WJ200 Series Inverter Quick Reference Guide • Single-phase Input 200V class • Three-phase Input 200V class • Three-phase Input 400V class Manual Number: NT3251AX March 2012 Refer to the user manual for detail Hitachi Industrial Equipment Systems Co., Ltd.
UL® Cautions, Warnings and Instructions xii Warnings and Cautions for Troubleshooting and Maintenance (Standard to comply with : UL508C,CSA C22.2 No.14-05) Warning Markings GENERAL: These devices are open type Power Conversion Equipment. They are intended to be used in an enclosure. Insulated gate bipolar transistor (IGBT) incorporating microprocessor technology.
Terminal symbols and Screw size Inverter Model WJ200-001S WJ200-002S WJ200-004S WJ200-007S WJ200-015S WJ200-022S WJ200-001L WJ200-002L WJ200-004L WJ200-007L WJ200-015L WJ200-022L WJ200-037L WJ200-055L WJ200-075L WJ200-110L WJ200-150L WJ200-004H WJ200-007H WJ200-015H WJ200-022H WJ200-030H WJ200-040H WJ200-055H WJ200-075H WJ200-110H WJ200-150H Screw Size Required Torque (N-m) Wire range M3.5 1.0 AWG16 (1.3mm2) M4 1.4 AWG12 (3.3mm2) M4 1.4 AWG10 (5.3mm2) M3.5 1.0 AWG16 (1.3mm2) M4 M4 M4 1.
Fuse Sizes Distribution fuse size marking is included in the manual to indicate that the unit shall be connected with a Listed Cartridge Nonrenewable fuse, rated 600 Vac with the current ratings as shown in the table below or Type E Combination Motor Controller marking is included in the manual to indicate that the unit shall be connected with,LS Industrial System Co.
Inverter Specification Label The Hitachi WJ200 inverters have product labels located on the right side of the housing, as pictured below. Be sure to verify that the specifications on the labels match your power source, and application safety requirements. Model name -001SF 200-240 Input ratings Output ratings MFG number 200-240 05A_T12345_A_-001 Ver:2.0 2.0/1.3 1.2/1.
WJ200 Inverter Specifications Model-specific tables for 200V and 400V class inverters The following tables are specific to WJ200 inverters for the 200V and 400V class model groups. Note that “General Specifications” on page in this chapter apply to both voltage class groups. Footnotes for all specification tables follow the table below.
WJ200 Inverter Specifications, continued… Item WJ200 inverters, 200V models Applicable motor size kW HP Rated capacity (kVA) 200V 240V Rated input voltage Rated output voltage Rated output current (A) VT CT VT CT VT CT VT CT VT CT Starting torque Braking Without resistor With resistor DC braking Weight kg lb Item WJ200 inverters, 200V models Applicable motor size kW HP Rated capacity (kVA) 200V 240V Rated input voltage Rated output voltage Rated output current (A) VT CT VT CT VT CT VT CT VT CT S
WJ200 Inverter Specifications, continued… Item WJ200 inverters, 400V models Applicable motor size kW HP Rated capacity (kVA) 380V 480V Rated input voltage Rated output voltage Rated output current (A) VT CT VT CT VT CT VT CT VT CT Starting torque Braking Without resistor With resistor DC braking Weight kg lb Item WJ200 inverters, 400V models Applicable motor size kW HP Rated capacity (kVA) 380V 480V Rated input voltage Rated output voltage Rated output current (A) VT CT VT CT VT CT VT CT VT CT S
The following table shows which models need derating.
Basic System Description A motor control system will obviously include a motor and inverter, as well as a circuit breaker or fuses for safety. If you are connecting a motor to the inverter on a test bench just to get started, that’s all you may need for now. But a system can also have a variety of additional components. Some can be for noise suppression, while others may enhance the inverter’s braking performance.
Determining Wire and Fuse Sizes The maximum motor currents in your application determines the recommended wore size. The following table gives the wire size in AWG. The “Power Lines” column applies to the inverter input power, output wires to the motor, the earth ground connection, and any other components shown in the “Basic System Description” on page 9. The “Signal Lines” column applies to any wire connecting to the two green connectors just inside the front cover panel.
