User Manual
Table Of Contents
- Front_page_ErP2013
- TC_Clause
- 00_CONTENTS_ErP_2013
- 01_SYSTEM_DESCRIPTION_ErP2013(190313-draft_10C1a)
- 02_GENERAL_DATA_ErP2013(draft2D)
- 03_DIMENSIONAL_DATA_ErP2013(done)
- -DIMENSIONAL DATA
- MONOZONE / MULTIZONE Indoor Units
- MONOZONE / MULTIZONE Outdoor Units
- MONO SPLIT
- WALL TYPE: RAK-18PSA/25PSA/35PSA/18PSAN/25PSAN/35PSAN
- WALL TYPE: RAC-18WSA/25WSA/35WSA/18WSAN/25WSAN/35WSAN
- WALL TYPE: RAK-18PSPA/25PSPA/35PSPA
- WALL TYPE: RAC-18WSPA/25WSPA/35WSPA
- WALL TYPE: RAK-25PXA/35PXA/50PXA
- WALL TYPE: RAC-25WXA/35WXA
- WALL TYPE: RAC-50WXA
- WALL TYPE: RAK-18PPA/25PPA/35PPA
- WALL TYPE: RAC-18WPA/25WPA
- WALL TYPE: RAC-35WPA
- WALL TYPE: RAK-50PPA
- WALL TYPE: RAC-50WPA
- WALL TYPE : RAK-60PPA
- WALL TYPE: RAC-60WPA
- WALL TYPE: RAK-70PPA
- WALL TYPE: RAC-70WPA
- WALL TYPE: RAK-18PEA/25PEA/35PEA/50PEA
- WALL TYPE: RAC-18WEA/25WEA
- WALL TYPE: RAC-35WEA
- WALL TYPE: RAC-50WEA
- FLOOR TYPE: RAF-25PXA/35PXA/50PXA
- FLOOR TYPE: RAC-25FXA/35FXA
- FLOOR TYPE: RAC-50FXA
- FLOOR TYPE: RAF-25RPA/35RPA/50RPA
- FLOOR TYPE: RAC-25FPA/35FPA
- FLOOR TYPE: RAC-50FPA
- DUCT TYPE: RAD-50PPA/60PPA/70PPA
- DUCT TYPE: RAC-50DPA/60DPA/70DPA
- -DIMENSIONAL DATA
- 04_CAPACITIES_AND_SELECTION-ErP2013(DRAFT04)_3
- 05_WORKING_RANGE_ErP2013(23042012-done)
- 06_ELECTRICAL_DATA_ErP2013(Done)
- 07_A_ELECTRICAL_WIRING_DIAG-ErP2013(draft-03)
- ELECTRICAL WIRING DIAGRAM
- MONOZONE/MULTIZONE
- RAK-18QXA, RAK-25QXA, RAK-35QXA, RAK-50QXA
- RAK-18QPA, RAK-25QPA, RAK-35QPA, RAK-50QPA
- RAF-25QXA, RAF-35QXA, RAF-50QXA
- RAF-25RPA, RAF-35RPA, RAF-50RPA
- RAI-25RPA, RAI-35RPA, RAI-50RPA
- RAD-18RPA, RAD-25RPA, RAD-35RPA, RAD-50RPA
- RAC-25NPA, RAC-35NPA, RAC-50NPA
- RAM-36NP2A
- RAM-53NP2A
- RAM-53NP3A
- RAM-68NP3A
- RAM-70NP4A
- RAM-90NP5A
- RAM-130NP6A (OUTDOOR 1)
- RAM-130NP6A (OUTDOOR 2)
- MONO - SPLIT
- RAK-18PSA, RAK-25PSA, RAK-35PSA
- RAK-18PSAN, RAK-25PSAN, RAK-35PSAN
- RAC-18WSA, RAC-25WSA, RAC-35WSA, RAC-18WSAN, RAC-25WSAN, RAC-35WSAN
- RAK-18PSPA, RAK-25PSPA, RAK-35PSPA
- RAC-18WSPA, RAC-25WSPA, RAC-35WSPA
- RAK-25PXA, RAK-35PXA, RAK-50PXA
- RAC-25WXA, RAC-35WXA
- RAC-50WXA
- RAK-18PPA, RAK-25PPA, RAK-35PPA
- RAC-18WPA, RAC-25WPA
- RAC-35WPA
- RAK-50PPA
- RAC-50WPA
- RAK-60PPA
- RAC-60WPA
- RAK-70PPA
- RAC-70WPA
- RAK-18PEA, RAK-25PEA, RAK-35PEA, RAK-50PEA
- RAC-18WEA, RAC-25WEA
- RAC-35WEA
- RAC-50WEA
- RAF-25PXA, RAF-35PXA, RAF-50PXA
- RAC-25FXA, RAC-35FXA
