall be suitable supported with a maximum
spacing of 1m between supports
• An IEC approved power cord should be used. Power
cord type: NYM.
The choice of mounting site
WARNING
• The unit should be mounted at stable, non-vibratory
location which can provide full support to the unit.
CAUTION
• No nearby heat source and no obstruction near the
air outlet is allowed.
• The clearance distances from top right and left are
specified in figure below.
• The location must be convenient for water drainage
and pipe connection with the Outdoor unit.
• To avoid interference from noise, please place the
unit and its remote controller at least 1m from the
radio, television and inverter type fluorescent lamp.
• To avoid any error in signal transmission form the
remote controller, please put the controller far away
from high-frequency machines and high-power
wireless systems.
Indoor unit installation
Piping configuration
may be in three
differ
ent directions:
direct rear piping, right
downward piping and
right sideway piping.
Model Floor
Type
Maximum
piping
length (m)
Minimum
piping
length (m)
Maximum
height (m)
RAF-25RPA
10
5
20
RAF-35RPA
10
5
20
RAF-50RPA
10
5
20
Installation of wall penetration and installation of
protection pipe
1. Hole position
• Make a hole on the wall such as the position
shown below, in order to keep the flow for
condensed water smooth
Hole position
In case of making a hole on
the wall
In case of making a
hole on the floor
Above 150m
Above
100m
Above 200m
Be sure to
completely seal
any gap with
putty
Above 150m
Above
100m
Above
100mm
Above 150mm
Above 200mm
Be sure to
completely seal
any gap with
putty
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the
insulator is insufficient,
please use commercial
products.)
Drain pipe must be
installed separately.
Insulate indoor part of pipe
to prevent condensation
Drain
hose to
be
lower
than
center
of hole