Wire the Inverter Input to a Supply In this step, you will connect wiring to the input of the inverter. First, you must determine whether the inverter model you have required three-phase power only, or single-phase power only. All models have the same power connection terminals [R/L1], [S/L2], and [T/L3].
Three-phase 200V 3.7kW Three-phase 400V 4.0kW R/L1 Chassis Ground (M4) S/L2 RB PD/+1 T/L3 U/T1 V/T2 W/T3 Power input P/+ N/- Output to Motor Three-phase 200V 5.5, 7.5kW Three-phase 400V 5.5, 7.
Three-phase 200V 11kW Three-phase 400V 11, 15kW R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 P/+ N/- RB PD/+1 Power input G G Output to Motor Three-phase 200V 15kW R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 P/+ N/- RB PD/+1 Power input G G Output to Motor NOTE: An inverter powered by a portable power generator may receive a distorted power waveform, overheating the generator. In general, the generator capacity should be five times that of the inverter (kVA).
Using the Front Panel Keypad Please take a moment to familiarize yourself with the keypad layout shown in the figure below. The display is used in programming the inverter’s parameters, as well as monitoring specific parameter values during operation.
Keys, Modes, and Parameters The purpose of the keypad is to provide a way to change modes and parameters. The term function applies to both monitoring modes and parameters. These are all accessible through function codes that are primary 4-character codes. The various functions are separated into related groups identifiable by the left-most character, as the table shows.
Func. code display SET Group "d" Func. code display : Moves to data display SET d001 V 0.00 ESC U d002 Func. code display ESC : Jumps to the next group d104 ESC Group "F" Func. code display Save SET F001 V 50.00 U SET ESC SET ESC F002 50.01 Data display (F001 to F003) Data does not blink because of real time synchronizing F004 ESC Group "A" Func. code display SET : Saves the data in EEPROM ESC : Returns to func. code display without saving data. and returns to func. code display.
[Setting example] After power ON, changing from 0.00 display to change the A002 (Run command source) data. Data of d001 will be shown on the display after the first power ON Press [ESC] key to show the function code ESC 0.00 d001 ESC SET Press [ESC] key to move on to the function group F001 F001 ESC Press [ESC] key Once to move on to the function group A001. A001 U V Press Up key to change increase A002) function code (A001 Press SET key to display the data of A002 SET Display is solid lighting.
When a function code is shown… ESC key Move on to the next function group SET key Move on to the data display When a data is shown… Cancels the change and moves back to the function code Fix and stores the data and moves back to the function code U key Increase function code Increase data value V key Decrease function code Decrease data value Note Keep pressing for more than 1 second leads to d001 display, regardless the display situation.
Connecting to PLCs and Other Devices Hitachi inverters (drives) are useful in many types of applications. During installation, the inverter keypad (or other programming device) will facilitate the initial configuration. After installation, the inverter will generally receive its control commands through the control logic connector or serial interface from another controlling device.
Example Wiring Diagram The schematic diagram below provides a general example of logic connector wiring, in addition to basic power and motor wiring converted in Chapter 2. The goal of this chapter is to help you determine the proper connections for the various terminals shown below for your application needs.
Control Logic Signal Specifications The control logic connectors are located just behind the front housing cover. The relay contacts are just to the left of the logic connectors. Connector labeling is shown below. RS485 comm. SN Relay contacts Logic inputs 7 6 5 4 3 2 1 L PLC P24 Jumper wire SP EO EA AL2 AL1 AL0 H RS485 Pulse Pulse comm.
O Terminal Name Description Analog voltage input H SP, SN AL0, AL1, AL2 *3 +10V analog reference Serial communication terminal Relay common contact Note 1: Note 2: Note 3: Ratings 0 to 9.8 VDC range, 10 VDC nominal, input impedance 10 kΩ 10VDC nominal, 10mA max. For RS485 Modbus communication. 250VAC, 2.5A (R load) max. 250VAC, 0.2A (I load, P.F.=0.4) max. 100VAC, 10mA min. 30VDC, 3.0A (R load) max. 30VDC, 0.7A (I load, P.F.=0.4) max. 5VDC, 100mA min.
