User Manual
Table Of Contents
- Front_page_ErP2013
- TC_Clause
- 00_CONTENTS_ErP_2013
- 01_SYSTEM_DESCRIPTION_ErP2013(190313-draft_10C1a)
- 02_GENERAL_DATA_ErP2013(draft2D)
- 03_DIMENSIONAL_DATA_ErP2013(done)
- -DIMENSIONAL DATA
- MONOZONE / MULTIZONE Indoor Units
- MONOZONE / MULTIZONE Outdoor Units
- MONO SPLIT
- WALL TYPE: RAK-18PSA/25PSA/35PSA/18PSAN/25PSAN/35PSAN
- WALL TYPE: RAC-18WSA/25WSA/35WSA/18WSAN/25WSAN/35WSAN
- WALL TYPE: RAK-18PSPA/25PSPA/35PSPA
- WALL TYPE: RAC-18WSPA/25WSPA/35WSPA
- WALL TYPE: RAK-25PXA/35PXA/50PXA
- WALL TYPE: RAC-25WXA/35WXA
- WALL TYPE: RAC-50WXA
- WALL TYPE: RAK-18PPA/25PPA/35PPA
- WALL TYPE: RAC-18WPA/25WPA
- WALL TYPE: RAC-35WPA
- WALL TYPE: RAK-50PPA
- WALL TYPE: RAC-50WPA
- WALL TYPE : RAK-60PPA
- WALL TYPE: RAC-60WPA
- WALL TYPE: RAK-70PPA
- WALL TYPE: RAC-70WPA
- WALL TYPE: RAK-18PEA/25PEA/35PEA/50PEA
- WALL TYPE: RAC-18WEA/25WEA
- WALL TYPE: RAC-35WEA
- WALL TYPE: RAC-50WEA
- FLOOR TYPE: RAF-25PXA/35PXA/50PXA
- FLOOR TYPE: RAC-25FXA/35FXA
- FLOOR TYPE: RAC-50FXA
- FLOOR TYPE: RAF-25RPA/35RPA/50RPA
- FLOOR TYPE: RAC-25FPA/35FPA
- FLOOR TYPE: RAC-50FPA
- DUCT TYPE: RAD-50PPA/60PPA/70PPA
- DUCT TYPE: RAC-50DPA/60DPA/70DPA
- -DIMENSIONAL DATA
- 04_CAPACITIES_AND_SELECTION-ErP2013(DRAFT04)_3
- 05_WORKING_RANGE_ErP2013(23042012-done)
- 06_ELECTRICAL_DATA_ErP2013(Done)
- 07_A_ELECTRICAL_WIRING_DIAG-ErP2013(draft-03)
- ELECTRICAL WIRING DIAGRAM
- MONOZONE/MULTIZONE
- RAK-18QXA, RAK-25QXA, RAK-35QXA, RAK-50QXA
- RAK-18QPA, RAK-25QPA, RAK-35QPA, RAK-50QPA
- RAF-25QXA, RAF-35QXA, RAF-50QXA
- RAF-25RPA, RAF-35RPA, RAF-50RPA
- RAI-25RPA, RAI-35RPA, RAI-50RPA
- RAD-18RPA, RAD-25RPA, RAD-35RPA, RAD-50RPA
- RAC-25NPA, RAC-35NPA, RAC-50NPA
- RAM-36NP2A
- RAM-53NP2A
- RAM-53NP3A
- RAM-68NP3A
- RAM-70NP4A
- RAM-90NP5A
- RAM-130NP6A (OUTDOOR 1)
- RAM-130NP6A (OUTDOOR 2)
- MONO - SPLIT
- RAK-18PSA, RAK-25PSA, RAK-35PSA
- RAK-18PSAN, RAK-25PSAN, RAK-35PSAN
- RAC-18WSA, RAC-25WSA, RAC-35WSA, RAC-18WSAN, RAC-25WSAN, RAC-35WSAN
- RAK-18PSPA, RAK-25PSPA, RAK-35PSPA
- RAC-18WSPA, RAC-25WSPA, RAC-35WSPA
- RAK-25PXA, RAK-35PXA, RAK-50PXA
- RAC-25WXA, RAC-35WXA
- RAC-50WXA
- RAK-18PPA, RAK-25PPA, RAK-35PPA
- RAC-18WPA, RAC-25WPA
- RAC-35WPA
- RAK-50PPA
- RAC-50WPA
- RAK-60PPA
- RAC-60WPA
- RAK-70PPA
- RAC-70WPA
- RAK-18PEA, RAK-25PEA, RAK-35PEA, RAK-50PEA
- RAC-18WEA, RAC-25WEA
- RAC-35WEA
- RAC-50WEA
- RAF-25PXA, RAF-35PXA, RAF-50PXA
- RAC-25FXA, RAC-35FXA
