Brochure

25
Note 1: Field wiring must be made by a UL-Listed and CSA-certied closed-loop terminal connector sized for the wire gauge involved.
Connector must be xed by using the crimping tool specied by the connector manufacturer.
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66ft. (20 m).
Note 4: Use 18 AWG / 0.75mm
2
wire for the alarm signal wire ([AL0], [AL1], [AL2] terminals).
Power Supply
R S T
PD
P
RB
N
U V W
IM
Inverter
Motor
Fuse
Input
Voltage
Motor Output
Inverter
Model
Wiring
Fuse
(UL-rated,
class J, 600V)
Circuit
Breaker
(Inverse Time)
kW HP
Power Lines Signal Lines
VT CT VT CT
1-phase
100V
0.4 1/2 WJ200-004MF AWG12/3.3mm
2
(75
°
C only)
18 to 28 AWG /
0.14 to 0.75 mm
2
shielded wire
(see Note 4)
50A 30A
0.75 1 WJ200-007MF AWG10/5.3mm
2
(75
°
C only)
1-phase
200V
0.2 0.1 1/4 1/8 WJ200-001SF
AWG16 / 1.3mm
2
(75
°
C only) 10A
30A
0.4 0.2 1/2 1/4 WJ200-002SF
0.55 0.4 3/4 1/2 WJ200-004SF
1.1 0.75 1.5 1 WJ200-007SF AWG12 / 3.3mm
2
(75
°
C only) 20A
2.2 1.5 3 2 WJ200-015SF
AWG10 / 5.3mm
2
30A
3.0 2.2 4 3 WJ200-022SF
3-phase
200V
0.2 0.1 1/4 1/8 WJ200-001LF
AWG16 / 1.3mm
2
10A
30A
0.4 0.2 1/2 1/4 WJ200-002LF
0.75 0.4 1 1/2 WJ200-004LF
1.1 0.75 1.5 1 WJ200-007LF
15A
2.2 1.5 3 2 WJ200-015LF
AWG14 / 2.1mm
2
(75
°
C only)
3.0 2.2 4 3 WJ200-022LF AWG12 / 3.3mm
2
(75
°
C only) 20A
5.5 3.7 7.5 5 WJ200-037LF AWG10 / 5.3mm
2
(75
°
C only) 30A
7.5 5.5 10 7.5 WJ200-055LF
AWG6 / 13mm
2
(75
°
C only) 60A
100A
11 7.5 15 10 WJ200-075LF
15 11 20 15 WJ200-110LF AWG4 / 21mm
2
(75
°
C only)
80A
18.5 15 25 20 WJ200-150LF AWG2 / 34mm
2
(75
°
C only)
3-phase
400V
0.75 0.4 1 1/2 WJ200-004HF
AWG16 / 1.3mm
2
10A
20A
1.5 0.75 2 1 WJ200-007HF
2.2 1.5 3 2 WJ200-015HF
3.0 2.2 4 3 WJ200-022HF
AWG14 / 2.1mm
2
4.0 3.0 5 4 WJ200-030HF
15A
5.5 4.0 7.5 5 WJ200-040HF AWG12 / 3.3mm
2
(75
°
C only)
7.5 5.5 10 7.5 WJ200-055HF
AWG10 / 5.3mm
2
(75
°
C only) 30A
40A
11 7.5 15 10 WJ200-075HF
15 11 20 15 WJ20 0 -110HF AWG6 / 13mm
2
(75
°
C only)
50A
18.5 15 25 20 WJ200-15 0HF AWG6 / 13mm
2
(75
°
C only)
Name Function
Input-side AC Reactor
This is useful in suppressing harmonics induced on the power supply lines and
for improving the power factor.
WARNING: Some applications must use an input-side AC Reactor to prevent
inverter damage. See Warning on next page.
EMC lter
(for CE applications, see Appendix D)
Reduces the conducted noise on the power supply wiring between the inverter
and the power distribution system. Connect to the inverter primary (input) side.
Radio noise lter
Electrical noise interference may occur on nearby equipment such as a radio
receiver. This magnetic choke lter helps reduce radiated noise (can also be used
on output).
Radio noise lter
(use in non-CE applications)
This capacitive lter reduces radiated noise from the main power wires in the
inverter (input) side.
DC link choke
Suppress harmonics generated by the inverter. However, it will not protect the
input diode bridge rectier.
Braking register This is useful for increasing the inverter's control torque for high duty-cycle (on-
off) applications, and improving the decelerating capability.
Braking unit
Output side nose lter Reduces radiated noise from wiring in the inverter output side.
Radio noise lter
Electrical noise interference may occur on nearby equipment such as a radio
receiver. This magnetic choke lter helps reduce radiated noise (can also be used
on input).
Output-side AC Reactor
This reactor reduces the vibration in the motor caused by the inverter’s switching
waveforms, by smoothing the waveform to approximate commercial power
quality. It is also useful to reduce harmonics when wiring from the inverter to
the motor is more than 10 m in length.
LCR lter Sine wave shaping lter for output side.
Wiring and Accessories