Sink/source logic of intelligent input terminals Sink or source logic is switched by a jumper wire as below. Sink logic 2 1 Source logic L PLC P24 2 Jumper wire 1 L PLC P24 Jumper wire Wire size for control and relay terminals Use wires within the specifications listed below. For safe wiring and reliability, it is recommended to use ferrules, but if solid or stranded wire is used, stripping length should be 8mm.
Recommended ferrule For safe wiring and reliability, it is recommended to use following ferrules. Wire size mm2 (AWG) 0.25 (24) Model name of ferrule * AI 0.25-8YE 0.34 (22) 0.5 (20) L [mm] Φd [mm] ΦD [mm] 12.5 0.8 2.0 AI 0.34-8TQ 12.5 0.8 2.0 AI 0.5-8WH 14 1.1 2.5 0.75 (18) AI 0.75-8GY 14 1.3 * Supplier: Phoenix contact Crimping pliers: CRIPMFOX UD 6-4 or CRIMPFOX ZA 3 2.8 Φd 8 L ΦD How to connect? (1) Push down an orange actuating lever by a slotted screwdriver (width 2.5mm max.).
Intelligent Terminal Listing Intelligent Inputs Use the following table to locate pages for intelligent input material in this chapter.
Use the following table to locate pages for intelligent input material in this chapter. Symbol DISP NO Code 86 255 Input Function Summary Table Function Name Display limitation No assign Page Intelligent Outputs Use the following table to locate pages for intelligent output material in this chapter.
Using Intelligent Input Terminals Terminals [1], [2], [3], [4], [5], [6] and [7] are identical, programmable inputs for general use. The input circuits can use the inverter’s internal (isolated) +24V field supply or an external power supply. This section describes input circuits operation and how to connect them properly to switches or transistor outputs on field devices. The WJ200 inverter features selectable sinking or sourcing inputs.
The two diagrams below input wiring circuits using the inverter’s internal +24V supply. Each diagram shows the connection for simple switches, or for a field device with transistor outputs. Note that in the lower diagram, it is necessary to connect terminal [L] only when using the field device with transistors. Be sure to use the correct connection of the jumper wire shown for each wiring diagram.
The two diagrams below show input wiring circuits using an external supply. If using the “Sinking Inputs, External Supply” in below wiring diagram, be sure to remove the jumper wire, and use a diode (*) with the external supply. This will prevent a power supply contention in case the jumper wire is accidentally placed in the incorrect position. For the “Sourcing Inputs, External Supply”, please connect the jumper wire as drawn in the diagram below.
CAUTION: Be sure to diode in between "P24" and "PLC" when connecting plural inverters with digital input wiring in common. The power to the inverter control part can be supplied externally as shown below. Except driving motor, it is possible read and write the parameters by keypad and via communication even the drive itself is not powered. By having ability inverter doesn’t block the current flowing into itself when it is not powered.
Forward Run/Stop and Reverse Run/Stop Commands: When you input the Run command via the terminal [FW], the inverter executes the Forward Run command (high) or Stop command (low). When you input the Run command via the terminal [RV], the inverter executes the Reverse Run command (high) or Stop command (low).
Multi-Speed Select ~Binary Operation The inverter can store up to 16 different target frequencies (speeds) that the motor output uses for steady-state run condition. These speeds are accessible through programming four of the intelligent terminals as binary-encoded inputs CF1 to CF4 per the table to the right. These can be any of the six inputs, and in any order. You can use fewer inputs if you need eight or fewer speeds.
Two Stage Acceleration and Deceleration When terminal [2CH] is turned ON, the inverter changes the rate of acceleration and deceleration from the initial settings (F002 and F003) to use the second set of acceleration/ deceleration values. When the terminal is turned OFF, the inverter is returned to the original acceleration and deceleration time (F002 acceleration time 1, and F003 deceleration time 1).
Unattended Start Protection If the Run command is already set when power is turned ON, the inverter starts running immediately after powerup. The Unattended Start Protection (USP) function prevents that automatic startup, so that the inverter will not run without outside intervention. When USP is active and you need to reset an alarm and resume running, either turn the Run command OFF, or perform a reset operation by the terminal [RS] input or the keypad Stop/reset key.