- RAC-50FXA
- RAF-25RPA, RAF-35RPA, RAF-50RPA
- RAC-25FPA, RAC-35FPA
- RAC-50FPA
- RAD-50PPA, RAD-60PPA, RAD-70PPA
- RAC-50DPA, RAC-60DPA, RAC-70DPA
- MONOZONE/MULTIZONE
- ELECTRICAL WIRING DIAGRAM
- 08_REFRIGERANT_CYCLE_ErP2013(done)
- REFRIGERANT CYCLE
- Monozone/Multizone Indoor Units
- Monozone/Multizone Outdoor Units
- MONO SPLIT
- WALL TYPE: RAK-18PSA/25PSA/35PSA / RAC-18WSA/25WSA/35WSA
- WALL TYPE: RAK-18PSAN/25PSAN/35PSAN / RAC-18WSAN/25WSAN/35WSAN
- WALL TYPE: RAK-18PSPA/25PSPA/35PSPA / RAC-18WSPA/25WSPA/35WSPA
- WALL TYPE: RAK-25PXA / RAC-25WXA
- WALL TYPE: RAK-35PXA / RAC-35WXA
- WALL TYPE: RAK-50PXA / RAC-50WXA
- WALL TYPE: RAK-18PPA/25PPA / RAC-18WPA/25WPA
- WALL TYPE: RAK-35PPA / RAC-35WPA
- WALL TYPE: RAK-50PPA / RAC-50WPA
- WALL TYPE: RAK-60PPA / RAC-60WPA
- WALL TYPE: RAK-70PPA / RAC-70WPA
- WALL TYPE: RAK-18PEA/25PEA / RAC-18WEA/25WEA
- WALL TYPE: RAK-35PEA / RAC-35WEA
- WALL TYPE: RAK-50PEA / RAC-50WEA
- FLOOR TYPE: RAF-25PXA/35PXA / RAC-25FXA/35FXA
- FLOOR TYPE: RAF-50PXA / RAC-50FXA
- FLOOR TYPE: RAF-25RPA / RAC-25FPA
- FLOOR TYPE: RAF-35RPA / RAC-35FPA
- FLOOR TYPE: RAF-50RPA / RAC-50FPA
- DUCT TYPE: RAD-50PPA/60PPA / RAC-50DPA/60DPA
- DUCT TYPE: RAD-70PPA / RAC-70DPA
- REFRIGERANT CYCLE
- 09_REMOTE_CONTROLLERS_OPERA-ErP2013(draft-03D)
- 10_UNITS_INSTALLATION-ErP2013(draft04A)
- UNITS INSTALLATION
- 10.1 INSTALLATION OF INDOOR UNIT
- INSTALLATION OF OUTDOOR UNIT
- FINAL STAGE OF INSTALLATION
- UNITS INSTALLATION
- 11_REFRIGERANT_PIPING_ErP2013(done)
- 12_DRAIN_PIPING_ErP2013(done)
- 13_ELECTRICAL_WIRING-ErP2013(draft01)
- ELECTRICAL WIRING
- General Check
- Electrical wiring for MONOZONE/MULTIZONE Unit
- Procedures of Wiring
- Electrical Wiring for Outdoor unit
- Electrical Wiring for Wall Type Indoor unit
- Electrical Wiring for Floor Type Indoor unit
- Electrical Wiring for 4 Way Ceiling Cassette Type Indoor unit (RAI-25RPA/RAI-35RPA/RAI-50RPA)
- Electrical Wiring for Duct Type Indoor unit (RAD-18RPA/RAD-25RPA/RAD-35RPA/RAD-50RPA/RAD-50PPA/RAD-60PPA/RAD-70PPA)
- Electrical wiring for SINGLE INVERTER Unit
- ELECTRICAL WIRING
- 14_TROUBLESHOOTING_ErP2013(done)
- TROUBLESHOOTING
- PRECAUTIONS FOR TROUBLE SHOOTING
- MONOZONE RAC-25NPA / 35NPA / 50NPA
- MULTIZONE RAM-36NP2A
- MULTIZONE/MONO SPLIT RAM-53NP2A / 53NP3A / 68NP3A / 70NP4A , MONO SPLIT RAF-50PXA/RAC-50FXA
- MULTIZONE RAM-90NP5A
- MULTIZONE RAM-130NP6A