- RAC-50FXA
- RAF-25RPA, RAF-35RPA, RAF-50RPA
- RAC-25FPA, RAC-35FPA
- RAC-50FPA
- RAD-50PPA, RAD-60PPA, RAD-70PPA
- RAC-50DPA, RAC-60DPA, RAC-70DPA
- MONOZONE/MULTIZONE
- ELECTRICAL WIRING DIAGRAM
- 08_REFRIGERANT_CYCLE_ErP2013(done)
- REFRIGERANT CYCLE
- Monozone/Multizone Indoor Units
- Monozone/Multizone Outdoor Units
- MONO SPLIT
- WALL TYPE: RAK-18PSA/25PSA/35PSA / RAC-18WSA/25WSA/35WSA
- WALL TYPE: RAK-18PSAN/25PSAN/35PSAN / RAC-18WSAN/25WSAN/35WSAN
- WALL TYPE: RAK-18PSPA/25PSPA/35PSPA / RAC-18WSPA/25WSPA/35WSPA
- WALL TYPE: RAK-25PXA / RAC-25WXA
- WALL TYPE: RAK-35PXA / RAC-35WXA
- WALL TYPE: RAK-50PXA / RAC-50WXA
- WALL TYPE: RAK-18PPA/25PPA / RAC-18WPA/25WPA
- WALL TYPE: RAK-35PPA / RAC-35WPA
- WALL TYPE: RAK-50PPA / RAC-50WPA
- WALL TYPE: RAK-60PPA / RAC-60WPA
- WALL TYPE: RAK-70PPA / RAC-70WPA
- WALL TYPE: RAK-18PEA/25PEA / RAC-18WEA/25WEA
- WALL TYPE: RAK-35PEA / RAC-35WEA
- WALL TYPE: RAK-50PEA / RAC-50WEA
- FLOOR TYPE: RAF-25PXA/35PXA / RAC-25FXA/35FXA
- FLOOR TYPE: RAF-50PXA / RAC-50FXA
- FLOOR TYPE: RAF-25RPA / RAC-25FPA
- FLOOR TYPE: RAF-35RPA / RAC-35FPA
- FLOOR TYPE: RAF-50RPA / RAC-50FPA
- DUCT TYPE: RAD-50PPA/60PPA / RAC-50DPA/60DPA
- DUCT TYPE: RAD-70PPA / RAC-70DPA
- REFRIGERANT CYCLE
- 09_REMOTE_CONTROLLERS_OPERA-ErP2013(draft-03D)
- 10_UNITS_INSTALLATION-ErP2013(draft04A)
- UNITS INSTALLATION
- 10.1 INSTALLATION OF INDOOR UNIT
- INSTALLATION OF OUTDOOR UNIT
- FINAL STAGE OF INSTALLATION
- UNITS INSTALLATION
- 11_REFRIGERANT_PIPING_ErP2013(done)
- 12_DRAIN_PIPING_ErP2013(done)
- 13_ELECTRICAL_WIRING-ErP2013(draft01)
- ELECTRICAL WIRING
- General Check
- Electrical wiring for MONOZONE/MULTIZONE Unit
- Procedures of Wiring
- Electrical Wiring for Outdoor unit
- Electrical Wiring for Wall Type Indoor unit
- Electrical Wiring for Floor Type Indoor unit
- Electrical Wiring for 4 Way Ceiling Cassette Type Indoor unit (RAI-25RPA/RAI-35RPA/RAI-50RPA)
- Electrical Wiring for Duct Type Indoor unit (RAD-18RPA/RAD-25RPA/RAD-35RPA/RAD-50RPA/RAD-50PPA/RAD-60PPA/RAD-70PPA)
- Electrical wiring for SINGLE INVERTER Unit
- ELECTRICAL WIRING
- 14_TROUBLESHOOTING_ErP2013(done)
- TROUBLESHOOTING
- PRECAUTIONS FOR TROUBLE SHOOTING
- MONOZONE RAC-25NPA / 35NPA / 50NPA
- MULTIZONE RAM-36NP2A
- MULTIZONE/MONO SPLIT RAM-53NP2A / 53NP3A / 68NP3A / 70NP4A , MONO SPLIT RAF-50PXA/RAC-50FXA
- MULTIZONE RAM-90NP5A
- MULTIZONE RAM-130NP6A
