TROUBLESHOOTING
9 times
outdoor is interrupted
Open connection on the C-D cable.
Interface circuit of indoor/outdoor unit.
Abnormal power voltage Abnormal power source is detected.
Abnormal power source
Cable is wrongly connected
Main P.W.B.
10 times
Fan lock error
Outdoor fan actual rpm could not
reach as per instructed.
Outdoor fan motor
Fan motor circuit.
12 times
EEPROM read error
Microcomputer cannot read the data
in EEPROM.
Main P.W.B.
13 times
Example of blinking (5 times)
14.8.6 MONO SPLIT (RAC-50WXA, RAC-50FXA
SELF-DIAGNOSIS LIGHTING MODE
: LIGHT
: BLINK
: OFF
LD301 LD302 SELF DIAGNOSIS NAME DETAIL MAIN CHECK POINT
1. DURING OPERATION LD303 (RED) LIGHTS.
Normal operation Compressor operation Not malfunction
Overload (1)
The rotation speed is automatically controlled to
protect the compressor in the overload
condition.
This shows an overload but not malfunction.
Overload (2)
Overload (3)
2. DURING STOP
LD303 (RED) GOES OFF.
Normal stop Stopped by Thermostat or Controller NOT MALFUNCTION
Reset stop
Microprocessor was re-booted. (It is
NORMAL when power SW has been
turned ON)
Main P.W.B.
1 time
Peak current cut
Compressor Peak Current was
beyond the maximum limit
Main P.W.B.
Compressor
2 times
Abnormal low speed rotation
Compressor Rotor position could not
be detected.
Main P.W.B.
Compressor
3 times
Switching failure
Switching from low frequency sync
start to position detection operation
failure
Main P.W.B.
Compressor
4 times
Overload lower limit cut
Overload protection mechanism is
requesting compressor to run at a
speed lower than the minimum
speed limit
Outdoor unit is exposed to direct sunlight or
its airflow is blocked.
Fan motor Main PWB
The Voltage is extremely LOW
5 times
OH thermistor temperature rise
OH thermistor detected compressor
overheat
Leak of refrigerant.
Compressor
OH thermistor circuit.
6 times
Thermistor abnormal
Abnormal thermistor value was
detected (Open or Short)
Thermistor.
Connection of thermistor defective.
Thermistor circuit.
7 times
Acceleration failure
Compressor acceleration was not
more that the minimum speed
setting.
Leak of refrigerant.
Compressor.
8 times
Communication error
Communication between indoor and
outdoor is interrupted
C-D cable wrongly connected
Open connection on the C-D cable.
Interface circuit of indoor/outdoor unit.
9 times
Abnormal power voltage Abnormal power source is detected.
Abnormal power source
Cable is wrongly connected
Main P.W.B.
10 times
2SEC
Lights for 0.25 sec at
interval of 0.25 sec
TIME
SET
VALUE
ROTATION
SPEED
(1)
(2)
(3)
TIME
SET VALUE
(1)
(2)
(3)
ROTATION
SPEED