- MONO SPLIT RAK-18/25/35PSA / RAC-18/25/35WSA , RAK-18/25/35PSAN / RAC-18/25/35WSAN , RAK-18/25/35PSPA / RAC-18/25/35WSPA
- MONO SPLIT RAK-18/25/35PPA / RAC-18/25/35WPA , RAK-18/25/35/50PEA / RAC-18/25/35/50WEA , RAF-25/35RPA / RAC-25/35FPA
- MONO SPLIT RAK-50/60/70PPA / RAC-50/60/70WPA
- MONO SPLIT RAF-50RPA / RAC-50FPA
- MONO SPLIT RAF-25/35PXA / RAC-25/35FXA
- MONO SPLIT RAD-50/60/70PPA / RAC-50/60/70DPA
- DISCHARGE PROCEDURE AND POWER SHUT OFF METHOD FOR POWER CIRCUIT
- MONOZONE RAC-25NPA / 35NPA / 50NPA & MULTIZONE RAM-36NP2A / 53NP2A / 53NP3A / 68NP3A / 70NP4A / 130NP6A & MONO SPLIT RAF-50PXA / RAC-50FXA, RAD-50/60/70PPA / RAC-50/60/70DPA
- MULTIZONE RAM-90NP5A
- MONO SPLIT RAK-18/25/35PSA / RAC-18/25/35WSA, RAK-18/25/35PSAN / RAC-18/25/35WSAN , RAK-18/25/35PSPA / RAC-18/25/35WSPA
- MONO SPLIT RAK-18/25/35PPA / RAC-18/25/35WPA, RAK-18/25/35/50PEA / RAC-18/25/35/50WEA , RAF-25/35PXA / RAC-25/35FXA RAF-50RPA / RAC-50FPA
- MONO SPLIT RAK-50/60/70PPA / RAC-50/60/70WPA
- MONO SPLIT RAF-25/35RPA / RAC-25/35FPA
- PRELIMINARY CHECK ON INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING
- CHECKING THE INDOOR UNIT ELECTRICAL PARTS
- No power is detected (no operation)
- Indoor fan does not operate (others are normal) – RAK-25/35/50PXA, RAK-18/25/35/50/70PPA, RAK-18/25/35/50PEA, RAF-25/35/50RPA, RAF-25/35/50PXA, RAD-50/60/70PPA
- Air deflector does not move (others are normal)
- Check the control P.W.B. (power circuit) – RAK-25/35PXA, RAK-18/25/35PPA, RAK-18/25/35/50PEA, RAF-25/35/50RPA, RAF-25/35PXA
- Checking the remote controller
- Outdoor unit does not operate (but receives remote infrared signal)
- All systems stop from several seconds to several minutes after operation is started (all indicators are also off)
- CHECKING OUTDOOR UNIT ELECTRICAL PARTS
- CHECKING BETWEEN GAS LEAKAGE AND COMPRESSOR FAULTY
- TROUBLESHOOTING WHEN INDOOR TIMER LAMP BLINKS
- TROUBLESHOOTING WHEN OUTDOOR LED LAMP BLINKS
- MONOZONE RAC-25NPA / 35NPA / 50NPA
- MULTIZONE
- COMMUNICATION ERROR DIAGNOSIS MULTIZONE RAM- 53NP3A / 68NP3A / 70NP4A / 130NP6A
- COMMUNICATION ERROR DIAGNOSIS MULTIZONE RAM-90NP5A
- MONO SPLIT(RAC-18/25/35WPA, RAC-25/35WXA, RAC-25/35FXA)
- MONO SPLIT (RAC-50WXA, RAC-50FXA
- MONO SPLIT (RAC-50/60/70WPA, RAC-50/60/70DPA)
- CHECKING POWER MODULE
- THERMISTOR
- PRECAUTIONS FOR TROUBLE SHOOTING
- TROUBLESHOOTING
- 15_MISC_Notes_split_ErP2013(done)
- MISCELLANEOUS NOTE
- INSTALLATION AT COLD REGIONS OR SNOWFALL REGIONS.