- MONO SPLIT RAK-18/25/35PSA / RAC-18/25/35WSA , RAK-18/25/35PSAN / RAC-18/25/35WSAN , RAK-18/25/35PSPA / RAC-18/25/35WSPA
- MONO SPLIT RAK-18/25/35PPA / RAC-18/25/35WPA , RAK-18/25/35/50PEA / RAC-18/25/35/50WEA , RAF-25/35RPA / RAC-25/35FPA
- MONO SPLIT RAK-50/60/70PPA / RAC-50/60/70WPA
- MONO SPLIT RAF-50RPA / RAC-50FPA
- MONO SPLIT RAF-25/35PXA / RAC-25/35FXA
- MONO SPLIT RAD-50/60/70PPA / RAC-50/60/70DPA
- DISCHARGE PROCEDURE AND POWER SHUT OFF METHOD FOR POWER CIRCUIT
- MONOZONE RAC-25NPA / 35NPA / 50NPA & MULTIZONE RAM-36NP2A / 53NP2A / 53NP3A / 68NP3A / 70NP4A / 130NP6A & MONO SPLIT RAF-50PXA / RAC-50FXA, RAD-50/60/70PPA / RAC-50/60/70DPA
- MULTIZONE RAM-90NP5A
- MONO SPLIT RAK-18/25/35PSA / RAC-18/25/35WSA, RAK-18/25/35PSAN / RAC-18/25/35WSAN , RAK-18/25/35PSPA / RAC-18/25/35WSPA
- MONO SPLIT RAK-18/25/35PPA / RAC-18/25/35WPA, RAK-18/25/35/50PEA / RAC-18/25/35/50WEA , RAF-25/35PXA / RAC-25/35FXA RAF-50RPA / RAC-50FPA
- MONO SPLIT RAK-50/60/70PPA / RAC-50/60/70WPA
- MONO SPLIT RAF-25/35RPA / RAC-25/35FPA
- PRELIMINARY CHECK ON INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING
- CHECKING THE INDOOR UNIT ELECTRICAL PARTS
- No power is detected (no operation)
- Indoor fan does not operate (others are normal) – RAK-25/35/50PXA, RAK-18/25/35/50/70PPA, RAK-18/25/35/50PEA, RAF-25/35/50RPA, RAF-25/35/50PXA, RAD-50/60/70PPA
- Air deflector does not move (others are normal)
- Check the control P.W.B. (power circuit) – RAK-25/35PXA, RAK-18/25/35PPA, RAK-18/25/35/50PEA, RAF-25/35/50RPA, RAF-25/35PXA
- Checking the remote controller
- Outdoor unit does not operate (but receives remote infrared signal)
- All systems stop from several seconds to several minutes after operation is started (all indicators are also off)
- CHECKING OUTDOOR UNIT ELECTRICAL PARTS
- CHECKING BETWEEN GAS LEAKAGE AND COMPRESSOR FAULTY
- TROUBLESHOOTING WHEN INDOOR TIMER LAMP BLINKS
- TROUBLESHOOTING WHEN OUTDOOR LED LAMP BLINKS
- MONOZONE RAC-25NPA / 35NPA / 50NPA
- MULTIZONE
- COMMUNICATION ERROR DIAGNOSIS MULTIZONE RAM- 53NP3A / 68NP3A / 70NP4A / 130NP6A
- COMMUNICATION ERROR DIAGNOSIS MULTIZONE RAM-90NP5A
- MONO SPLIT(RAC-18/25/35WPA, RAC-25/35WXA, RAC-25/35FXA)
- MONO SPLIT (RAC-50WXA, RAC-50FXA
- MONO SPLIT (RAC-50/60/70WPA, RAC-50/60/70DPA)
- CHECKING POWER MODULE
- THERMISTOR
- PRECAUTIONS FOR TROUBLE SHOOTING
- TROUBLESHOOTING
- 15_MISC_Notes_split_ErP2013(done)
- MISCELLANEOUS NOTE
- INSTALLATION AT COLD REGIONS OR SNOWFALL REGIONS.
