UNITS INSTALLATION
Multisplit
(L1+L2+L3++L
n
)= Total maximum Length
TOTAL
Minimum piping length for each indoor unit
is 5m
Maximum piping length for one indoor unit
is 25m.
Height difference between indoor units should not be
more than
Idoor
5m.
Only for RAM-130NP6A
CAUTION
Indoor 3 and Indoor 6 connections to outdoor are COMPULSORY. If not,
ICING at condenser base may occur in the winter season.
Models:
(m)
(m)
(m)
(m)
(m)
TOTAL
(m)
(m)
(m)
Idoor
(m)
RAM-36NP2A >0.7
>0.2 >0.1
>0.1
>0.2 35 5 20 5
RAM-53NP2A >0.7
>0.2 >0.1
>0.1
>0.2 35 5 20 5
RAM-53NP3A >0.7
>0.2 >0.1
>0.1
>0.2 45 5 20 5
RAM-68NP3A >0.7
>0.2 >0.1
>0.1
>0.2 60 5 20 5
RAM-70NP4A >0.7
>0.2 >0.1
>0.1
>0.2 60 5 20 5
RAM-90NP5A >0.5
>0.2 >0.1
>0.1
>0.2 75 5 20 5
RAM-130NP6A >0.7
>0.2 >0.1
>0.1
>0.2 90 5 20 5
Installation of refrigerating pipes and air removal
Please refer to Chapter 11 Refrigerant Piping and
Refrigerant Charge
Connecting of Power cord
Please refer to the Chapter 13 Electrical wiring.
Outdoor unit
Indoor 1
Indoor 2
Indoor 3
Indoor n
L1
L2
L3
LN
Outdoor unit
Indoor 1
Indoor 2
Indoor 3
Indoor n
Maximum
pipe
height
Indoor n
Outdoor unit
Indoor 1
Indoor 2
Indoor 3
Indoor 4
L1
L2
L3
L4
L4
Outdoor unit
Indoor 1
Indoor 2
idoor
Indoor 5
Indoor 6
L5
L6
Give clearance
as wide as
possible
Maximum height
difference
between indoor