DRAIN PIPING
foamed polyethylene) around drain hose, inside
the house, for insulation heat.
Check drain for water leakage. Perform after
connecting power.
If inspection of drainage is not done, water drop
may occur
Add water to water pan of indoor unit as shown
below.
Perform test running of drain pump to check drainage
operation.
Turn power on
Remover cover o felectric box and set the drain
pump test run switch to test.
After checking the drainage, return the switch to
NORMAL
Caution
If drain pump test run is always set to TEST, drain
pump may malfunction
12.4 DUCT TYPE INDOOR
12.4.1 DRAIN PIPE INSTALLATION
Use PVC pipe (polyvinyl chloride) VP20 with the
following outer diameter for(O.D. 26mm) for drain
pipe.
Model
Outer diameter
RAD-25RPA/35RPA/50RPA
26 mm
RAD-50PPA/60PPA/70PPA
32 mm
Be sure to roll insulation (thickness 10mm or
more) from the drain pipe at the indoor side.
Always draw the drain pipe downward so that
water flows smoothly. Fix it (ex. by hanger) to
prevent a peak and trap
12.4.2 CONNECTION OF DRAIN PIPE
1) Securely glue connection part of drain hose and PVC
pipe, using PVC adhesive.
CAUTION
If gluing of drain hose and PVC pipe is too weak, water
leakage may occur.
2) Be sure to wrap generally available insulator (10mm or
more of foamed polyethylene) around drain hose,
inside the house for insulation heat.
3) Perform checking of drain and water leakage after
connecting power supply
Add water to water pan of indoor unit as shown
below
PVC pipe
Drain hose
Indoor unit
To be adhesion
PVC adhesive
PVC pipe
(Purchased in the field)
(Insulation pipe
(100mm or more of
foamed polyethylene)
(Purchase in the field)
Insulation pipe for
drain pipe
Evaporator
Air outlet
Water pan
Pitcher
(Add water)
DRAIN PUMP
TEST SW
NORMAL
TEST
Downward 1/25~1/100
Seal
Insulation (Thickness
10mm or more
Trap
No insulation
Ditch
Stagnant
water
PVC adhesive