Reset Inverter The [RS] terminal causes the inverter to execute the reset operation. If the inverter is in Trip Mode, the reset cancels the Trip state. When the signal [RS] is turned ON and OFF, the inverter executes the reset operation. The minimum pulse width for [RS] must be 12 ms or greater. The alarm output will be cleared within 30 ms after the onset of the Reset command. 12 ms minimum 1 [RS] 0 Approx.
Using Intelligent Output Terminals Run Signal When the [RUN] signal is selected as an 1 intelligent output terminal, the inverter outputs [FW,RV] 0 a signal on that terminal when it is in Run Mode. The output logic is active low, and is B082 Output the open collector type (switch to ground). frequency Run signal Option Code 00 Terminal Symbol RUN Valid for inputs: Required settings Function Name Run Signal State ON OFF start freq.
Frequency Arrival Signals The Frequency Arrival group of outputs helps coordinate external systems with the current velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output frequency arrives at the standard set frequency (parameter F001). Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility. For example, you can have an output turn ON at one frequency during acceleration, and have it turn OFF at a different frequency during deceleration.
Frequency arrival output [FA1] uses the standard output frequency (parameter F001) as the threshold for switching. In the figure to the right, Frequency Arrival [FA1] turns ON when the output frequency gets within Fon Hz below or Fon Hz above the target constant frequency, where Fon is 1% of the set maximum frequency and Foff is 2% of the set maximum frequency. This provides hysteresis that prevents output chatter near the threshold value.
Alarm Signal The inverter alarm signal is active when a fault has occurred and it is in the Trip Mode (refer to the diagram at right). When the fault is cleared the alarm signal becomes inactive. Run STOP RESET Stop RUN STOP RESET We must make a distinction between the alarm signal Trip AL and the alarm relay contacts [AL0], [AL1] and [AL2]. Fault Fault The signal AL is a logic function, which you can assign Alarm signal active to the open collector output terminals [11], [12], or the relay outputs.
The alarm relay output can be configured in two main ways: • Trip/Power Loss Alarm – The alarm relay is configured as normally closed (C036=01) by default, shown below (left). An external alarm circuit that detects broken wiring also as an alarm connects to [AL0] and [AL1]. After powerup and short delay (< 2 seconds), the relay energizes and the alarm circuit is OFF.
Analog Input Operation The WJ200 inverters provide for analog input to command the inverter frequency output value. The analog input terminal group includes the [L], [OI], [O], and [H] terminals on the control connector, which provide for Voltage [O] or Current [OI] input. All analog input signals must use the analog ground [L]. If you use either the voltage or current analog input, you must select one of them using the logic input terminal function [AT] analog type.
The following table shows the available analog input settings. Parameter A005 and the input terminal [AT] determine the External Frequency Command input terminals that are available, and how they function. The analog inputs [O] and [OI] use terminal [L] as the reference (signal return).
Pulse Train Input Operation The WJ200 inverter is capable of accepting pulse train input signals, that are used for frequency command, process variable (feedback) for PID control, and simple positioning. The dedicated terminal is called “EA” and “EB”. Terminal “EA” is a dedicated terminal, and the terminal “EB” is an intelligent terminal, that has to be changed by a parameter setting. RS485 comm.
Analog Output Operation In inverter applications it is useful to monitor the inverter operation from a remote location or from the front panel of an inverter enclosure. In some cases, this requires only a panel-mounted volt meter. In other cases, a controller such as a PLC may provide the inverter’s frequency command, and require inverter feedback data (such as output frequency or output current) to confirm actual operation. The analog output terminal [AM] serves these purposes.
The [AM] signal offset and gain are adjustable, as indicated below. Func. C106 C109 Description [AM] output gain [AM] output offset Range 0.~255. 0.0~10.0 Default 100. 0.0 The graph below shows the effect of the gain and offset setting. To calibrate the [AM] output for your application (analog meter), follow the steps below: 1. Run the motor at the full scale speed, or most common operating speed. a.
Monitoring functions NOTE:. Mark “ ” in b031=10 shows the accessible parameters when b031 is set “10”, high level access. * Please change from"04 (Basic display)" to "00 (Full display)" in parameter B037 (Function code display restriction), in case some parameters cannot be displayed.
“d” Function Func.