- INSTALLATION POINTS ON OUTDOOR UNITS IN COLD OR SNOWFALL REGIONS.
- Installation place of Cold and Snowfall Regions
- Considerations to the Seasonal Winds and Snowfall
- Considerations to Snowfall / Snow Buildup
- Considerations to Sliding Snow from Roof or SNOWFALL
- As to Proper Drainage of Defrosting WATER
- Request to cut Net attached to Rear side of Outdoor Unit
- Installation of HOT PIPE
- H-LINK ADAPTOR
- MISCELLANEOUS NOTE
- Back_page(new)
GENERAL DATA
2-25
2.2.15. FLOOR TYPE (RAF-25PXA/35PXA/50PXA)
INDOOR
Unit
RAF-25PXA
RAF-35PXA
RAF-50PXA
Nominal capacity adjustable
-
-
-
Nominal Cooling capacity (min - max)
kW
2.5(0.9-3.1)
3.5(0.9-4.0)
5.0 (0.9-5.2)
Cooling sensible capacity
kW
2.50
2.95
3.80
Nominal Heating capacity (min - max)
kW
3.4(0.9-4.4)
4.5(0.9-5.0)
6.5 (0.9-8.1)
Noise level cooling (sound pressure)
(SL / L / M / H)
dB(A)
20/26/31/38
20/26/31/39
22/29/36/43
Noise level heating (sound pressure)
(SL / L / M / H)
dB(A)
20/26/31/38
20/26/31/39
22/29/36/44
Noise level (sound power)
dB(A)
55
56
59
Air flow cooling mode (SL / L / M / H)
m
3
/h
270/390/510/630
270/390/510/630
300/450/540/720
Air flow heating mode (SL / L / M / H)
m
3
/h
300/420/540/660
300/420/540/660
330/480/570/750
Fan Motor
W
25
25
25
Drain pump pressure lift
cm
-
-
-
Static pressure (SL / L / M / H)
(nominal conditions SP 00)
Pa
-
-
-
Dehumidification
l/h
1.4
1.9
2.8
Included drain pump
no
no
no
Max. height available for drain pump
(RAD/RAI only)
no
no
no
Dimensions (H x W x D)
mm
590x750x215
590x750x215
590x750x215
Panel dimensions (H x W x D)
mm
-
-
-
Weight
kg
15.0
15.0
15.0
Colour (Munsell Code)
Pearl White
Condensate Drain
mm
φ16
φ16
φ16
Panel weight
kg
-
-
-
Panel reference
-
-
-
Color of the panel (RAL)
-
-
-
Running current
A
2.66-2.55/3.63-3.47
4.68-4.48/5.60-5.36
7.16-6.85/8.17-7.82
Power supply
36 V DC from outdoor
unit
37 V DC from outdoor
unit
38 V DC from outdoor
unit
Cable section
mm²
1.250
1.250
1.250
Piping diameter (Liq / Gas)
1/4" / 3/8"
1/4" / 3/8"
1/4" / 1/2"
Drain diameter (ext)
mm
φ16
φ16
φ16
Remote control (standard/optional) *
RAR-5E4/ SPX-RCDB
RAR-5E4/ SPX-RCDB
RAR-5E4/ SPX-RCDB
Filter
ACL Filter
Nano Titanium
Nano Titanium
Nano Titanium
Dimensions (H x W x D)
mm
48x243x8
48x243x8
48x243x8
Pre-filter (Standard / Optional)
Nano Stainless/-
Nano Stainless/-
Nano Stainless/-
*more information regarding remote control can be found in Chapter 9*
NOTE:
1. The nominal cooling and heating capacity is the
combined capacity of the HITACHI standard split
system, and are based on the ISO 5151.
2. The Sound Pressure Level is based on the following
conditions:
- 1.5 meter beneath the Unit
The above data was measured in an anechoic
chamber. Please take into consideration reflected
sound of your specific site
Operation Conditions
Cooling
Heating
Indoor Air Inlet Temperature
dB
27.0 °C
20.0 °C
WB
19.0 °C
Outdoor Air Inlet
Temperature
dB
35.0 °C
7.0 °C
WB
6.0 °C
Piping Length: 5.0 meters; Piping Lift: 0 meter
dB: Dry Bulb; WB: Wet Bulb