- INSTALLATION POINTS ON OUTDOOR UNITS IN COLD OR SNOWFALL REGIONS.
- Installation place of Cold and Snowfall Regions
- Considerations to the Seasonal Winds and Snowfall
- Considerations to Snowfall / Snow Buildup
- Considerations to Sliding Snow from Roof or SNOWFALL
- As to Proper Drainage of Defrosting WATER
- Request to cut Net attached to Rear side of Outdoor Unit
- Installation of HOT PIPE
- H-LINK ADAPTOR
- MISCELLANEOUS NOTE
- Back_page(new)
DRAIN PIPING
12-5
12.5 DRAIN PUMP
12.5.1 BUILD IN DRAIN PUMP
The air conditioner is equipped with an internal drain pump
to remove accumulated condensation water from drain pan
even while it is operating. A float switch
• Monitors the water level and automatically activates
the pump as necessary.
*Applicable for
ceiling cassette
type indoor and
duct type indoor
only.
12.5.2 SPECIFICATION OF DRAIN PUMP
Applicable models
RAI-25RPA, RAI-35RPA, RAI
50RPA
RAD-18RPA, RAD-25RPA,
RAD-35RPA, RAD-50RPA
RAD-50PPA, RAD-60PPA,
RAD-70PPA
Fluid
Water
Water
Water
Fluid temperature
o
C
0 ~ 40
0 ~ 40
0 ~ 40
Ambient temperature
o
C
0 ~ 40
0 ~ 40
-10 ~ 50
Max humidity %
95 and below
95 and below
95 and below
Storage temperature
o
C
-10~70
o
C
-10~70
o
C
-20~80
o
C
Mounting direction
Shall be install upward
Slanting gradient should be
less than 5 degree
Shall be install upward
Slanting gradient should be
less than 5 degree
Shall be install upward
Slanting gradient should be
less than 10 degree
Motor type
DC brushless motor
(insulation class E)
DC brushless motor
(insulation class E)
DC 2-pole motor
(insulation class E)
Maximum lift
Lift 300mm water in rated
voltage
Lift 300mm water in rated
voltage
Lift 500mm water in rated
voltage
Minimum water level
8mm
8mm
6mm
Noise
45dB max
45dB max
37dB max
Insulation resistance
100M
Ω
at DC500V
100M
Ω
at DC500V
100M
Ω
at DC500V
Life span
Operate continuously up to
10,000 hours, under 300mm
lift, 10mm water level, rated
voltage, and rated water
temperature
Operate continuously up to
10,000 hours, under 300mm
lift, 10mm water level, rated
voltage, and rated water
temperature
Operate continuously up to
15,000 hours, under 500mm
lift, 10mm water level, rated
voltage, and rated water
temperature
12.6 CONDENSED WATER DISPOSAL OF
OUTDOOR UNIT
• There are holes on the base of Outdoor unit for
condensed water to discharge
• In order to drain out the condensed water, the unit
is installed on a stand or a block so that the unit is
100mm above the ground as the shown figure.
Join the drain pipe to one hole.
• At first insert one portion of the hook to the base
(Portion A), then pull the drain pipe in the direction
shown by the arrow while inserting the hook into
the base. After installation, check whether the
drain pipe cling to the base firmly.
When Use and Install in Cold Areas
• When using in cold region with severe cold
climate and heavy snow, water discharged from
the heat exchanger will freeze on the base
surface and this may block the drainage. In such
regions, remove the bush on the bottom face of
outdoor unit to prevent water build up leading to
icing and blockage. Keep a minimum gap of
250mm between the base and the ground. When
using drain pipe, consult your sales agent
DRAIN PIPE
BASE
A
DRAIN PIPE
BUSH
BUSH
100mm ABOVE