“d” Function Func. Code Name d029 Positioning command monitor d030 Current position monitor d050 Dual monitor d060 Inverter mode monitor D080 Trip counter D081 Trip monitor 1 D082 Trip monitor 2 D083 Trip monitor 3 d084 Trip monitor 4 d085 Trip monitor 5 d086 Trip monitor 6 Description Displays the positioning command, range is –268435455~+268435455 Displays the current position, range is –268435455~+268435455 Displays two different data configured in b160 and b161.
Main Profile Parameters NOTE:. Mark “ ” in b031=10 shows the accessible parameters when b031 is set “10”, high level access. “F” Function Func. Code Name F001 Output frequency setting F002 Acceleration time (1) Description Run Mode Edit Standard default target frequency that determines constant motor speed, range is 0.0 / start frequency to maximum frequency (A004) Standard default acceleration, range is 0.01 to 3600 sec.
Standard Functions NOTE:. Mark “ ” in b031=10 shows the accessible parameters when b031 is set “10”, high level access. “A” Function Func. Code Name A001 Frequency source Description Run Mode Edit Defaults Initial data Units Eight options; select codes: 00 …POT on ext.
“A” Function Func. Code Name A015 [O] input start frequency enable A016 Analog input filter Description Two options; select codes: 00…Use offset (A011 value) 01…Use 0Hz Range n = 1 to 31, 1 to 30 : ×2ms filter 31: 500ms fixed filter with ± 0.1kHz hys. Run Mode Edit selection A020 Multi-speed freq. 0 freq. 0, A220 Multi-speed nd 2 motor A021 Multi-speed freq.
“A” Function Func. Code Name Description nd Run Mode Edit Defaults Initial data Units A242 Manual torque boost value, 2 normal V/f curve, range is 0.0 to 20.0% 1.0 % A043 Manual torque boost Sets the frequency of the V/f breakpoint A in graph (top of previous page) for torque boost, range is 0.0 to 50.0% 5.0 % 5.0 % U 00 − U 00 − 100. % 100. % 100. − 100. − 100. − 100.
“A” Function Func. Code Name a058 DC braking time at start a059 Carrier frequency during DC braking A061 Frequency upper limit A261 Frequency upper limit, 2nd motor A062 Frequency lower limit A262 Frequency lower limit, 2nd motor A063 Jump freq. (center) 1 to 3 A065 A067 A064 Jump freq. width (hysteresis) 1 to 3 A066 A068 A069 Acceleration hold frequency A070 Acceleration hold time A071 PID enable Description Sets the duration for DC braking, range is from 0.0 to 60.
“A” Function Func. Code Name Description Run Mode Edit Defaults Initial data Units A072 PID proportional gain Proportional gain has a range of 0.00 to 25.00 1.0 − A073 PID integral time constant Integral time constant has a range of 0.0 to 3600 seconds 1.0 sec A074 PID derivative time constant Derivative time constant has a range of 0.0 to 100 seconds 0.00 sec A075 PV scale conversion Process Variable (PV), scale factor (multiplier), range of 0.01 to 99.
“A” Function Func. Code Name Description nd Run Mode Edit Duration of 2 segment of acceleration, range is: 0.01 to 3600 sec. A092 Acceleration time (2) time (2), A292 Acceleration nd 2 motor Duration of 2nd segment of deceleration, range is: 0.01 to 3600 sec.
“A” Function Func. Code Name Description Run Mode Edit Defaults Initial data Units a131 Acceleration curve constant Range is 01 to 10. U 02 − a132 Deceleration curve constant Range is 01 to 10. U 02 − A141 A input select for calculate U 02 − U 03 − U 00 − 0.
“A” Function Func. Code Name a156 PID sleep function action Description Sets the threshold for the action, set range 0.0~400.0 Hz Run Mode Edit Defaults Initial data Units U 0.00 Hz a157 PID sleep function action delay Sets the delay time for the U 0.0 sec A161 [VR] input active range start U 0.00 Hz U 0.00 Hz U 0. % U 100.
Fine Tuning Functions “b” Function Func. Code Name B001 Restart mode on power failure Description Run Defaults Mode Initial data Units Edit Select inverter restart method, Five option codes: 00…Alarm output after trip, no automatic restart 01…Restart at 0Hz 02…Resume operation after frequency matching 03…Resume previous freq. after freq. matching, then decelerate to stop and display trip info 04…Resume operation after active freq.
“b” Function Func. Code Name B012 Level of electronic thermal of electronic thermal, B212 Level nd 2 characteristic Electronic thermal characteristic, 2nd motor b015 Free setting electronic thermal b016 b017 b018 b019 b020 B021 B221 ~freq.1 Free setting electronic thermal ~current1 Free setting electronic thermal ~freq.2 Free setting electronic thermal ~current2 Free setting electronic thermal ~freq.
“b” Function Func. Code Name b025 Overload restriction level 2 b026 Deceleration rate 2 at overload restriction b027 OC suppression selection B028 Current level of active freq. matching B029 Deceleration rate of active freq. matching B030 Start freq. of active freq.
“b” Function Func. Code Name b037 Function code display restriction b038 Initial display selection B039 Automatic user parameter registration B040 Torque limit selection B041 Torque limit 1 (fwd/power) Description Run Defaults Mode Initial data Units Edit Six option codes: 00…Full display 01…Function-specific display 02…User setting (and b037) 03…Data comparison display 04…Basic display 05…Monitor display only 000…Func. code that SET key pressed last displayed.
“b” Function Func.
“b” Function Func.
“b” Function Func. Code Name b096 BRD activation level Description Run Defaults Mode Initial data Units Edit U 360/ 720 b097 BRD resistor value Range is: 330 to 380V (200V class) 660 to 760V (400V class) Min.Resistance to 600.0 U Min. Resistanc e B100 Free V/F setting, freq.1 Set range, 0 ~ value of b102 U 0. Hz b101 Free V/F setting, voltage.1 Set range, 0 ~ 800V U 0.0 V b102 Free V/F setting, freq.2 Set range, value of b100 ~b104 U 0. Hz b103 Free V/F setting, voltage.
“b” Function Func. Code Name B133 Decel. overvolt. suppress B134 b145 proportional gain Decel. overvolt. suppress integral time GS input mode b150 Display ex.operator connected b160 1st parameter of Dual Monitor Description Proportional gain when b130=01. Range is: 0.00 to 5.00 Integration time when b130=01. Range is: 0.00 to 150.
Intelligent Terminal Functions “C” Function Func.
“C” Function Func.
“C” Function Func. Code Name C047 Pulse train input/output Description Run Mode Edit Defaults Initial data Units C055 Over/under-torque level If EO terminal is configured as pulse train input (C027=15), scale conversion is set in C047. Pulse-out = Pulse-in × (C047) Set range is 0.01 to 99.99 When the PV exceeds this value, the PID loop turns OFF the PID second stage output, range is 0.0 to 100% When the PV goes below this value, the PID loop turns ON the PID second stage output, range is 0.
“C” Function Func. Code Name C076 Communication error Description Selects inverter response to communications error. Five options: 00…Trip 01…Decelerate to a stop and trip 02…Disable 03…Free run stop (coasting) 04…Decelerates to a stop Sets the communications watchdog timer period. Range is 0.00 to 99.99 sec 0.0 = disabled Time the inverter waits after receiving a message before it transmits. Range is 0. to 1000.
“C” Function Func. Code Name C102 Reset selection Description Run Mode Edit Defaults Initial data Units C105 C106 C109 C111 EO gain adjustment Determines response to Reset input [RS].
“C” Function Func.
Input Function Summary Table Option Code Terminal Symbol 09 2CH 11 FRS 12 EXT Function Name 2-stage Acceleration and Deceleration Description ON OFF ON Free-run Stop OFF ON External Trip OFF Unattended Start Protection ON 13 USP 14 CS Commercial power ON source switchover OFF 15 SFT Software Lock 16 AT 18 RS 19 PTC 20 STA 21 STP 22 F/R OFF ON OFF ON Analog Input Voltage/Current Select OFF Reset Inverter ON OFF PTC thermistor ANLG Thermal Protection (C005 only) OPEN Start
Input Function Summary Table Option Code 29 Terminal Symbol UDC 31 OPE Function Name Remote Control Data Clearing Operator Control Description ON OFF ON OFF 32 SF1 Multi-speed Select, Bit operation Bit 1 Multi-speed Select, Bit operation Bit 2 Multi-speed Select, Bit operation Bit 3 Multi-speed Select, Bit operation Bit 4 Multi-speed Select, Bit operation Bit 5 Multi-speed Select, Bit operation Bit 6 Multi-speed Select, Bit operation Bit 7 Overload Restriction Source Changeover Torque Limit Sele
Input Function Summary Table Option Code 58 Terminal Symbol MI3 59 MI4 60 MI5 61 MI6 62 MI7 65 AHD 66 CP1 67 CP2 68 CP3 69 ORL 70 ORG 73 SPD 77 GS1 Trigger signal of homing Speed/position changeover GS1 input 78 GS2 GS2 input 81 485 Start EzCOM 82 PRG 83 HLD 84 ROK 85 EB 86 DISP Executing EzSQ program Retain output frequency Permission of Run command Rotation direction detection (C007 only) Display limitation 255 no Function Name General purpose input (3) Gener
Output Function Summary Table – This table shows all functions for the logical outputs (terminals [11], [12] and [AL]) at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Output Terminals” on page 36.
Option Code 21 Output Function Summary Table Terminal Function Name Description Symbol ZS Zero Hz Speed ON Output frequency falls below the threshold Detection Signal specified in C063 OFF 22 DSE Speed Deviation Excessive ON OFF 23 POK Positioning Completion ON OFF 24 FA4 Frequency Arrival Type 4–Over frequency ON OFF 25 FA5 Frequency Arrival Type 5–Set frequency ON OFF 26 OL2 Overload Advance Notice Signal 2 ON OFF 27 ODc Analog Voltage Input Disconnect Detection 28 OIDc Analog
Option Code 40 Output Function Summary Table Terminal Function Name Description Symbol WAF Cooling Fan Warning ON Lifetime of cooling fan has expired. Signal 41 FR 42 OHF OFF Lifetime of cooling fan has not expired.
Motor Constants Functions “H” Function Func.
“H” Function Func. Code Name Description constant R2, H231 Motor nd H032 H232 H033 H233 H034 H234 H050 H051 2 motor (Auto tuned data) Motor constant L (Auto tuned data) Motor constant L, 2nd motor (Auto tuned data) Motor constant I0 (Auto tuned data) Motor constant I0, 2nd motor (Auto tuned data) Motor constant J (Auto tuned data) Motor constant J, 2nd motor (Auto tuned data) Slip compensation P gain for V/f control with FB Slip compensation I gain for V/f control with FB 0.01~655.35mH 0.01~655.
“H” Function Func. Code Name Description Run Mode Edit Defaults Initial data Units PM const Ld(d-axis 0.01-655.35 [mH] U kW dependent mH PM const Lq(q-axis 0.01-655.35 [mH] U kW dependent mH 1-1000 [%] U 100 20.00-100.00 [%] U 70.00[%] 0.01-60.00 [s] U 1.
Expansion Card Functions “P” parameters will be appeared when the expansion option is connected. “P” Function Func. Code Name P001 Reaction when option card Description P026 Over-speed error detection Two option codes: 00…Inverter trips 01…Ignores the error (Inverter continues operation) Three option codes: 00…Speed reference (incl.
“P” Function Func. Code Name Description p041 Speed / Torque control Set range is 0 to 1000 ms P044 Set range is 0.00 to 99.
“P” Function P077 Encoder Run Defaults Mode Description Initial data Units Edit 0 to +268435455(Higher 4-digits +2684354 Pulse displayed) 55 s -2684354 Pulse –268435455 to 0(Higher 4-digits 55 displayed) s 00…With limitation 01…No limitation (shorter route) U 00 P004 is to be set 00 or 01 s 0.0 to 10.0 s 1.0 p100 Each set range is 0~65535 Func.
Monitoring Trip Events, History, & Conditions Trip History and Inverter Status We recommend that you first find the cause of the fault before clearing it. When a fault occurs, the inverter stores important performance data at the moment of the fault. To access the data, use the monitor function (dxxx) and select d081 details about the present fault. The previous 5 faults are stored in d082 to d086. Each error shifts d081-d085 to d082-d086, and writes the new error to d081.
Error Codes An error code will appear on the display automatically when a fault causes the inverter to trip. The following table lists the cause associated with the error. Error Code Name Cause(s) The inverter output was short-circuited, or the motor shaft is locked or has a heavy load. These conditions cause excessive current for the inverter, so the inverter output is turned OFF. The dual-voltage motor is wired incorrectly.
Error Code Name E25 Main circuit error (*3) E30 Driver error E35 Thermistor E36 Braking error E37 E38 Safe Stop E40 Operator connection E41 Modbus communication error E43 EzSQ invalid instruction E44 EzSQ nesting count error E45 E50 EzSQ instruction error Low-speed overload protection Option error (DeviceNet Communications error) If the disconnection due to the Bus-Off signal or timeout occurs during the operation using DeviceNet commands, the inverter will shut off its output and di
Error Code Name E81 Excessive speed E83 Positioning range error Cause(s) If the motor speed rises to "maximum frequency (A004) x over-speed error detection level (P026)" or more, the inverter will shut off its output and display the error code shown on the right. If current position exceeds the position range (P072-P073), the inverter will shut off its output and display the error code.
CE-EMC Installation Guidelines You are required to satisfy the EMC directive (2004/108/EC) when using an WJ200 inverter in an EU country. To satisfy the EMC directive and to comply with standard, you need to use a dedicated EMC filter suitable for each model, and follow the guidelines in this section. Following table shows the compliance condition for reference. Table 1. Condition for the compliance Model Cat. Carrier f Motor cable All WJ200 series C1 2kHz 20m (Shielded) Table 2.
4. 5. 6. 7. 8. • Ensure that the connections are metallic and have the largest possible contact areas (zinc-plated mounting plates). Avoid conductor loops that act like antennas, especially loops that encompass large areas. • Avoid unnecessary conductor loops. • Avoid parallel arrangement of low-level signal wiring and power-carrying or noise-prone conductors. Use shielded wiring for the motor cable and all analog and digital control lines.
protective conductor connection. The filter must be solidly and permanently connected with the ground potential so as to preclude the danger of electric shock upon touching the filter if a fault occurs. To achieve a protective ground connection for the filter: • Ground the filter with a conductor of at least 10 mm2 cross-sectional area. • Connect a second grounding conductor, using a separate grounding terminal parallel to the protective conductor.
Installation for WJ200 series (example of SF models) Model LFx (3-ph. 200V class) and HFx (3-ph. 400V class) are the same concept for the installation. Power supply 1-ph. 200V Metal plate (earth) The filter is a footprint type, so it is located between the inverter and the metal plate. Remove the insulation material coating of the earth contact portions so to obtain good grounding condition.
Hitachi EMC Recommendations WARNING: This equipment should be installed, adjusted, and serviced by qualified personal familiar with construction and operation of the equipment and the hazards involved. Failure to observe this precaution could result in bodily injury. Use the following checklist to ensure the inverter is within proper operating ranges and conditions. 1.
Functional Safety (Certification in Progress) Introduction The Gate Suppress function can be utilized to perform a safe stop according to the EN60204-1, stop category 0 (Uncontrolled stop by power removal). It is designed to meet the requirements of the ISO13849-1, PL=d only in a system in which EDM signal is monitored by an “external device monitor”.
(When safety switch or EDM switch is turned off, the intelligent input and output terminal assigned on will be set as "no" function, and contact will remain normally off.) Always use both inputs to disable the drive. If for any reason only one channel is opened, the drive output is stopped but the EDM output is not activated. In this case the Safe Disable input wiring must be checked. Installation According to the safety standard listed above, please install referring to the example.
Wiring example When the Gate Suppress function is utilized, connect the drive to a safety certified interrupting device utilizing EDM output signal to reconfirm both safety inputs GS1 and GS2.
Inverter doesn’t block the current flowing into itself when it is not powered. This may cause the closed circuit when two or more inverters are connected to common I/O wiring as shown below to result in unexpected turning the on the input. This may lead to dangerous situation. To avoid this closed circuit, please put the diode (rated:50V/0.1A) in the path as described below.
Components to be combined Followings are the example of the safety devices to be combined. Series Model Norms to comply Certification date GS9A 301 ISO13849-2 cat4, SIL3 06.06.2007 G9SX GS226-T15-RC IEC61508 SIL1-3 04.11.2004 NE1A SCPU01-V1 IEC61508 SIL3 27.09.